INSTALLATION 

 

This robust stack assembly will operate in an ambient temperature of up to 45°C when naturally cooled and has a built in 
90°C over temperature trip on the heatsink as a safety feature.  The unit should be mounted vertically, with heatsink fins 
top to bottom and with sufficient surrounding air space to maximise natural convection cooling.  If the unit is mounted in an 
enclosure or cabinet, adequate ventilation and/or forced air-cooling should be fitted. 

Load considerations

 

The PR3E series of power controllers are designed for 3-wire, 3-phase floating-star or closed delta, resistive loads.  The 
PR3-E series are 2-leg thyristor controllers and therefore do not support 3-phase, 4-wire star, star point to neutral loads.  
For further information on configured loads, see the ‘Application Circuits’ section of our supporting datasheet  – APC (ref. 
X10322). 
Heating loads such as Molybdenum, Platinum or Tungsten have a typical, 10:1, hot to cold, resistance ratio and therefore, 
when cold, draw larger currents than normal, it is recommended to enable the soft start feature when driving these types 
of load.  

Connections 

This unit has simple clamp type connectors for all auxiliary-wiring requirements. 

Power Supply 

Three  way  internal  jumper  JP2  selects  the  internal  power  supply  input  voltage  to  either  420v  or  460v  ac  rms,  phase  to 
phase.  If  the  jumper  link  is  fitted  across  HI-COM,  460v  is  selected  with  the  jumper  link  fitted  across  COM-LO,  420v  is 
selected. The jumper header is labelled as shown below: 

 

COM

HI

LO

 

The SPM model has an internal power supply, the units are factory set for 420v rms (COM-LO) supply. For operation with 
an external power supply the jumper link should be removed from JP2. 

Fusing 

It is recommended that high speed semiconductor type fuses (as supplied on SPM models) be used for protection.  See 
SRA Data sheet X10255 for further information.  Other external supplies should be fused accordingly. 

CE Marking 

This  famil

y  carries  a  “CE”  marking.    These  burst  fire  controllers  do  not  normally  require  a  remote  filter.    For  more 

information contact our sales desk. A Declaration of Conformity is available on request. 

 

SPECIFICATIONS 
Power (Current) ratings:

 

 

30kW (42A); 36kW (50A); @ a typical supply of 415V RMS 

Input voltage:

 

 

400V RMS +/- 10% 

Frequency: 

 

50/60Hz

 

Control Signal Input Options: 

0 to 5V or Manual using 5K Potentiometer: SW1-3:OFF, SW1-5:OFF, SW1-6:OFF. 
1 to 5V: SW1-3:ON, SW1-5:OFF, SW1-6:OFF. 0 to 10V: SW1-3:OFF, SW1-5:OFF,SW1-
6:ON  

 

 

2 to 10V: SW1-3:ON, SW1-5:OFF, SW1-6:ON  
0-20mA: SW1-3:OFF, SW1-5:ON, SW1-6:OFF. 4-20mA: SW1-3:ON, SW1-5:ON, SW1-
6:OFF. 

Alarms Relay Contact Rating: 

2A @ 125V ac Max.

  

Power Indicator: 

 

Power

 

LED 

 

Status Indicator: 

 

Status LED indicator changes intensity during phase angle soft start or flashes in 
synchronisation with bursts.

 

Over Temperature: 

 

Temperature trip activates   @ 90ºC, +/- 1ºC. Fault LED indicator flashes,

 

continuous fast 

pulsing. 

 

 

Temperature trip de-activates @ 85ºC, +/- 1ºC 

Alarm Relay Default State 

 

SW1-4

:

OFF Relay is energised in no fault state, NO contact is closed (connected to 

COM). 

 

 

SW1-4

:

ON Relay is de-energised in no fault state, NO contact is open (disconnected from 

COM). 

SW1 Pos 4

 = ON - Relay is de- 

Phase 

Phase loss Detection 

 

Fault LED indicator 'flashes' continuous slow pulsing. 

Sensor Loss Detection: 

 

Fault LED indicator ‘flashes’

 

fast pulsing. 

SCR/Fuse Fault: 

 

Fault LED and Status LED

 

alternately flash (SPM model only).

 

Cable Terminations:

 

 

Phase Power 

 

 

10mm² rising clamp terminal block 

 

 

Earth 

 

 

 

10mm² rising clamp terminal block 

 

 

Remote Supply, Alarm Relay, Enable, Control Signal  2.5mm² rising clamp terminal block

 

 

  Terminal Torque Settings: 

 

1.2Nm (10mm²) Power terminals only. 

Fusing                                           

30kW:    56ET (56A) High-Speed Semiconductor type fuse, or equivalent.  

             

 

36kW:

 

63ET (63A) High-Speed Semiconductor type fuse, or equivalent.  

   Ambient Temperature:

 

 

45

C without de-rating 

Dimensions:

 

 

152mm (D) x 241mm (W) x 115mm (H) 

Fixing Centres: 

 

4 x 5.5mm ø holes on centres 220mm (W) x 130mm (D) 

Weight: 

 

2.6kg Maximum (all models) 

 

 

 

 

Содержание PR3-E SPM Series

Страница 1: ...ature and temperature sensor error The power to drive the alarm relay coil is obtained from the board power supply which can be either internal or external L2 L3 are used to power the internal transformer based power supply therefore when internally powered the loss of phase L2 and L3 condition cannot be indicated as this results in a loss of power to the controller card Over Temperature Protectio...

Страница 2: ...Dual cycle is selected when Burst Rate trimmer VR1 is fully clockwise Offset Option SW1 3 When SW1 3 is in the off position no offset is selected for the voltage and current input control signals When SW1 3 is in the ON position an offset is introduced this option is selected for 1 5V 2 10V and 4 20mA control signals Voltage or Current Option SW1 5 When switch SW1 5 is in the OFF position this sel...

Страница 3: ...Data sheet X10255 for further information Other external supplies should be fused accordingly CE Marking This family carries a CE marking These burst fire controllers do not normally require a remote filter For more information contact our sales desk A Declaration of Conformity is available on request SPECIFICATIONS Power Current ratings 30kW 42A 36kW 50A a typical supply of 415V RMS Input voltage...

Страница 4: ...gulations BS7671 by suitably qualified trained personnel The regulations contain important requirements regarding installation and safety of electrical equipment Specific installers should refer to local and national regulations These products are protected by unregistered design with United Automation Limited Southport UK ORDER DETAILS When ordering directly please use the following stock codes M...

Отзывы: