TECHNICAL SPECIFICATION 

 
 

Supply Voltage 

 

 

 

 

/- 10% @ 50/60Hz 

Switching Capacity 

 

 

 

 

4kW Max. 

Detection Range 

 

 

 

 

5 metres 

Detection Angle 

 

 

 

 

100° 

Temperature Set Point  

 

 

 

1 to 60°C 

Lamp On-Time  

 

 

 

 

5 Minutes (fixed) 

Current Consumption (control circuit)  

 

50mA 

Terminals 

 

 

 

 

 

2.5mm

2

 Rising Clamp 

Operating Temperature 

 

 

 

-20 to 40°C 

Protection Rating 

 

 

 

 

IP65 

Gland Diameter 

 

 

 

 

Max Cable Entry 2.5mm² 

Enclosure Dimensions (WxLxH) 

 

 

100 x 112 x 55 (mm) 

 

Introduction 

The infresco-P 4kW is part of a family of controllers designed to provide energy saving when used with Quartz Infrared 
Halogen Lamps. The ‘P’ model has a built in PIR sensor allowing the lamps to automatically switch on only when people 
are present. In addition to the PIR, a temperature sensor monitors the outside temperature and inhibits the lamps when 
the temperature exceeds a pre-determined set point of between 1°C and 60°C. 

The microcontroller-based  system  incorporates  zero-voltage  switching  and  a  soft-start  function  to  eliminate  the  lamps’ 
initial high inrush current – potentially increasing lamp life by as much as 30%. The lamps are switched on for a fixed time 
period of 5 minutes. This period is reset each time the PIR detects any further movement. Installation of the unit is simple 
and once installed is relatively maintenance-free

 

Installation 

Important: Read carefully the following information before installing the unit. 
 
The passive infrared sensor (PIR) fitted in this unit detects changes of infrared energy through the Fresnel lens on the 
front face of the unit. The detection area and range depend significantly on its mounting position. 
 
The  PIR  not  only  detects  movement  of  the  human  body,  but  also  other  heat  sources  similar  to  the  human  body.  To 
prevent  false  activation,  the  unit  must  not  be  located  directly  facing  or  in  close  proximity  to  the  heater  lamps.  Avoid 
locating the unit near to heating flues/exhausts, air conditioning units, moving trees/bushes and reflective surfaces. 
 
Note: The PIR cannot detect the presence of a human body that is not moving. 

 

To prevent malfunction of the PIR sensor, avoid subjecting it to rapidly-changing temperatures, strong shock or vibration 
or high humidity and temperature. 
 

 

Содержание INFRESCO P

Страница 1: ...EY FEATURES Energy saving o Only provides heat when people are present Extends lamp life Temperature sensor o Lamps inhibited when ambient temperature exceeds set point Soft start zero voltage switch off Low cost Easy to install Power ON Blue Heater ON Red LED indication ...

Страница 2: ... high inrush current potentially increasing lamp life by as much as 30 The lamps are switched on for a fixed time period of 5 minutes This period is reset each time the PIR detects any further movement Installation of the unit is simple and once installed is relatively maintenance free Installation Important Read carefully the following information before installing the unit The passive infrared s...

Страница 3: ...WIRING DIAGRAM ...

Страница 4: ...bove shows the PIR s detection area The unit should be fixed securely using the four mounting holes accessible from the front of the unit Remove the lid to access the mounting holes To ease installation a mounting template is provided on the next page to locate the 4 mounting hole centres IMPORTANT When wall mounting the unit must be orientated with the cable glands facing down ...

Страница 5: ...e dimensions to locate the 4 mounting hole centres prior to drilling IMPORTANT Drilling of any holes through the enclosure will immediately invalidate the warranty of the unit The unit MUST be orientated with the cable glands facing down ...

Страница 6: ...L to the N terminal and EARTH to the E terminal If two lamps are to be fitted they must be wired in parallel Warning Ensure all earth wires are connected to maintain earth continuity to the lamp fittings Check all wiring and make sure the cable glands are tightened Commissioning Turn the set point temperature preset VR1 fully clockwise to select walk test mode VR1 is located at the top of the prin...

Страница 7: ... point temperature VR1 Check the lamps Lamp fittings Contact your supplier Problem Lamps do not switch off Solution Ensure nobody enters the detection area for 5 minutes This will allow the 5 minute on time to expire The PIR might be continually being re triggered due to false activations Mask the PIR lens and wait 5 minutes If the lamps switch off after 5 minutes the PIR is receiving false activa...

Страница 8: ...tion of the I E E Wiring Regulations BS7671 The regulations contain important requirements regarding the safety of electrical equipment ELECTROSTATIC DISCHARGE ESD This product range has been identified has requiring protection from electrostatic discharge ESD They include integrated circuits IC s that may be damaged or degraded if mishandled They are much less vulnerable when built in circuit and...

Страница 9: ...4 H Q T e l 4 4 0 1 7 0 4 5 1 6 5 0 0 F a x 4 4 0 1 7 0 4 5 1 6 5 0 1 E m a i l s a l e s u n i t e d a u t o m a t i o n c o m W e b w w w u n i t e d a u t o m a t i o n c o m PRODUCT APPLICATIONS Patio areas Smoking shelters Restaurants Warehouses Workshops Garden lighting Livery stables ...

Отзывы: