WIRING

fIeld  wIrIng  MusT  be  raTed  90°c  MInIMuM.  for  aMbIenT 

TeMperaTures below -10°c, use suITable fIeld wIrIng.

dIsconnecT  all  supply  cIrcuITs  before  wIrIng  unIT. 

wIre  unITs  accordIng  To  naTIonal  and  local  elec-

TrIcal  codes.  MaxIMuM  recoMMended  wIre  sIze  Is 

14   awg.    The  recoMMended  TIghTenIng  Torque  for  fIeld  wIrIng  

TerMInals Is 7 To 17 In-lbs.

elecTrIcal raTIngs sTaTed In lITeraTure and on naMeplaTes 

MusT  noT  be  exceeded—overload  on  a  swITch  can  cause 

faIlure on The fIrsT cycle.  

To  prevenT  seIzure  of  enclosure  cover,  do  noT  reMove 

lubrIcanT. Threads should also be free of dIrT, eTc. 

The  exTernal  groundIng  TerMInal  Is  noT  To  be  used  as 

The prIMary equIpMenT groundIng TerMInal.  The InTernal 

groundIng TerMInal shall be used as The prIMary equIp-

MenT  groundIng  Means  and  The  exTernal  groundIng  TerMInal 

Is  only  for  a  suppleMenTal  (secondary)  groundIng  connecTIon 

where local auThorITIes perMIT or requIre such a connecTIon.

remove  cover  and  wire  control  according  to  product  configuration  (see 

figure 4).  wire directly to the terminal block.  an internal grounding terminal 

is  located  near  the  right-hand  conduit  opening.    replace  cover  and  hand 

tighten to fully engage cover o-ring.

ORN

YEL

RED

TYPES B122, E122, E122P

BLU

VLT

BLK

NOTE 

REVERSE 

WIRING OF 

LOW SWITCH

N.C.

N.O.

COM.

N.C.

N.O.

COM.

2SPDT

N.C.

N.O.

COM.

Plunger

TYPES B121, C120, E121, F120, 820E

SPDT

N.C.1

N.C.2

N.O.1

N.O.2

COM. 1

COM. 2

Plunger

RED

YEL.

ORN.

OPTION 1010, 1190, 1195

(FOR TYPE B121, C120, E121, F120 ONLY)

DPDT

N.C.

N.O.

COM.

N.C.

N.O.

COM.

TYPE 822E

#1

#2

NC NO COM NC NO COM

SWT#2

SWT#1

BLK BLU VLT RED ORN YEL

Breather Drain Option M450: Types C120, F120 

  

Mount with breather drain facing down (see figure 1). The conduit connec-

tion must be properly sealed (potted) for this type of installation.

Breather Drain Option M450: Types B121, B122, E121 & E122, E122P

Mount in vertical position with temperature assembly and breather drain fac-

ing down  (see figure 2).

820E and 822E

 type units must be surface mounted.  drill mounting holes 

per figure 3.

If a seal fitting is required, install the nipple and the seal fitting prior to sur-

face mounting the controller. 

Mounting Bulb and Capillary

fully immerse the bulb and 6” of capillary in the control zone.  for best con-

trol it is generally desirable to place the bulb close to the heating or cooling 

source in order to sense temperature fluctuations quickly.  be sure to locate 

the bulb so it will not be exposed to temperature beyond the instruments 

range limits.
avoid bending or coiling the capillary tube tighter than 1/2” radius. exercise 

caution when making bends near the capillary ends. 
If a separable well or union connector is used follow separate instructions 

included with them.

Figure 2:  Types B121, 

B122, E121, E122, E122P

F

igure 3:  820E, 822E Mounting

clearance for 1/4 screw (4) places

Figure 4

use 90°c copper conductors only. 
recommended tightening torque for 
field wiring terminals is 7-17 in-lbs.

Figure 1:  Types C120, F120

Содержание 120 Series

Страница 1: ...om Date code format on nameplate is YYWW for year and week TOOLS NEEDED Screwdriver Adjustable Wrench to 1 1 2 MOUNTING The connection of the device shall be made by cable entries or a stopping box certified in type of explosion protection flameproof enclosure d suitable for the conditions of use and correctly installed to prevent ignition seal all conduit runs within 18 inches of enclosure Always...

Страница 2: ...C 2 N O 1 N O 2 COM 1 COM 2 Plunger RED YEL ORN OPTION 1010 1190 1195 FOR TYPE B121 C120 E121 F120 ONLY DPDT N C N O COM N C N O COM TYPE 822E 1 2 NC NO COM NC NO COM SWT 2 SWT 1 BLK BLU VLT RED ORN YEL Breather Drain Option M450 Types C120 F120 Mount with breather drain facing down See Figure 1 The conduit connec tion must be properly sealed potted for this type of installation Breather Drain Opt...

Страница 3: ...bly movement Connect test lights to indicate switch operation or listen for the switch to click Loosen adjustment A and move the Adjustment Pointer until it agrees with the Indicating Pointer When the switch clicks re tighten the screw NOTE Type 822E has a single knob and pointer for both switches Both switches are standardly factory set together within 5 of the dial range Turning the knob positio...

Страница 4: ...ove to the left if capillary is to be added to the process or to the right if capillary is to be removed from process Type E121 E122 E122P F120 Models 1BS 8BS Remote Mount Temperature Assembly Type B121 B122 C120 Models 120 121 Direct Mount Temperature Assembly Added to or taken away from the process Model Number Range Cap Length Division 1 180 to 120 F 2 ft 2 125 to 350 F 1 1 2 ft 3 125 to 500 F ...

Страница 5: ... Model Inches mm 1BS 3 3 4 95 3 2BS 2 5 8 66 7 3BS 2 1 8 54 0 4BS 6 3 4 171 5 5BS 5 127 0 6BS 4 1 2 114 3 7BS 3 76 2 8BS 3 1 4 82 6 3 1 2 88 9mm 3 3 16 81 0mm 7 177 8mm 6 3 8 161 9mm 1 3 16 30 2mm 9 228 6mm 14 11 16 373 1mm 4 11 16 119 3mm 1 11 16 43 2mm 2 1 4 57 5mm 1 17 32 38 9mm 3 8 9 5mm A 7 8 22 2mm BULB SET POINT ADJUSTMENT KNOB SET POINT INDICATING POINTER RED CLEARANCE FOR 1 4 SCREW 4 MT G...

Страница 6: ... before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon del...

Отзывы: