3 Electrical installation
P3 240-840A
15
A
ttention:
The order of the connections to the connector numbers or screw terminals is
obligatory. All further advice is non-obligatory.
The input and output conductors may be altered or supplemented in accordance
with the electrical standards.
Note:
- Connection and operating instructions
- Local regulations
- EU guideline 89/392/EWG
- VDE and TÜV regulations and Trade body guidelines
Switch on
the auxiliary voltage and the supply voltage simultaneously.
Switch off
the supply voltage after the auxiliary voltage
Input filter
see CE advice, page 14
Short conductor length to be used between the input filter and the device
Auxiliary voltage connection
Connection
terminal X5:11, X5:12
Power supply
400V~ ±15%
Special voltages
24V~, 110V~, 230V~, 500V~
Input current
max. 300mA
Phase position
regardless
Internal fuses
FE1, FE2 0.8AT
- Min. line cross-section 0.5mm²
- External fuse
- Min. line protection 6A
Note:
Observe the respective type plate.
Control voltage XXX
Po
w
er
su
p
p
ly
Содержание Classic P3 Series
Страница 13: ...3 Electrical Installation P3 240 840A 13 Connection diagram...
Страница 18: ...Classic P3 x x 240 840A 18 Free...
Страница 23: ...3 Electrical Installation P3 240 840A 23 Circuit diagramm...
Страница 33: ...8 Drawings P3 240 840A 33 Dimensions P3 240 360A...