THROUGH THE WALL INSTALLATION 

(RECOMMENDED INSTALLATION)

TYPICAL THROUGH THE 

WALL INSTALLATION

Canadian installations must conform to CAN/CSA-B365. 

To vent the unit through the wall, connect the pipe 

adapter to the exhaust motor adapter. If the exhaust 

adapter is at least 18” (457 mm) above ground level, a 

straight section of pellet vent pipe can be used through 

the wall. Your heater dealer should be able to provide 

you with a kit that will handle most of this installation, 

which will include a wall thimble that will allow the proper 

clearance through a combustible wall. Once outside the 

structure, a 3” (76 mm) clearance should be maintained 

from the outside wall and a clean out tee should be 

placed on the pipe with a 90-degree turn away from the 

house. At this point, a 3ft (0.91m) (minimum) section of 

pipe should be added with a horizontal cap, which would 

complete the installation. A support bracket should be 

placed just below the termination cap or one every 4ft 

(1.22m) to make the system more stable. If you live in an 

area that has heavy snowfall, it is recommended that the 

installation be taller than 3ft (0.91m) to get above the 

snowdrift line. This same installation can be used if your 

heater is below ground level by simply adding the clean-

out section and vertical pipe inside until ground level is 

reached. With this installation you have to be aware of the 

snowdrift line, dead grass, and leaves. We recommend 

a 3ft (0.91m) minimum vertical rise on the inside or 

outside of the house. The “through the wall” installation 

is the least expensive and simplest installation. Never 

terminate the end vent under a deck, in an alcove, under 

a window, or between two windows. We recommend 

Simpson Dura-Vent® or Metal-Fab® kits.

THROUGH THE ROOF/CEILING 

INSTALLATION

•  When venting the heater through the ceiling, the pipe 

is connected the same as through the wall, except the 

clean-out tee is always on the inside of the house, and a 

3” (76 mm) adapter is added before the clean-out tee. 

•  You must use the proper ceiling support flanges and 

roof flashing (supplied by the pipe manufacturer; follow 

the pipe manufacturer’s directions). It is important to 

note that if your vertical run of pipe is more than 12ft 

(3.7m), the pellet vent pipe size should be increased to 

4” (102 mm) in diameter. 

•  Do not exceed more than 4ft (1.22m) of pipe on a 

horizontal run and use as few elbows as possible. If 

an offset is required, it is better to install 45-degree 

elbows rather than 90-degree elbows.

INSTALLATION

Содержание KP130

Страница 1: ...lding or fire officials about permits restrictions and installation requirements in your area NEVER OPERATE THIS PRODUCT WHILE UNATTENDED CAUTION Please read this entire manual before you install or u...

Страница 2: ...s burning wood pellet fuel this heater has been shown to deliver heat at a rate of 8 932 to 25 701 Btu hr This heater achieved a particulate emissions rate of 1 3 g hr when tested to method ASTM E 277...

Страница 3: ...and_____________________________________________ If no Date of inspection of existing venting system ________________________________________________________________ COMMISSIONING Confirm Hearth Pad I...

Страница 4: ...OR IS REQUIRED THIS UNIT MUST BE PLUGGED INTO A 110 120V 60 HZ GROUNDED ELECTRICAL OUTLET DO NOT USE AN ADAPTER PLUG OR SEVER THE GROUNDING PLUG DO NOT ROUTE THE ELECTRICAL CORD UNDERNEATH IN FRONT OF...

Страница 5: ...behind the stove Floor protection must extend under and 2 51 mm to each side of the chimney tee for an interior vertical installation A Floor Protector of 1 26 mm thick is recommended for this instal...

Страница 6: ...ate paint or protective coating to ensure grounding Vent must be 3 or 4 inch PL Vent and must extend a minimum or 36 914 mm above the roof line of the mobile home and must be installed using a certifi...

Страница 7: ...pellet vent pipe is not furnished with the unit and must be purchased separately PELLET VENT INSTALLATION The installation must include a clean out tee to enable collection of fly ash and to permit pe...

Страница 8: ...d void your warranty HORIZONTAL EXHAUST VENT INSTALLATION 1 Locate your pellet stove in a location which meets the requirements of this manual but in an area where it does not interfere with the house...

Страница 9: ...o get above the snowdrift line This same installation can be used if your heater is below ground level by simply adding the clean out section and vertical pipe inside until ground level is reached Wit...

Страница 10: ...ll with too much fuel and the fire will smother out To much air will result in a flame that is overactive or aggressive The flame in this situation is typically very blue at the bottom and resembles a...

Страница 11: ...ordance to the heat range setting However this speed can be manually operated by pressing the Draft Fan arrows up or down Draft Fan when pressed the display will show Df A which is automatic Press the...

Страница 12: ...the stove cycle between the preselected desired heat range setting 1 to 5 and the minimum heat range setting of 1 The T Stat will not turn the stove on and off When the desired room temperature has be...

Страница 13: ...reduced performance Store your pellets in a dry place DO NOT store the fuel within the installation clearances of the unit or within the space required for refuelling and ash removal Doing so could re...

Страница 14: ...RN MAY ARISE FROM SPARKS OR FUMES ENTERING THE ROOM THE DOOR MUST BE CLOSED AND SEALED DURING OPERATION If the door is opened while the stove is in operation it must be closed within 30 seconds or the...

Страница 15: ...cally remove and clean the burn pot and the area inside the burn pot housing In particular it is advisable to clean out the holes in the burn pot to remove any build up that may prevent air from movin...

Страница 16: ...rush specifically designed for the type of chimney in use A qualified chimney sweep can perform this service It is also recommended that before each heating season the entire system be professionally...

Страница 17: ...gloves carefully remove any loose pieces of glass from the door frame 4 Replace the glass and gasket making sure the gasket runs the full perimeter of the glass edge 5 Re install the retainer and eigh...

Страница 18: ...d or replace door gaskets Check that all outside connections are clear of any obstructions Check the exhaust system clean as needed Checkthatthepressureswitchconnectiontothefireboxisfreeofashorclearof...

Страница 19: ...he stove is in the Shut Down state waiting for the off button or for a 15 minute period after the stove was turned off or for the stove to cool down or for the door to be closed Flashing dash in Heat...

Страница 20: ...Clear Glass 1 3 88324 1 Rope Gasket 1 4 69762 Burnpot Assembly 1 5 80780 IR Remote 1 6 88168 Burnpot Housing Gasket 1 7 80778 Circuit Board Assy 1 8 88117 Exhaust Duct Gasket 1 9 88118 Ignitor Flange...

Страница 21: ...s are ordered Before contacting customer service write down the model number and the serial number of this unit That information can be found on the certification label attached to the back of the uni...

Страница 22: ..._____ Engineer Name _____________________________________ License No _________________________________________ Company ___________________________________________ Telephone No ________________________...

Страница 23: ...2021 United States Stove Company 23 NOTES...

Страница 24: ...24 2021 United States Stove Company NOTES...

Страница 25: ...2021 United States Stove Company 25 NOTES...

Страница 26: ..._____________________ Service de 07 Date ______________________ Nom de l ing nieur _________________________________ N de licence ______________________________________ Compagnie _____________________...

Страница 27: ...RIQUE BLANC NOIR PCB ALLUMEUR PRESSOSTAT MARRON MARRON NOIR BLANC ROUGE BLEU ORANGE PRISE MOLEX AU CIRCUIT IMPRIM PCB PRINCI PAL NOIR NOIR NOIR BLANC BLANC SOUFFLANTE DE DISTRIBUTION VENTILATEUR D VAC...

Страница 28: ...rcuit Board Assy 1 8 88117 Joint de conduit d chappement 1 9 88118 Joint de bride d allumage 1 10 80607 Cartouche d allumage 1 11 80549 Pressostat 1 12 80472 Ventilateur de distribution 1 13 88106 Joi...

Страница 29: ...t deux fois par seconde Cela indique que le po le fonctionne normalement et qu une condition de temp rature excessive existe provoquant l arr t du combustible Indicateur de r glage du niveau de chaleu...

Страница 30: ...st me vis sans fin est bloqu ou il y a une vo te de combustible dans la tr mie qui emp che le combustible de s couler dans le syst me d approvisionnement vis sans fin PROBL ME CAUSE L allumeur automat...

Страница 31: ...re sont sp cifiques votre appareil Lors de la commande de pi ces de rechange les informations contenues dans ce manuel vous aideront vous assurer que les bons articles sont command s Avant de contacte...

Страница 32: ...verre N UTILISEZ PAS de nettoyants abrasifs N effectuez PAS le nettoyage lorsque la vitre est CHAUDE N essayez pas de faire fonctionner l appareil avec du verre bris Le verre de remplacement peut tre...

Страница 33: ...p cialement con ue pour le type de chemin e utilis Un ramoneur qualifi peut fournir ce service Il est galement conseill d inspecter de nettoyer et si n cessaire de r parer la totalit du syst me avant...

Страница 34: ...int et la mention E2 s affiche sur l cran deux chiffres Le po le doit s arr ter compl tement avant de pouvoir tre red marr CHAMBRES INT RIEURES Pot de combustion Retirez et nettoyez p riodiquement le...

Страница 35: ...le voyant vert s allume 3 Ajustez la vitesse d alimentation au r glage souhait en appuyant sur le bouton Avance du niveau de chaleur Si le feu ne d marre pas dans 12 minutes appuyez sur Marche Arr t...

Страница 36: ...inf rieur 300 parties par million Les granul s mous contenant une quantit excessive de sciure de bois en vrac qui ont t ou sont mouill s r duiront les performances Rangez vos pellets dans un endroit...

Страница 37: ...entre le r glage pr s lectionn de la plage de chaleur d sir e 1 5 et le r glage de la plage de chaleur minimale de 1 Le T Stat n allumera ni ne teindra le po le Lorsque la temp rature ambiante souhai...

Страница 38: ...de chaleur Cependant cette vitesse peut tre r gl e manuellement en appuyant sur les fl ches haut et bas du ventilateur de tirage Draft Fan Lorsque le bouton Draft Fan ventilateur de tirage est appuy...

Страница 39: ...ant une dur e suffisante le pot de combustion se remplira avec trop de combustible et le feu s touffera Trop d air provoquera une flamme hyperactive ou agressive La flamme dans cette situation est g n...

Страница 40: ...chutes de neige il est recommand que l installation soit plus grand que 3 pieds 0 91 m pour obtenir au dessus de la ligne de cong re Cette m me installation peut tre utilis e si votre chauffe eau est...

Страница 41: ...re garantie ECHAPPEMENT HORIZONTALES INSTALLATION 1 Localisez votre po le granul s dans un endroit qui r pond aux exigences de ce manuel mais dans une zone o il ne g ne pas la charpente de la maison l...

Страница 42: ...volantes et pour permettre le nettoyage p riodique du syst me d chappement Les coudes 90 degr s accumulent les cendres volantes et la suie r duisant ainsi le d bit d chappement et les performances du...

Страница 43: ...e la maison mobile et doit tre install l aide d un coupe feu de plafond certifi et d un chapeau de pluie Lors du d m nagement de votre maison mobile toute ventilation ext rieure doit tre enlev e penda...

Страница 44: ...grand pour s tendre sur au moins 6 po 153 mm l avant 6 po 153 mm de chaque c t et 1 po 26 mm derri re le po le La protection du plancher doit s tendre sous et 2 po 51 mm de chaque c t du t de chemin...

Страница 45: ...E PRISE ET NE COUPEZ PAS LA FICHE DE TERRE N ACHEMINEZ PAS LE CORDON LECTRIQUE SOUS DEVANT OU SUR LE PO LE NE FAITES PAS COURIR LE CORDON LECTRIQUE DANS LES ZONES DE PASSAGE ET NE LE COINCEZ PAS SOUS...

Страница 46: ...n date d inspection du syst me de ventilation existant ___________________________________________________________________ MISE EN SERVICE Confirmer l installation du tapis de foyer conform ment aux i...

Страница 47: ...Pellet peut effectuer le taux r el d alimentation en carburant et de br ler fois Taux d alimentation en carburant peut varier par autant que 20 Utiliser PFI carburant list pour de meilleurs r sultats...

Страница 48: ...fortune lors de l installation de ce radiateur Contactez les responsables locaux du b timent ou des pompiers pour conna tre les permis les restrictions et les exigences d installation dans votre r gio...

Отзывы: