 SMOKE DETECTOR 230 V

READ AND RETAIN THIS USER MANUAL

6

years

warrenty

85

dB

230

V

Installation:

WARNING:

 Ensure the power supplies are turned off before installing 

smoke detectors.

1.   Using the fixings supplied attach the base plate of the smoke detector to 

the desired position.

2.   Connect the supply wires to the connectors – Brown to Live (L), Grey to 

neutral (N) and the Black to Interlink (I). Be sure to sleeve the bare earth 
wire and terminate it in the connector shown above.

3.   7885653303 versions only – Fit batteries in accordance with section 

“Changing the Batteries” below.

4.   Close the smoke detector making sure the 3 retaining clips are fitting 

securely. When removing the smoke detector from it’s base-plate, use 
a small flat bladed screwdriver in the slots to push away the clips and 
lever the smoke detector away.

5.   Test the smoke detector using the large test button (shown above) without 

mains power and check it sounds at least 3 times and that the red LED 
flashes.

6.   Turn on the mains power supply. (7885653316 versions only – the 

alarm may beep once every minute for around an hour while the battery 
charge is topped up).

7.   Check that the Green LED is on and that the red LED flashes once every 

minute.

8.   Test the smoke detector to check that all other interlinked smoke detectors 

in the system sound. The LEDS on the other smoke detector will not flash 
repeatedly during this operation.

IMPORTANT NOTE:

 Use only the test button to test the smoke detector 

weekly. Do not test the smoke detector with either a naked flame or smoke, 
this will damage and contaminate the smoke detector causing nuisance 
alarms in the future.

6. USER INFORMATION

Protect your home against fire

Make sure all occupants of the home know what a fire alarm sounds like. 
Prove and practise a fire escape plan and arrange a suitable and safe 
assembly point.

What to do if the acoustic alarms sound

Alarms sounds are as follows:

Full alarm indicating 
smoke and fire

Repeating series of 3 beeps every  
4 seconds with flashing light

··· ··· ··· ···

Low Battery

Single beep every minute

·    ·    ·    ·

Test button jammed

One beep every 11 seconds

·  ·  ·  ·

Other fault

Double beep every minute

··   ··   ··   ··

If the full alarm sounds, ensure everyone leaves the building as soon as possible.

•  Do not run.

•  Do not stop to collect belongings.

•   If it is safe to do so, close all windows and doors as you escape to prevent 

the spread of fire.

•   Smoke is the main cause of death from fire. If trapped inside the building, 

cover your mouth, conserve breath and crawl to safety.

Do not silence a smoke detector until you know the cause of the alarm and 
when all occupants are safely outside the building. The red LED on the test but-
ton of the smoke detector that has set the system off will be flashing Red once 
every second. The lights on the other smoke detectors will be flashing once 
every minute. The system can only be silenced from this smoke detector.

7. CHANGING THE BATTERIES

CAUTION!

 Danger of explosion if the battery is incorrectly replaced. Replace 

only with correct batteries

The smoke detector will emit an acoustic signal once a minute to indicate the 
batteries need replacing. If this happens at night press the test button to silence 
the warning for 10 hours and replace the following day. 

In the event of a low battery warning on the 7885653316 replace the alarm. 
The battery is not replaceable.

Replacing batteries (7885653303 only)

To replace the batteries on the 7885653303 version, isolate mains power to 
the smoke detector, release the retaining clips, lower the smoke detector on its 
hinge and refer to Fig. 2.

Insert the three AAA-batteries. Ensure the new batteries are installed correctly 
and close the detector. Mount the detector correctly, reconnect the power and 
test the detector. 

Maintenance of the smoke detector

A regular smoke detector maintenance is advised to ensure the detector 
always works properly. 

•  Test the smoke detector once a week. All linked detectors should sound 

within 10 seconds. 

•  Vacuum the smoke detector every 6 months and wipe the surface with a 

damp cloth. 

8. TROUBLE SHOOTING

Problems are indicated in several ways

1.   The smoke detector emits an acoustic signal twice every minute indicating 

a malfunction.

2.   The smoke detector emits an acoustic signal once every minute indicating a 

low battery. Replace the battery as above.

3.   The smoke detector emits an acoustic signal once every 11 seconds indi-

cating the test button is jammed on. Press the test button to reset.

4.   The full alarm sounds for no reason. (A repeating series of three beeps with 

flashing light). Clean the alarm as above.

5.  The alarm does not sound when pressing the test button.

6.   The red LED remains steadily on or off. (i.e. does not flash approximately 

once every minute, when the unit is not in alarm).

7.   The green LED is off. 

Inspect for obvious damage. Check that the smoke detector has been installed 
in accordance with the instructions, that the smoke detector is connected and 
the supply turned on. In the case of repeated nuisance alarms, check that it is 
free from dust, cobwebs and external contamination.

Stationsalléen 40  ·  DK-2730 Herlev

www.lemu.dk

Models: 7885653303 and 7885653316

Live, iterconnect and
Neutral connections

Earth

Fig. 1

Fig. 2

Smoke detector
retaining clips 
(x3)

Test button

Remove this cover when using mini-trunking