IM_1XTXSW-08
www.ueonline.com
18
HART Commands Cont.
Command
Description
Type
59
Write Number of Response Preambles
Common Practice
71
Lock Device
Common Practice
76
Read Lock Device State
Common Practice
140
Write Field Stats Information
Overwrites the Max and Min values from the device.
Device Specific
141
Read Field Stats Information
Reads the current Max and Min values from the device.
Device Specific
221
Write Protect Enable/Disable, Modify Password
Allows write protect mode to be enabled/disabled and allows editing of the
device password.
Device Specific
222
Read, Write Protect Status
Reads the write protect status of the device.
Device Specific
223
Write Trip Counters
Writes an unsigned 16-bit integer between 0 – 9999 to the trip counters associ-
ated with switch 1 and switch 2 (Trips 1 and 2).
Device Specific
224
Trips 1 and 2
Reads the value of the trip counters associated with switch 1 and switch 2 (Trips 1
and 2). The number is an unsigned 16-bit integer between 0 – 9999.
Device Specific
225
Manual Reset
Resets one or more switches that are in the latched state.
Device Specific
226
Read Switch Latch Status
Reads the latch status of one or more switches.
Device Specific
244
Write Switch Configuration
Write Switch Number, Mode, Set Points, Deadbands, Latch Settings, Trip Delay
Settings
Device Specific
245
Read Switch Configuration
Read Switch Number, Mode, Set Points, Deadbands, Latch Settings, Trip Delay
Settings
Device Specific
246
Write Plugged Port Settings
Enable/Disable Plugged Port Feature, set plugged port time and threshold.
Device Specific
247
Read Plugged Port Settings
Read Plugged Port time and threshold.
Device Specific
248
Write Offset and Span
Writes offset and span values for the purpose of calibration to the offset and
span menu entries.
Device Specific
249
Read Offset and Span
Reads offset and span values from the device.
Device Specific
Table 5