NOTE: SAFETY WARNING: 

Isolate supply before removing cover;

 

Metal parts, in particular the heatsink, may get very hot when 

the unit is fully operational; DO NOT COVER enclosure ventilation slots. 

It is essential that a load 

break switch and contact breaker is installed in the supply.

 The supply to the contactor coil 

should be interrupted by an over-temperature thermostat located in the heater battery and also by 

detection of airflow loss. 

 

RECOMMENDATIONS

 

Additional supporting documents, which may be appropriate for your application, are available on request (see X10593). 

NOTE: 

 It is recommended that installation and maintenance of this equipment should be done with reference to the 

current edition of the I.E.T. (formally I.E.E.) regulations (BS7671) by suitably qualified/trained personnel. The regulations 
contain important requirements regarding installation and safety of electrical equipment. Specific installers should refer to 
local and national regulations.  

 

© These products are protected by unregistered design with United Automation Limited, Southport, UK

 

 

ORDER DETAILS 

When ordering directly, please use the following stock codes:-  

Manufacturer stock code

 

Product Description

 

Rating

 

A437420-HV 

PR3-E-30kW-SPM 

3-phase, 30kW, 42A@415V, 2/3rds 

control 

A437483-HV 

PR3-E-36kW-SPM 

3-phase, 36kW, 50A@415V, 2/3rds 

control 

A403011 

5k

Ω, 1W Potentiometer with 0.5m long leads for 

manual control option 

 

Available on request 

Spare HS fuses: 56ET (56A) or 63ET (63A) SCR-

type 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

UNITED AUTOMATION LIMITED 

Southport Business Park 

 

 Tel:  0044 (0) 1704 

– 516500 

Wight Moss Way   

 

 Fax: 0044 (0) 1704 

– 516501 

Southport, PR8 4HQ 

 

 [email protected] 

ENGLAND 

 

 

 www.united-automation.com 

 

 Issue 4  

 

 

 

Date  08/08/2016   

 

 

 

 

 

Содержание PR3-E SPM Series

Страница 1: ...ature and temperature sensor error The power to drive the alarm relay coil is obtained from the board power supply which can be either internal or external L2 L3 are used to power the internal transformer based power supply therefore when internally powered the loss of phase L2 and L3 condition cannot be indicated as this results in a loss of power to the controller card Over Temperature Protectio...

Страница 2: ...Dual cycle is selected when Burst Rate trimmer VR1 is fully clockwise Offset Option SW1 3 When SW1 3 is in the off position no offset is selected for the voltage and current input control signals When SW1 3 is in the ON position an offset is introduced this option is selected for 1 5V 2 10V and 4 20mA control signals Voltage or Current Option SW1 5 When switch SW1 5 is in the OFF position this sel...

Страница 3: ...Data sheet X10255 for further information Other external supplies should be fused accordingly CE Marking This family carries a CE marking These burst fire controllers do not normally require a remote filter For more information contact our sales desk A Declaration of Conformity is available on request SPECIFICATIONS Power Current ratings 30kW 42A 36kW 50A a typical supply of 415V RMS Input voltage...

Страница 4: ...gulations BS7671 by suitably qualified trained personnel The regulations contain important requirements regarding installation and safety of electrical equipment Specific installers should refer to local and national regulations These products are protected by unregistered design with United Automation Limited Southport UK ORDER DETAILS When ordering directly please use the following stock codes M...

Отзывы: