Unitary products group YMB Series Скачать руководство пользователя страница 7

170761-UIM-B-0406

Unitary Products Group

7

CFM SELECTION BOARD SETTINGS

For proper system operation the CFM Selection Board jumpers must be
set properly. 

Refer to the Tabular Data Sheet for the recommended air flow settings
for each size condensing unit.

Set the cooling speed per the instructions for the air handler or furnace
by selecting the correct COOL and ADJ taps. Verify the airflow using
the LED display on the CFM selection board.

The HEAT PUMP jumper MUST be removed for proper system opera-
tion.

The HUMIDISTAT jumper must also be removed if a dehumidistat is
installed.

SECTION VI: EVACUATION

It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again. 

To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it’s an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, its an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.

SECTION VII: SYSTEM CHARGE

The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set and the smallest indoor coil match-up. Some indoor
coil matches may require additional charge. See tabular data sheet pro-
vided in unit literature packet for charge requirements.

The “TOTAL SYSTEM CHARGE” must be permanently stamped on the
unit data plate.

Total system charge is determined as follows:

1.

Determine outdoor unit charge from tabular data sheet.

2.

Determine indoor coil adjustment from tabular data sheet.

3.

Calculate the line charge using the tabular data sheet if line length
is greater than 15 feet.

4.

Total system charge = item 1 + item 2 + item 3.

5.

Permanently stamp the unit data plate with the total amount of
refrigerant in the system.

If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly. Otherwise, model-specific charging
charts are provided in Tables 12 - 18 for cooling mode only. There is no
accurate method for charging these units in the heating mode. If charg-
ing is required during the heating mode, the unit must be evacuated
and charge weighed in according to the rating plate. If TXV indoor coils
are used with the 2 through 3-1/2 ton models, the following subcooling
charging method must be used. Superheat charging charts are not valid
with TXV equipped systems.

Subcooling Charging Method - Cooling Only

The recommended subcooling is 10°F

1.

Set the system running in the cooling mode by setting the thermo-
stat at least 6°F below the room temperature.

2.

Operate the system for a minimum of 15-20 minutes.

3.

Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).

4.

Measure the liquid refrigerant pressure P and temperature T at the
service valve.

5.

Calculate the saturated liquid temperature ST from Table 1.

6.

Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).

Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level. See Table 1
for R-22 saturation temperatures 

See Figure 9 to trace the flow of refrigerant through the system.

Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).

 FIGURE 7: CFM Selection Board

Do not leave the system open to the atmosphere.

CFM SELECTION BOARD

TAP SELECTION

D
C
B
A

D
C
B
A

COOL

HEAT

ADJ

DELAY

REMOVE FOR

HEAT PUMP

HUMIDISTAT

Refrigerant charging should only be carried out by a qualified air
conditioning contractor.

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

Example: The pressure P and temperature T measured at the liq-
uid service port is 196 psig and 90°F, respectively. From Table 1, 
the saturated temperature for 196 psig is 100°F. The subcooling 
temperature TC = 100°-90°=10°F

Содержание YMB Series

Страница 1: ...or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual for assistance or for additional in...

Страница 2: ...sor burnout then installation of a 100 activated alumina suction line filter drier is required in addition to the factory installed liquid line drier Operate the system for 10 hours Monitor the suction drier pres sure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suction line pressure drop has not exceeded...

Страница 3: ...door unit is above the indoor coil oil trapping is necessary An oil trap should be provided for every 20 ft of rise See Figure 2 PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copp...

Страница 4: ...l 5 Slide the grommet away from the vapor connection at the indoor coil Braze the vapor line to the evaporator vapor connection After the connection has cooled slide the grommet back into original position Refer to the Tabular Data Sheet for proper vapor line siz ing 6 Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit The nitrogen flow should be exiting...

Страница 5: ...orous copper alloy material such as Silfos 5 or equivalent DO NOT use soft solder Install the TXV bulb to the vapor line near the equalizer line using the two bulb clamps furnished with the TXV assembly Ensure the bulb is making maximum contact Refer to TXV installation instruction for view of bulb location a Bulb should be installed on a horizontal run of the vapor line if possible On lines under...

Страница 6: ...xposed glass or appliances drafts from outside doors or supply air grilles 5 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat DEHUMIDIFICATION CONTROL A dehumidification con...

Страница 7: ...brated charging cylinder or accurate weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided in Tables 12 18 for cooling mode only There is no accurate method for charging these units in the heating mode If charg ing is required during the heating mode the unit must be evacuated and charge weighed in according to the rating plate If TXV indoo...

Страница 8: ...95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 126 72 156 85 186 97 216 107 246 116 98 58 128 73 158 86 188 97 218 107 248 117 100 59 130 74 160 87 190 98 220 108 250 117 102 60 132 75 162 88 192 99 222 109 252 118 104 61 134 76 164 88 194 99 224 109 254 118 106 62 136 77 166 89 196 100 226 110 256 119 108 63 138 78 168 90 198 101 228 111 258 119 FIGURE 8 Heat Pump Flow Diagra...

Страница 9: ...display various types of diagnostic information LED1 is red and LED2 is green The location of the LED s is shown in Figures 10 and 13 These LED s are used to display opera tional mode status and fault information OPERATIONAL MODE DETECTION The control can be used in a variety of applications including heat pumps and air conditioners with modulating compressors The control uses various inputs to de...

Страница 10: ...reen is not energized These faults typically occur when the heat pump has been operating and a problem occurs Sensor or Switch Fault Codes Table 7 shows the faults that the control can detect when a problem is present with a sensor or switch The control displays this type of error by energizing LED1 Red constantly and flashing LED2 Green These faults typically occur when the heat pump has been ope...

Страница 11: ...criptions of the conditions required for the control to enter the soft lockout mode are contained in other sections of this document 1 High pressure switch a Two openings within six hours 2 Low pressure switch a One opening of the switch for more than five seconds except under certain conditions 3 High discharge temperature with optional discharge sensor a Temperature reading exceeds 263F 4 Low di...

Страница 12: ...at has been forced using the TEST inputs It will also display the active defrost curve using the X L terminal when the operational mode is being displayed using the LED s For instance the X L output will be energized with two flashes when defrost curve 2 is active The control will lock out the com pressor if the defrost curve selection jumper is not properly set Defrost Cycle Initiation The contro...

Страница 13: ...onnected to the indoor unit The SWITCH POINT jumper on the control has no effect on the opera tion of the heat pump The control implements the Hot Heat Pump Mode by controlling the indoor airflow level during heating operation only Cooling operation is not affected By reducing the indoor airflow level the heat pump system will operate with increased indoor discharge air temperatures The con trol c...

Страница 14: ...flow because of the Y1 signal being delivered to the Y1 input of the indoor unit When the ten minute timer expires the control will compare the liquid line temperature to the indoor airflow control curve for the measured outdoor ambient temperature If the point is within region A See Figure 12 the control shall maintain Y2 OUT in the de energized state until the liquid line temperature rises so th...

Страница 15: ...ient temperature is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under some conditions as described in the auxil iary heat sections of this document FOSSIL FUEL JUMPER FFUEL Setting The control includes a FFUEL jumper to specify whether the control is installe...

Страница 16: ...ll de energize the compressor outputs and energize W1 Out and W2 Out immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The heat pump may be equipped in the field with an optional indoor air discharge temperature or bonnet sensor The control does not allow the heat pump and the furnace to operate simultaneously even with a bon net sensor...

Страница 17: ...n time If the control senses another opening of the high pressure switch before the timer expires it will cause a soft lockout condition The second opening of the high pressure switch must be greater than 160 milliseconds for the lockout to occur If the second opening is between 40 and 160 milliseconds the control will de energize the com pressor but not cause a soft lockout condition If the contr...

Страница 18: ... and assure proper drainage IT IS UNLAWFUL TO KNOWINGLY VENT RELEASE OR DIS CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR SERVICE MAINTENANCE OR THE FINAL DIS POSAL OF THIS UNIT WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED SECURE THE OWNER S APPROVAL TABLE 12 1 1 2 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressu...

Страница 19: ...7 11 269 11 110 286 11 287 11 286 11 288 11 115 305 11 306 11 305 11 307 11 120 324 10 326 11 324 11 326 11 125 344 10 345 10 343 11 346 11 TABLE 17 4 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressure psig at Base Valve 65 141 4 140 3 141 3 142 2 70 155 5 154 4 156 4 157 3 75 169 5 169 5 171 4 172 4 80 183 5 183 5 185 5 187 4 85 197 5 198 5 200 5 202 ...

Страница 20: ...ce Printed in U S A 170761 UIM B 0406 Copyright by York International Corp 2006 All rights reserved Supersedes 170761 UIM A 0106 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM FIGURE 13 Wiring Diagram ...

Отзывы: