Unitary products group YMB Series Скачать руководство пользователя страница 14

170761-UIM-B-0406

14

Unitary Products Group

When the ten-minute timer expires, the control will measure the liquid
line temperature and determine whether to energize Y2 Out and
increase the indoor airflow or keep Y2 Out de-energized and maintain
reduced indoor airflow. The control compares the measured liquid line
temperature to a pre-programmed indoor airflow curve. It continues to
keep Y2Out de-energized until the liquid line temperature exceeds the
curve for the given outdoor ambient temperature continually for 30 sec-
onds. If the liquid line temperature drops below the curve, the control
will reset the 30-second timer and restart it when the liquid line temper-
ature again exceeds the curve. When the liquid line temperature
exceeds the indoor airflow control curve continually for 30 seconds, the
control will energize Y2Out, i.e. cause high indoor airflow, until the ther-
mostat demand is satisfied and the thermostat signal inputs are
removed.  Figure 12 describes the required behavior.

Once the control energizes Y2 Out to create high airflow, it will keep Y2
Out energized until the thermostat is satisfied and the call for heating is
removed. It will do this regardless of a change in outdoor ambient or liq-
uid line temperature. Therefore, if the control energizes Y2 Out because
the outdoor ambient temperature is greater than or equal to 50F or
because the liquid line temperature exceeds the curve for the given out-
door ambient temperature (point within region B), it will keep Y2 Out
energized until the thermostat is satisfied even if the liquid line or out-
door ambient temperature falls below the curve (point within region A).

The control of Y2 Out to generate high indoor airflow as required will
prevent the heat pump system pressures and temperatures from
becoming too great when the compressor is running at full capacity with
low indoor airflow. 

As an example, assume that the HOT HP jumper is in the ON position.
When the control receives a call for heating (Y1), it checks the outdoor
ambient temperature. If the outdoor ambient temperature is 52F, the
control will energize Y2 Out immediately causing high indoor airflow
and keep it energized until the Y1 signal is removed. If the outdoor
ambient temperature is 48F, the control will maintain Y2 OUT in a de-
energized state and begin a ten-minute timer. The indoor unit will be
running at low airflow because of the Y1 signal being delivered to the
Y1 input of the indoor unit. 

When the ten-minute timer expires, the control will compare the liquid
line temperature to the indoor airflow control curve for the measured
outdoor ambient temperature. If the point is within region A (See Figure
12), the control shall maintain Y2 OUT in the de-energized state until
the liquid line temperature rises so that region B is entered. While in
region A, the indoor unit will continue to run at low airflow. When the liq-
uid line temperature point enters region B, the control will start a 30 sec-
ond timer. When the timer expires, the control will immediately energize
Y2 OUT. If the liquid line temperature drops back into region A before
the timer expires, the control will reset the timer and restart it when the
liquid line temperature again enters region B. When the liquid line tem-
perature is in region B continually for thirty seconds, the Y2 Out signal
will be delivered to the indoor unit and cause high airflow. 

During defrost operation, the control will ignore the HOT HP jumper set-
ting and energize the Y2 Out signal to create high indoor airflow. Addi-
tionally, if at any point the conditions require a defrost cycle, the control
will override the reduced indoor airflow feature and function based on
the defrost requirements and conditions.

EMERGENCY HEAT

When the control receives a W signal without a Y signal (emergency
heat), the control will de-energize the compressor and energize the W1
Out and W2 Out terminals immediately. The balance point setting is
ignored during a call for emergency heat. Therefore, W1 Out and W2
Out will be energized regardless of the outdoor ambient temperature.

JUMPER INPUTS

The control uses seven jumpers to determine how the heat pump
should operate. These jumpers are shown in Figures 10 and 13. The
jumpers that affect this heat pump are the following. The effects of
these jumper settings on the operation of the heat pump are described
in other sections of this document.

LTCO – Low Temperature Cutout

BP – Balance Point

Defrost  Curve

FFUEL – Specifies fossil fuel furnace application

HOT HEAT PUMP – Enables indoor airflow control for hot heat
pump application

The two jumpers that do not affect the operation of this heat pump are
Y2 LOCK and SWITCH POINT. Both of these jumpers apply only to
two-stage compressor units. 

 FIGURE 11: Hot Heat Pump Indoor Airflow Control

IN

DO

O

AI

RF

LO

W

 C

O

NT

RO

CU

RV

E

REGION A

REGION B

AMBIENT TEMPERATURE

LI

Q

U

ID LINE

 (

C

OIL) T

E

M

PER

AT
URE

Y2Out Energized (High Indoor Airflow)

Y2Out De-energized (Low Indoor Airflow)

Содержание YMB Series

Страница 1: ...or moderate injury It is also used to alert against unsafe practices and hazards involving only property dam age Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service or mainte nance can cause injury or property damage Refer to this manual for assistance or for additional in...

Страница 2: ...sor burnout then installation of a 100 activated alumina suction line filter drier is required in addition to the factory installed liquid line drier Operate the system for 10 hours Monitor the suction drier pres sure drop If the pressure drop exceeds 3 psig replace both the suction line and liquid line driers After a total of 10 hours run time where the suction line pressure drop has not exceeded...

Страница 3: ...door unit is above the indoor coil oil trapping is necessary An oil trap should be provided for every 20 ft of rise See Figure 2 PRECAUTIONS DURING LINE INSTALLATION 1 Install the lines with as few bends as possible Care must be taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copp...

Страница 4: ...l 5 Slide the grommet away from the vapor connection at the indoor coil Braze the vapor line to the evaporator vapor connection After the connection has cooled slide the grommet back into original position Refer to the Tabular Data Sheet for proper vapor line siz ing 6 Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit The nitrogen flow should be exiting...

Страница 5: ...orous copper alloy material such as Silfos 5 or equivalent DO NOT use soft solder Install the TXV bulb to the vapor line near the equalizer line using the two bulb clamps furnished with the TXV assembly Ensure the bulb is making maximum contact Refer to TXV installation instruction for view of bulb location a Bulb should be installed on a horizontal run of the vapor line if possible On lines under...

Страница 6: ...xposed glass or appliances drafts from outside doors or supply air grilles 5 Route the 24 volt control wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat DEHUMIDIFICATION CONTROL A dehumidification con...

Страница 7: ...brated charging cylinder or accurate weighing device is avail able add refrigerant accordingly Otherwise model specific charging charts are provided in Tables 12 18 for cooling mode only There is no accurate method for charging these units in the heating mode If charg ing is required during the heating mode the unit must be evacuated and charge weighed in according to the rating plate If TXV indoo...

Страница 8: ...95 212 105 242 115 94 56 124 71 154 84 184 96 214 106 244 115 96 57 126 72 156 85 186 97 216 107 246 116 98 58 128 73 158 86 188 97 218 107 248 117 100 59 130 74 160 87 190 98 220 108 250 117 102 60 132 75 162 88 192 99 222 109 252 118 104 61 134 76 164 88 194 99 224 109 254 118 106 62 136 77 166 89 196 100 226 110 256 119 108 63 138 78 168 90 198 101 228 111 258 119 FIGURE 8 Heat Pump Flow Diagra...

Страница 9: ...display various types of diagnostic information LED1 is red and LED2 is green The location of the LED s is shown in Figures 10 and 13 These LED s are used to display opera tional mode status and fault information OPERATIONAL MODE DETECTION The control can be used in a variety of applications including heat pumps and air conditioners with modulating compressors The control uses various inputs to de...

Страница 10: ...reen is not energized These faults typically occur when the heat pump has been operating and a problem occurs Sensor or Switch Fault Codes Table 7 shows the faults that the control can detect when a problem is present with a sensor or switch The control displays this type of error by energizing LED1 Red constantly and flashing LED2 Green These faults typically occur when the heat pump has been ope...

Страница 11: ...criptions of the conditions required for the control to enter the soft lockout mode are contained in other sections of this document 1 High pressure switch a Two openings within six hours 2 Low pressure switch a One opening of the switch for more than five seconds except under certain conditions 3 High discharge temperature with optional discharge sensor a Temperature reading exceeds 263F 4 Low di...

Страница 12: ...at has been forced using the TEST inputs It will also display the active defrost curve using the X L terminal when the operational mode is being displayed using the LED s For instance the X L output will be energized with two flashes when defrost curve 2 is active The control will lock out the com pressor if the defrost curve selection jumper is not properly set Defrost Cycle Initiation The contro...

Страница 13: ...onnected to the indoor unit The SWITCH POINT jumper on the control has no effect on the opera tion of the heat pump The control implements the Hot Heat Pump Mode by controlling the indoor airflow level during heating operation only Cooling operation is not affected By reducing the indoor airflow level the heat pump system will operate with increased indoor discharge air temperatures The con trol c...

Страница 14: ...flow because of the Y1 signal being delivered to the Y1 input of the indoor unit When the ten minute timer expires the control will compare the liquid line temperature to the indoor airflow control curve for the measured outdoor ambient temperature If the point is within region A See Figure 12 the control shall maintain Y2 OUT in the de energized state until the liquid line temperature rises so th...

Страница 15: ...ient temperature is greater than the bal ance point setting the control will not energize the auxiliary heat out puts However the control shall ignore the balance point setting and energize auxiliary heat under some conditions as described in the auxil iary heat sections of this document FOSSIL FUEL JUMPER FFUEL Setting The control includes a FFUEL jumper to specify whether the control is installe...

Страница 16: ...ll de energize the compressor outputs and energize W1 Out and W2 Out immediately Table 11 describes the auxiliary heat operation for fossil fuel mode Bonnet Sensor Fossil Fuel Mode The heat pump may be equipped in the field with an optional indoor air discharge temperature or bonnet sensor The control does not allow the heat pump and the furnace to operate simultaneously even with a bon net sensor...

Страница 17: ...n time If the control senses another opening of the high pressure switch before the timer expires it will cause a soft lockout condition The second opening of the high pressure switch must be greater than 160 milliseconds for the lockout to occur If the second opening is between 40 and 160 milliseconds the control will de energize the com pressor but not cause a soft lockout condition If the contr...

Страница 18: ... and assure proper drainage IT IS UNLAWFUL TO KNOWINGLY VENT RELEASE OR DIS CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR SERVICE MAINTENANCE OR THE FINAL DIS POSAL OF THIS UNIT WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED SECURE THE OWNER S APPROVAL TABLE 12 1 1 2 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressu...

Страница 19: ...7 11 269 11 110 286 11 287 11 286 11 288 11 115 305 11 306 11 305 11 307 11 120 324 10 326 11 324 11 326 11 125 344 10 345 10 343 11 346 11 TABLE 17 4 Ton Subcooling Charging Chart Outdoor Ambient Indoor Wet Bulb F 57 62 67 72 DB F Liquid Pressure psig at Base Valve 65 141 4 140 3 141 3 142 2 70 155 5 154 4 156 4 157 3 75 169 5 169 5 171 4 172 4 80 183 5 183 5 185 5 187 4 85 197 5 198 5 200 5 202 ...

Страница 20: ...ce Printed in U S A 170761 UIM B 0406 Copyright by York International Corp 2006 All rights reserved Supersedes 170761 UIM A 0106 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM FIGURE 13 Wiring Diagram ...

Отзывы: