Unitary products group YMB Series Скачать руководство пользователя страница 15

170761-UIM-B-0406

Unitary Products Group

15

The control only reads the jumper inputs when the Y1, Y2, and W ther-
mostat inputs are de-energized. If a jumper position is changed while
any of these inputs are energized, the control will not act upon the
jumper changes until all three of these thermostat calls are de-ener-
gized or power (24 VAC) to the control is cycled.

IMPORTANT: Changes to the jumper inputs do not take affect until Y1,
Y2, and W thermostat signals are de-energized.

LOW TEMPERATURE CUTOUT (LTCO) AND 

BALANCE POINT (BP)

The control includes a low temperature cutout (LTCO) feature that pre-
vents compressor operation below a specified temperature during heat
pump heating operation only. The LTCO setting does not apply to com-
pressor operation during cooling or defrost operation.

The control also includes a balance point feature that prevents the
operation of auxiliary heat above a specified temperature. 

Setting

The LTCO and BP jumpers on the control are shown in Figures 10 and
13. Both jumpers are placed on the same connector. The control will
consider the lowest jumper pin setting to be the LTCO and the highest
jumper pin setting to be the BP. The use of the same connector forces
the BP and the LTCO to always be separated by at least 10 degrees.

The temperatures shown on the side of the connector labeled LTCO are
the LTCO temperature options. The values shown are in degrees F. The
control allows the LTCO to be set to any of the following temperatures: -
10, 0, 10, 15, 20, 25, 30, 35 degrees F or ON. Placing the jumper in the
ON position will allow the control to operate the compressor at any tem-
perature during heating operation.   

The factory places the LTCO jumper in the ON position. The jumper
must be changed in the field to implement the LTCO feature. If the
jumper is removed, the control will behave as if the jumper is in the ON
position.

The temperatures shown on the side of the connector labeled BP are
the BP temperature options. The values are shown in degrees F. The
control allows the balance point to be set to any of the following temper-
atures: 0, 10, 15, 20, 25, 30, 35, 40, or 45 degrees F.

The factory places the BP jumper in the 35 F position. The jumper may
be changed in the field as desired. If the jumper is removed, the control
will behave as if the jumper is in the 35 position.

If only one jumper is in place, the control will set the balance point
based on the jumper position and will set the LTCO to ON. If only one
jumper is in place and it is below the valid BP settings (in the –10 or ON
position), the control will set the BP to the default value for no jumper in
place (35F) and set the LTCO based on the jumper position (-10 or
ON).

Low Temperature Cutout (LTCO) Operation

The control will not operate the compressor in heating mode when the
outdoor ambient temperature is below the selected LTCO. The LTCO
applies only to air handler mode operation. In fossil fuel mode the bal-
ance point (BP) restricts the operation of the compressor so the LTCO
setting has no effect.

Balance Point (BP) Operation

If the measured outdoor ambient temperature is greater than the bal-
ance point setting, the control will not energize the auxiliary heat out-
puts. However, the control shall ignore the balance point setting and
energize auxiliary heat under some conditions as described in the auxil-
iary heat sections of this document. 

FOSSIL FUEL JUMPER (FFUEL)

Setting

The control includes a FFUEL jumper to specify whether the control is
installed with a fossil fuel furnace or an air handler (electric heat). This
jumper is shown in Figures 10 and 13. The factory places the FFUEL
jumper in the OFF position which is the correct position for an air han-
dler installation. The jumper must be changed to the ON position in the
field if the heat pump is installed with a fossil fuel furnace. If the jumper
is removed, the control will behave as if the jumper is in the OFF posi-
tion.

IMPORTANT: If the heat pump is being installed with a fossil fuel fur-
nace, the FFUEL jumper must be placed in the ON position during
installation for proper system operation.

Operation

The control operates the auxiliary heat outputs, W1 Out and W2 Out,
based on the position of the FFUEL jumper. If the FFUEL jumper is in
the ON position, the control will function in fossil fuel mode. If the
jumper is in the OFF position, the control will function in air handler
mode. The FFUEL jumper has no effect on cooling operation.

AUXILIARY HEAT - AIR HANDLER MODE

The heat pump control energizes the auxiliary electric heat in air han-
dler mode using the W1 Out and W2 Out signals. The control receives
the room thermostat call for auxiliary heat at the W input terminal.

Standard Operation

If the outdoor ambient temperature is less than ten degrees F below the
balance point setting and a W input is received with a Y1 input, the con-
trol will energize the M compressor contactor output based on the Y1
input and will energize the W1 Out immediately when the W input is
received. When the W input is received, the control will start a fifteen-
minute timer. If the call for Y1 + W is still present after the fifteen-minute
timer expires, the control will then energize W2 Out along with W1 Out.
If the W input is removed but the Y1 signal remains, the control will de-
energize W1 Out and W2 Out (if energized) and reset and restart the
timer. If the W input is received again without a loss of the Y1, the same
functionality will be repeated.

If the outdoor ambient temperature is ten degrees F or more below the
balance point setting and a W input is received with a Y1 input, the con-
trol will energize W1 Out and W2 Out immediately.

If the outdoor ambient temperature is below the low temperature cutout
(LTCO) setting, the control will de-energize the compressor and ener-
gize W1 Out immediately when a Y1 input is received. If the outdoor
ambient temperature rises above the LTCO setting before the thermo-
stat is satisfied, the control will continue to keep the compressor outputs
de-energized until the thermostat is satisfied. In other words, the control
will use auxiliary heat to satisfy the thermostat demand and not turn the
compressor back on even if the outdoor ambient temperature rises
above the LTCO setting during a call for heating.

Table 10 describes the auxiliary heat operation for air handler mode.

 FIGURE 12: Jumper Inputs

Содержание YMB Series

Страница 1: ...or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual for assistance or for additional in...

Страница 2: ...sor burnout then installation of a 100 activated alumina suction line filter drier is required in addition to the factory installed liquid line drier Operate the system for 10 hours Monitor the suction drier pres sure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suction line pressure drop has not exceeded...

Страница 3: ...door unit is above the indoor coil oil trapping is necessary An oil trap should be provided for every 20 ft of rise See Figure 2 PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copp...

Страница 4: ...l 5 Slide the grommet away from the vapor connection at the indoor coil Braze the vapor line to the evaporator vapor connection After the connection has cooled slide the grommet back into original position Refer to the Tabular Data Sheet for proper vapor line siz ing 6 Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit The nitrogen flow should be exiting...

Страница 5: ...orous copper alloy material such as Silfos 5 or equivalent DO NOT use soft solder Install the TXV bulb to the vapor line near the equalizer line using the two bulb clamps furnished with the TXV assembly Ensure the bulb is making maximum contact Refer to TXV installation instruction for view of bulb location a Bulb should be installed on a horizontal run of the vapor line if possible On lines under...

Страница 6: ...xposed glass or appliances drafts from outside doors or supply air grilles 5 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat DEHUMIDIFICATION CONTROL A dehumidification con...

Страница 7: ...brated charging cylinder or accurate weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided in Tables 12 18 for cooling mode only There is no accurate method for charging these units in the heating mode If charg ing is required during the heating mode the unit must be evacuated and charge weighed in according to the rating plate If TXV indoo...

Страница 8: ...95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 126 72 156 85 186 97 216 107 246 116 98 58 128 73 158 86 188 97 218 107 248 117 100 59 130 74 160 87 190 98 220 108 250 117 102 60 132 75 162 88 192 99 222 109 252 118 104 61 134 76 164 88 194 99 224 109 254 118 106 62 136 77 166 89 196 100 226 110 256 119 108 63 138 78 168 90 198 101 228 111 258 119 FIGURE 8 Heat Pump Flow Diagra...

Страница 9: ...display various types of diagnostic information LED1 is red and LED2 is green The location of the LED s is shown in Figures 10 and 13 These LED s are used to display opera tional mode status and fault information OPERATIONAL MODE DETECTION The control can be used in a variety of applications including heat pumps and air conditioners with modulating compressors The control uses various inputs to de...

Страница 10: ...reen is not energized These faults typically occur when the heat pump has been operating and a problem occurs Sensor or Switch Fault Codes Table 7 shows the faults that the control can detect when a problem is present with a sensor or switch The control displays this type of error by energizing LED1 Red constantly and flashing LED2 Green These faults typically occur when the heat pump has been ope...

Страница 11: ...criptions of the conditions required for the control to enter the soft lockout mode are contained in other sections of this document 1 High pressure switch a Two openings within six hours 2 Low pressure switch a One opening of the switch for more than five seconds except under certain conditions 3 High discharge temperature with optional discharge sensor a Temperature reading exceeds 263F 4 Low di...

Страница 12: ...at has been forced using the TEST inputs It will also display the active defrost curve using the X L terminal when the operational mode is being displayed using the LED s For instance the X L output will be energized with two flashes when defrost curve 2 is active The control will lock out the com pressor if the defrost curve selection jumper is not properly set Defrost Cycle Initiation The contro...

Страница 13: ...onnected to the indoor unit The SWITCH POINT jumper on the control has no effect on the opera tion of the heat pump The control implements the Hot Heat Pump Mode by controlling the indoor airflow level during heating operation only Cooling operation is not affected By reducing the indoor airflow level the heat pump system will operate with increased indoor discharge air temperatures The con trol c...

Страница 14: ...flow because of the Y1 signal being delivered to the Y1 input of the indoor unit When the ten minute timer expires the control will compare the liquid line temperature to the indoor airflow control curve for the measured outdoor ambient temperature If the point is within region A See Figure 12 the control shall maintain Y2 OUT in the de energized state until the liquid line temperature rises so th...

Страница 15: ...ient temperature is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under some conditions as described in the auxil iary heat sections of this document FOSSIL FUEL JUMPER FFUEL Setting The control includes a FFUEL jumper to specify whether the control is installe...

Страница 16: ...ll de energize the compressor outputs and energize W1 Out and W2 Out immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The heat pump may be equipped in the field with an optional indoor air discharge temperature or bonnet sensor The control does not allow the heat pump and the furnace to operate simultaneously even with a bon net sensor...

Страница 17: ...n time If the control senses another opening of the high pressure switch before the timer expires it will cause a soft lockout condition The second opening of the high pressure switch must be greater than 160 milliseconds for the lockout to occur If the second opening is between 40 and 160 milliseconds the control will de energize the com pressor but not cause a soft lockout condition If the contr...

Страница 18: ... and assure proper drainage IT IS UNLAWFUL TO KNOWINGLY VENT RELEASE OR DIS CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR SERVICE MAINTENANCE OR THE FINAL DIS POSAL OF THIS UNIT WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED SECURE THE OWNER S APPROVAL TABLE 12 1 1 2 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressu...

Страница 19: ...7 11 269 11 110 286 11 287 11 286 11 288 11 115 305 11 306 11 305 11 307 11 120 324 10 326 11 324 11 326 11 125 344 10 345 10 343 11 346 11 TABLE 17 4 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressure psig at Base Valve 65 141 4 140 3 141 3 142 2 70 155 5 154 4 156 4 157 3 75 169 5 169 5 171 4 172 4 80 183 5 183 5 185 5 187 4 85 197 5 198 5 200 5 202 ...

Страница 20: ...ce Printed in U S A 170761 UIM B 0406 Copyright by York International Corp 2006 All rights reserved Supersedes 170761 UIM A 0106 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM FIGURE 13 Wiring Diagram ...

Отзывы: