X20109

 

30kW and 36kW HVAC RANGE 

3-PHASE BURST FIRE POWER CONTROLLER

  

 

 

RoHS 

Compliant 

 Sample Photo 

– PR3-E-27kW  

INTRODUCTION 

 

The  PR3-E  S/SP/SPM  range  of  thyristor  stacks 
provide  full,  seamless  control,  of  three  phase, 
resistive  loads  using  a  two  thirds  control  technique.  
Control of the power level is either by a dc signal or 
by  manual  control  using  a  5k

Ω  potentiometer.  The 

PR3-E burst firing control stacks use fast pulse, zero 
volts  switching  technology,  to  minimise  flicker  and 
eliminate  RFI  problems.  The  controllers  also 
incorporate  an  automatically  resetting  temperature 
trip,  integral  semiconductor  fuses,  and  an  integral 
volt  free  trip/enable  input  for  wiring  of  an  external 
thermal  trip.  The  range  contains  two  power  ratings: 
30kW  and  36kW.  For  each  power  rating,  the  SPM 
(Standard  Plus  Monitoring)  version  -  includes  HS 
fuses,  internal  power  supply  and  SCR/HS  Fuse 
monitoring.  All  have easy  access  to signal  &  power 
terminals for simple installation.   
 

APPLICATIONS 

Suitable for 3-wire, 3-phase floating-star or closed-delta configured resistive loads. This includes the Heating, Ventilating and Air 
Conditioning (HVAC) market for air curtain applications, but also for furnaces, ovens, dryers and hot plates. 

 

FUNCTION 

Trip/Enable Input

 

This input should be driven by a volt free contact. When the contact is closed the unit is enabled to supply power to the load. 
When the contact is open this disables the power to the load. If this input is not used a wire link must be fitted to enable the 
unit. 

Alarm Relay Output (3-way terminal 

– Volt Free Contacts, Normally Open (NO), Normally Closed (NC), Common 

(COM).

 

The alarm circuit has voltage free relay contacts which have a 2A@125 V AC RMS rating. The alarm conditions which are 
detected are phase loss (L1, L2, L3), fuse failure (L1, L3), device failure (L1, L3), over temperature and temperature sensor 
error. The power to drive the alarm relay coil is obtained from the board power supply, which can be either internal or external. 
L2 & L3 are used to power the internal, transformer based power supply, therefore when internally powered the loss of phase 
L2 and L3 condition cannot be indicated as this results in a loss of power to the controller card. 

Over Temperature Protection

 

When a heatsink temperature of above 90ºC is detected by the sensor, the alarms relay changes state and the Fault LED 
pulses rapidly. The power to the load will be disconnected and will not be re-enabled until the temperature drops to 85ºC. 

Temperature Sensor Loss

 

If the temperature sensor fails or becomes disconnected, the Fault LED changes to ON/OFF (fast pulsing) and the alarm relay 
state changes.  

Phase Loss with Auxiliary Supply 

When  any  one  of  the  three  phase  inputs  is  not  present,  the  relay  changes  state  and  the  Fault  LED  flashes  with  ON/OFF 
bursts of 1.5 seconds.  This is only functional with a remote supply (see below).

 

SCR/Fuse Monitoring  

Fault and Status LED flash alternately and the alarm relay will change state. This condition indicates that either a HS fuse  has 
failed or a SCR open or short circuit failure has been detected. 
 

 

NOTE: The fuse or device fault indication can also be caused by an open circuit load on Phase 1 or Phase 3. 

Alarm Relay Fault Indication 

If DIL switch SW1-4 is in the OFF position, the alarm relay will be energised with no fault present and hence the NO contact 
will  be  closed  and  connected  to  the  COM  terminal.    If  DIL  switch  SW1-4  is  in  the  ON  position,  the  alarm  relay  will  be  de-
energised when no fault is present and hence the NO contact will be disconnected from the COM terminal. For either state of 
SW1-4, the relay state toggles when an alarm condition is detected. 

Remote Supply

 

If there is a requirement for the alarm relay and Fault LED to energise when a phase fault condition occurs, the SPM model 
must be specified and an external 24V dc supply should be used. 

 
 

 

 

 

Содержание PR3-E SPM Series

Страница 1: ...ature and temperature sensor error The power to drive the alarm relay coil is obtained from the board power supply which can be either internal or external L2 L3 are used to power the internal transformer based power supply therefore when internally powered the loss of phase L2 and L3 condition cannot be indicated as this results in a loss of power to the controller card Over Temperature Protectio...

Страница 2: ...Dual cycle is selected when Burst Rate trimmer VR1 is fully clockwise Offset Option SW1 3 When SW1 3 is in the off position no offset is selected for the voltage and current input control signals When SW1 3 is in the ON position an offset is introduced this option is selected for 1 5V 2 10V and 4 20mA control signals Voltage or Current Option SW1 5 When switch SW1 5 is in the OFF position this sel...

Страница 3: ...Data sheet X10255 for further information Other external supplies should be fused accordingly CE Marking This family carries a CE marking These burst fire controllers do not normally require a remote filter For more information contact our sales desk A Declaration of Conformity is available on request SPECIFICATIONS Power Current ratings 30kW 42A 36kW 50A a typical supply of 415V RMS Input voltage...

Страница 4: ...gulations BS7671 by suitably qualified trained personnel The regulations contain important requirements regarding installation and safety of electrical equipment Specific installers should refer to local and national regulations These products are protected by unregistered design with United Automation Limited Southport UK ORDER DETAILS When ordering directly please use the following stock codes M...

Отзывы: