IMT120-10

correct  any  difference  between  the  Indicating  pointer  and  the  test 

thermometer by holding the compensator with a 5/16” wrench while turning 

the  zero  adjustment  “c”  on  the  thermal  assembly  with  a  second  5/16” 

wrench, per figure 7 until the brown Indicating pointer reads the same as 

the test thermometer. Turning clockwise lowers indicated reading. compare 

the  process  temperature  with  the  set  point  adjustment  pointer.  loosen 

adjustment screw “a” to align set point adjustment pointer with the Indicating 

pointer. re-tighten screw “a”.

Correction of Capillary (820E, 822E)

If the length of capillary immersed in the process differs from the amount 

immersed (6”, see Mounting bulb & capillary in part I - Installation) at the 

factory calibration bath, a calibration shift will occur. The error may be cor-

rected as follows:
Move  set  pointer  to  the  highest  temperature  setting.  note  indicating  scale 

reading  with  the  head  and  sensor  at  room  temperature.  loosen  the  two 

thermal assembly mounting screws. re-position the housing index against the 

calibration on the instrument case (or skeleton casting) at a rate of 1 divi-

sion line per capillary length listed in figure 8. Move to the left if capillary is 

to be added to the process, or to the right if capillary is to be removed from 

process. 

Type E121, E122, 
E122P, F120
Models 1BS-8BS
REMOTE MOUNT 

TEMPERATURE

ASSEMBLy

Type B121, B122, C120
Models 120-121
DIRECT MOUNT

TEMPERATURE ASSEMBLy

*added to or taken away from the process

Model 
number

range

cap length/
division*

1

-180 to 120

°

f

2 ft

2

-125 to 350

°

f

1 1 /2 ft

3

-125 to 500

°

f

1 ft

4

-40 to 120

°

f

4 ft

5

-40 to 180

°

f

3 ft

6

0 to 250

°

f

2 1/2 ft

7

0 to 400

°

f

2 ft

8

50 to 650

°

f

2 ft

Figure 8

zONE hAzARDOUS LOCATIONS FLAMEPROOF GAP AND jOINT

DETAILS

120’S

activation plunger to adjustment screw hole gap joints: 1.140” min length by 

0.0039” max annular gap

plunger  guide  to  enclosure  through  threaded  joints:  minimum  8  ½  fully 

engaged threads

cover  to  enclosure  through  threaded  joints:  minimum  7  ½  fully  engaged 
threads

121’S & 122’S 

activation plunger to enclosure through hole gap joints: 1.000” min length by 

0.0030” max annular gap

adjustment  shaft  to  shaft  through  hole  gap  joints:  1.050”  min.  length  by 

0.0035” max. annular gap

cover  to  enclosure  through  threaded  joints:  minimum  7  ½  fully  engaged 
threads

MANUAL RESET OPTION 1530 (120’S,121’S)

reset  pivot  to  pivot  guide  through  hole  gap  joints:  1.118”  min.  length  by 

0.0036” max annular gap

reset guide to enclosure through threaded joints: 8 fully engaged threads

Figure 7:  Indicating Enclosure Internals

Содержание 120 Series

Страница 1: ...om Date code format on nameplate is YYWW for year and week TOOLS NEEDED Screwdriver Adjustable Wrench to 1 1 2 MOUNTING The connection of the device shall be made by cable entries or a stopping box certified in type of explosion protection flameproof enclosure d suitable for the conditions of use and correctly installed to prevent ignition seal all conduit runs within 18 inches of enclosure Always...

Страница 2: ...C 2 N O 1 N O 2 COM 1 COM 2 Plunger RED YEL ORN OPTION 1010 1190 1195 FOR TYPE B121 C120 E121 F120 ONLY DPDT N C N O COM N C N O COM TYPE 822E 1 2 NC NO COM NC NO COM SWT 2 SWT 1 BLK BLU VLT RED ORN YEL Breather Drain Option M450 Types C120 F120 Mount with breather drain facing down See Figure 1 The conduit connec tion must be properly sealed potted for this type of installation Breather Drain Opt...

Страница 3: ...bly movement Connect test lights to indicate switch operation or listen for the switch to click Loosen adjustment A and move the Adjustment Pointer until it agrees with the Indicating Pointer When the switch clicks re tighten the screw NOTE Type 822E has a single knob and pointer for both switches Both switches are standardly factory set together within 5 of the dial range Turning the knob positio...

Страница 4: ...ove to the left if capillary is to be added to the process or to the right if capillary is to be removed from process Type E121 E122 E122P F120 Models 1BS 8BS Remote Mount Temperature Assembly Type B121 B122 C120 Models 120 121 Direct Mount Temperature Assembly Added to or taken away from the process Model Number Range Cap Length Division 1 180 to 120 F 2 ft 2 125 to 350 F 1 1 2 ft 3 125 to 500 F ...

Страница 5: ... Model Inches mm 1BS 3 3 4 95 3 2BS 2 5 8 66 7 3BS 2 1 8 54 0 4BS 6 3 4 171 5 5BS 5 127 0 6BS 4 1 2 114 3 7BS 3 76 2 8BS 3 1 4 82 6 3 1 2 88 9mm 3 3 16 81 0mm 7 177 8mm 6 3 8 161 9mm 1 3 16 30 2mm 9 228 6mm 14 11 16 373 1mm 4 11 16 119 3mm 1 11 16 43 2mm 2 1 4 57 5mm 1 17 32 38 9mm 3 8 9 5mm A 7 8 22 2mm BULB SET POINT ADJUSTMENT KNOB SET POINT INDICATING POINTER RED CLEARANCE FOR 1 4 SCREW 4 MT G...

Страница 6: ... before use Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published limits LIMITED WARRANTY Seller warrants that the product hereby purchased is upon del...

Отзывы: