background image

177820-YIM-A-0506

10

Unitary Products Group

THERMOSTAT

The room thermostat should be located on an inside
wall approximately 56 inches above the floor where it
will not be subject to drafts, sun exposure or heat from
electrical fixtures or appliances. Follow the manufac-
turer's instructions enclosed with the thermostat for
general installation procedure. A minimum of seven
color-coded insulated wires (#18 AWG) should be used
to connect the thermostat to the unit.

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of
the National Electrical Code, ANSI / NFPA No. 70 (in
U.S.A.), current Canadian Electrical Code C22.1 (in
Canada) and/or local ordinances. The unit must be
electrically grounded in accordance with NEC and CEC
(as specified above) and/or local codes. Voltage toler-
ances, which must be maintained at the compressor
terminals, during starting and running conditions, are
indicated on the unit Rating Plate and the Unit Applica-
tion Data table.

The internal wiring harness furnished with this unit is
an integral part of a CSA design certified unit. Field
alteration to comply with electrical codes should not be
required.

A fused disconnect switch should be field provided for
the unit. The switch must be separate from all other cir-
cuits. Wire entry at knockout openings require conduit
fittings to comply with NEC (in U.S.A.), CEC (in Can-
ada) and/or local codes. If any of the wire supplied with
the unit must be replaced, replacement wire must be of
the type shown on the wiring diagram and the same
minimum gauge as the replaced wire.

Use copper conductors properly sized to carry the load.
Each unit must be wired with a separate branch circuit
fed directly from the meter panel and properly fused.

Refer to the Typical Field Wiring Figure 3 and to the
appropriate unit wiring diagram for control circuit and
power wiring information.

OPTIONS/ACCESSORIES

ELECTRIC HEAT

The field-installed heaters are wired for single point
power supply. Power supply need only be brought into
the single point terminal block and thermostat wiring to
the low voltage terminal strip located in the upper por-
tion of the unit control box.

These CSA approved heaters are located within the
central compartment of the unit with the heater ele-
ments extending into the supply air chamber. Refer to
Figure 7 for access panel location.

Fuses are supplied, where required, by the factory.
Some KW sizes require fuses and others do not. Refer
to Table 3 for minimum CFM limitations and to Tables
9 and 10 for electrical data.

When connecting electrical power and control
wiring to the unit, waterproof type connectors

MUST BE USED

 so that water or moisture

cannot be drawn into the unit during normal
operation. The above waterproofing conditions
will also apply when installing a field-supplied
disconnect switch.

TABLE 2: CONTROL WIRE SIZES

Wire Size

Maximum Length

1

1.

From the unit to the thermostat and back to the unit.

18 AWG

150 Feet

Содержание SUNLINE 2000 BCH 036

Страница 1: ...TALLATION 5 OPERATION 27 START UP COOLING 31 TROUBLESHOOTING 32 MAINTENANCE 34 See the following page for a complete Table of Contents NOTES CAUTIONS AND WARNINGS The installer should pay particular a...

Страница 2: ...LY AIR BLOWERS 26 CHECKING SUPPLY AIR CFM 26 OPERATION 27 SEQUENCE OF OPERATIONS OVERVIEW 27 COOLING SEQUENCE OF OPERATION 27 CONTINUOUS BLOWER 27 INTERMITTENT BLOWER 28 NO OUTDOOR AIR OPTIONS 28 ECON...

Страница 3: ...CENTER OF GRAVITY ALL MODELS 13 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTION 13 6 BCH 6 POINT LOADS WEIGHT DISTRIBUTION 13 7 PHYSICAL DATA 14 8 OPERATING WEIGHTS LBS 14 9 ELECTRICAL DATA BCH036 060 DIRECT...

Страница 4: ...unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the car rier s freight bill A separate request for inspectio...

Страница 5: ...Current Canadian Electrical Code C22 1 Local plumbing and waste water codes Other applicable local codes Refer to the Unit Application Data Table 1 and the Electrical Data table for the unit If compon...

Страница 6: ...rails Spreader bars whose length exceeds the largest dimension across the unit MUST BE USED Units may also be moved or lifted with a forklift Slotted openings in the base rails are provided for this p...

Страница 7: ...lumbing must conform to local codes Use a sealing compound on male pipe threads Install a condensate drain line from the one inch NPT female connection on the unit to an open drain NOTE The condensate...

Страница 8: ...n Minimum filter area and required sizes are shown in Physical Data Table 7 SERVICE ACCESS The following removable panels provide access to all serviceable components Compressor compartment Electric H...

Страница 9: ...RANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE SECOND STAGE COOLING IS NOT REQUIRED ON UNITS...

Страница 10: ...and or local codes If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire Use copp...

Страница 11: ...CONOMIZER AND POWER EXHAUST DAMPER SET POINT ADJUSTMENTS AND INFORMATION Remove the economizer access panel from the unit Loosen but do not remove the two panel latches Locate the economizer control m...

Страница 12: ...ith power exhaust option each building pressur ization requirement will be different The point at which the power exhaust comes on is determined by the economizer damper position Percent Open The Exha...

Страница 13: ...NIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT TABLE 4 CENTER OF GRAVITY ALL MODELS DIMENSION 3 5 TON X 40 Y 19 TABLE 5 BCH 4 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D BCH036 62...

Страница 14: ...2 Nom CFM 4300 4200 4500 CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X...

Страница 15: ...8 8 2 20 8 25 2CE045110462 10 1 12 1 25 8 30 2CE045115462 13 6 16 4 31 0 35 2CE045120462 19 5 23 5 39 9 40 575 3 60 4 8 34 0 1 0 2 2 None 8 6 15 2CE04511058 10 6 10 2 21 3 25 2CE04511558 15 9 15 3 27...

Страница 16: ...0 2CE04511025 10 6 25 5 64 9 70 2CE04511525 15 9 38 2 80 8 90 2CE04512025 21 2 51 0 96 8 100 2CE04513025 29 6 71 2 122 0 125 460 3 60 10 0 62 0 1 3 3 3 None 17 1 25 2CE045107462 6 8 8 2 27 3 35 2CE045...

Страница 17: ...8 8 2 21 2 25 2CE045110462 10 1 12 1 26 2 30 2CE045115462 13 6 16 4 31 4 35 2CE045120462 19 5 23 5 40 3 45 575 3 60 4 8 34 0 1 0 2 0 None 8 8 15 2CE04511058 10 6 10 2 21 5 25 2CE04511558 15 9 15 3 27...

Страница 18: ...0 2CE04511025 10 6 25 5 63 5 70 2CE04511525 15 9 38 2 79 4 80 2CE04512025 21 2 51 0 95 4 100 2CE04513025 29 6 71 2 120 6 125 460 3 60 10 0 62 0 1 3 2 6 None 16 4 25 2CE045107462 6 8 8 2 26 6 30 2CE045...

Страница 19: ...OLTAGE kW CAP MULTIPLIER 208 208 0 75 240 230 0 92 480 460 0 92 600 575 0 92 TABLE 12 VOLTAGE LIMITATIONS1 1 Utilization Range A in accordance with ARI Standard 110 POWER SUPPLY VOLTAGE MIN MAX 208 23...

Страница 20: ...177820 YIM A 0506 20 Unitary Products Group FIGURE 8 UNIT WITH ECONOMIZER RAINHOOD FIGURE 9 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B...

Страница 21: ...TRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS...

Страница 22: ...40 880 680 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1...

Страница 23: ...40 880 680 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1...

Страница 24: ...500 882 740 926 780 965 830 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 14...

Страница 25: ...0 1900 970 LOW 2030 1070 1960 1020 1890 970 1810 920 3 1 4 1 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0 90 0 80 1 00 3 1 4 1 5 1 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 5 1 0 60 0 20 0 30 0 40 0 5...

Страница 26: ...0 12 0 14 0 16 20 30KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 BOTTOM DUCT CONNECTIONS1 ELECTRIC HEATERS1 RESISTANCE IWG CFM DESCRIPTION ECONOMIZER1 2...

Страница 27: ...the unit can be determined from the curve in Pressure Drop vs Supply Air CFM Figure 13 After readings have been obtained remove the tubes and reinstall the two 5 16 dot plugs that were removed in Ste...

Страница 28: ...motor only Once the thermostat has been satisfied it will de ener gize Y1 If the compressor has satisfied its minimum run time the compressor and condenser fan are de energized Otherwise the unit ope...

Страница 29: ...rate in the low ambient mode Low ambient mode operates the compressors in this manner 10 minutes on 5 minutes off The indoor blower is operated throughout the cycle The 5 minute off period is necessar...

Страница 30: ...timer that must be satisfied before defrost can begin This is accumulated compressor run time The selection pin is factory set at 60 minutes but is field adjustable to 30 60 or 90 minutes When the DC...

Страница 31: ...to on 5 Check indoor blower rotation If blower rotation is in the wrong direction Refer to Phasing Section in general informa tion section Check blower drive belt tension 6 Check the unit supply air...

Страница 32: ...the fan switch is set to ON check that line voltage is being supplied to the contacts of the M2 contactor and that the contactor is pulled in Check for loose wiring between the contactor and the sup p...

Страница 33: ...resent and M1 is not pulled in replace the contactor 5 Failing the above if voltage is supplied at M1 M1 is pulled in and the compressor still does not oper ate replace the compressor 6 If 24 volts is...

Страница 34: ...hanged by the local distributor 15 If none of the above correct the error replace the UCB UNIT FLASH CODES Various flash codes are utilized by the unit control board UCB to aid in troubleshooting Flas...

Страница 35: ...ponents Check that all mounting bolts are tight Replace defective parts as required OUTDOOR COIL Dirt should not be allowed to accumulate on the out door coil surface or other parts in the air circuit...

Страница 36: ...change without notice Printed in U S A 177820 YIM A 0506 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 66278 035 16197 001 A 0204 Unitary 5005 Norman Products York OK Group D...

Отзывы: