-5-
CLEARANCES TO COMBUSTIBLES
It is of utmost importance that the clearances to combustible materials be strictly adhered to during installation
of the stove.
A
B
SIDEW
ALL
F
E
C
D
BACK W
ALL
G
J
H
Key
in
mm
A
Sidewall To Flue
23
585
B
Sidewall To Stove
14
356
C
Ceiling Height
84
2134
D
Top Of Stove To Ceiling
50.5
1283
E
Back Wall To Flue
18
458
F
Back Wall To Stove
28
712
G
Wall To Corner (Angled Installation)
18
458
H
Wall To Corner Fuel Loading Side (Angled Installation)
18
458
J
Wall To Flue (Angled Installation)
18
458
L
K
M
N
P
P
Floor Protector
BACK WALL
SIDEW
ALL
Key
in
mm
K
Front
8
204
L
Rear
8
204
M
Fuel Loading Side
16 (USA)
18 (CAN)
407 (USA)
458 (CAN)
N
Left Side
8
204
P
Flue Pipe
2
51
Note: When choosing a location for this unit, make sure
there is enough space available to fully open the door.
•
Floor to ceiling height must be at least 7’ (2.13 m) in all cases.
•
Do not place any combustible material within 4’ (1.2 m) of the front of the unit.
•
The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue pipe.
•
The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
floor, or a ceiling.
•
For Canadian installations, where passage through a wall, or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365.
•
A flue pipe crossing a combustible wall must have a minimum clearance of 18” (458 mm).
•
To reduce flue clearances from combustible materials, contact your local safety department.
•
The provision that clearances may only be reduced by means approved by regulatory authority
FLOOR PROTECTOR
This heater must have a non-combustible floor protector with a minimum type 1 ember protection extending
beneath the heater if the floor is constructed of combustible material. If a floor pad is used, it should be UL
listed or equal. The floor protector should be large enough to extend under the stove and beyond each side
as indicated. If there is a horizontal run of flue pipe, there needs to be floor protection under it that extends two
inches beyond either side of the pipe.