background image

V130-33-B1 Installation Guide

4

Unitronics 

DIN-rail Mounting

1. Snap the controller onto the DIN 

rail as shown in the figure to the 
right. 

2. When properly mounted, the 

controller is squarely situated on 
the DIN-rail as shown in the figure 
to the right. 

Wiring 
 

Do not touch live wires. 

Install an external circuit breaker. Guard against short-circuiting in external wiring. 
Use appropriate circuit protection devices. 
Unused pins should not be connected. Ignoring this directive may damage the device. 
Double-check all wiring before turning on the power supply. 

Caution

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm). 
Do not use tin, solder, or any substance on stripped wire that might cause the wire strand 
to break. 
Install at maximum distance from high-voltage cables and power equipment. 

Wiring Procedure

Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 

2

–3.31 mm

2

): 

1.  Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  
2.  Unscrew the terminal to its widest position before inserting a wire.  
3.  Insert the wire completely into the terminal to ensure a proper connection. 
4.  Tighten enough to keep the wire from pulling free. 

Input or output cables should not be run through the same multi-core cable or share the same wire.
Allow for voltage drop and noise interference with input lines used over an extended distance.  Use 
wire that is properly sized for the load. 
The controller and I/O signals must be connected to the same 0V signal. 

 

Содержание Vision OPLC V130-33-B1

Страница 1: ...his mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information Mode press the i button for several seconds Programming Software Utilities The Unitronics Setup CD contains VisiLogic software and other utilities VisiLogic Easily configure hardware and write both HMI and Ladder control applications ...

Страница 2: ...onics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters ...

Страница 3: ...ller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure ...

Страница 4: ... kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Inse...

Страница 5: ...wer supply connect one end of a 14 AWG wire to the chassis signal connect the other end to the panel Note If possible the wire used to earth the power supply should not exceed 10 cm in length However it is recommended to earth the controller in all cases Communication Port Turn off power before making communications connections Caution Signals are related to the controller s 0V the same 0V is used...

Страница 6: ...gnal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Pin 1 Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapted to RS485 Pin 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B RS232 to RS485 Jumper Settings The figure to the right shows the jumper factory default settings RS232 RS485 termination ON Note that in ...

Страница 7: ...ntroller 1 Gently replace the board Make certain that the pins fit correctly into their matching receptacle Do not force the board into place doing so may damage the controller 2 Replace the back cover of the controller and fasten the corner screws Note You must replace the back cover securely before powering up the controller Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 ...

Отзывы: