CONTROL OPTIONS GUIDE 

Soft Start Option (SW1-1): 

When this switch is ON, the output ramps up to required power level using phase angle and then switches to burst 
fire mode.  

Rapid Burst Fire (SW1-2): 

When switch SW1-2 is in the OFF position, standard burst fire is used. When in standard burst fire mode, the Burst 
Rate trimmer (VR1) is used to set the time bae. The time base is the ON/OFF cycle time, this is variable from 1-30 
seconds. When switch SW1-2 is in the ON position, rapid burst fire mode is selected. Two types of rapid burst fire are 
supported, single and dual cycle. Single cycle is selected when Burst Rate trimmer (VR1) is fully anticlockwise. Dual 
cycle is selected when Burst Rate trimmer (VR1) is fully clockwise. 

Offset Option (SW1-3): 

When SW1-3 is in the off position no offset is selected for the voltage and current input control signals. When SW1-3 
is in the ON position an offset is introduced, this option is selected for 1-5V, 2-10V and 4-20mA control signals. 

Voltage or Current Option (SW1-5): 

When  switch  SW1-5  is  in  the  OFF  position  this  selects  a  voltage  control  input  signal  (0-5V,  1-5V,  0-10V,  2-10V). 
When switch SW1-5 is in the ON position this selects a current control signal (0-20mA, 4-20mA). 

10V Signal Option (SW1-6): 

When switch SW1-6 is in the OFF position the control voltage is selected to be 0-5V or 1-5V, depending on the Offset 
Option switch (SW1-3).When switch SW1-6 is in the ON position the control voltage range is selected to be 0-10V or 
2-10V depending on the Offset Option switch SW1-3. 

  

 

 

Содержание PR3-E SPM Series

Страница 1: ...ature and temperature sensor error The power to drive the alarm relay coil is obtained from the board power supply which can be either internal or external L2 L3 are used to power the internal transformer based power supply therefore when internally powered the loss of phase L2 and L3 condition cannot be indicated as this results in a loss of power to the controller card Over Temperature Protectio...

Страница 2: ...Dual cycle is selected when Burst Rate trimmer VR1 is fully clockwise Offset Option SW1 3 When SW1 3 is in the off position no offset is selected for the voltage and current input control signals When SW1 3 is in the ON position an offset is introduced this option is selected for 1 5V 2 10V and 4 20mA control signals Voltage or Current Option SW1 5 When switch SW1 5 is in the OFF position this sel...

Страница 3: ...Data sheet X10255 for further information Other external supplies should be fused accordingly CE Marking This family carries a CE marking These burst fire controllers do not normally require a remote filter For more information contact our sales desk A Declaration of Conformity is available on request SPECIFICATIONS Power Current ratings 30kW 42A 36kW 50A a typical supply of 415V RMS Input voltage...

Страница 4: ...gulations BS7671 by suitably qualified trained personnel The regulations contain important requirements regarding installation and safety of electrical equipment Specific installers should refer to local and national regulations These products are protected by unregistered design with United Automation Limited Southport UK ORDER DETAILS When ordering directly please use the following stock codes M...

Отзывы: