background image

035-17438-001 Rev. A (901)

Unitary Products Group

23

MOTOR OPERATION IS INTERMITTENT

Verify that all connectors are firmly seated. Gently pull 
the motor connector wires at both ends of the cables 
individually to be sure they are properly crimped into the 
housings.

MOTOR RUNS WHEN IT IS SUPPOSED TO BE OFF

Allow a few minutes for the motor to shut off. Motor-off 
delays are controlled by the ignition control. 

MOTOR STARTS BUT: RUNS ERRATICALLY

Check the line voltage for variation.

Check low voltage connections at motor, unseated pins 
in motor harness connectors.

Check “Bk” for erratic CFM command.

MOTOR HUNTS OR “PUFFS”

Excessive restriction in duct system or filter. Reduce 
maximum air flow.

STAYS AT LOW CFM DESPITE SYSTEM CALL FOR 
COOL OR HEAT CFM

Check low voltage wires and connections. 

Verify fan is not in delay mode - wait until delay is com-
plete.

“R” missing /not connected at motor or terminal strip.

Perform motor/control replacement check.

STAYS AT HIGH CFM

“R” missing/not connected at motor or terminal strip.

Is fan in delay mode? Wait until delay is complete.

Perform motor/control replacement check.

BLOWER WON’T SHUT OFF

Current leakage from controls into G, Y, or W? Check for 
Triac switched thermostat or solid state relay.

EXCESSIVE NOISE

Determine if it’s air noise, cabinet, duct, or motor noise.

AIR NOISE

Check for loose blower housing, panels, etc. 

High static creating high blower speed?

REPLACEMENT OF FAILED MOTOR CONTROL 
MODULE

NOTE:  

The motor control module may be removed and

BLOWER REMOVAL FOR CONTROLLER 
REPLACEMENT

Refer to “BLOWER CARE” on page 21 of this manual for 
blower removal instructions.

Rest the blower on its side so the end of the motor is 
accessible and facing up.

Wait at least 5 minutes after disconnecting AC power 
from the furnace before opening the motor.

Remove the 2-1/4” Hex head bolts from the motor while 
holding the control module.

Verify with an ohmmeter that the resistance of each 
motor lead is greater than 100K ohms by connecting one 
meter lead to the motor lead and the other to an 
unpainted portion of the motor housing. If any one of the 
leads fails this test THE MOTOR IS DEFECTIVE AND 
MUST BE REPLACED.

Verify that the replacement control module is the correct 
one and carefully orient the control module close to the 
motor so the cable can be plugged into the module. BE 
SURE THE PLUG LATCHES WITH A CLICK.

Carefully align the locating pin of the control module with 
the matching motor hole. Replace the 2-1/4” hex head 
bolts and tighten snugly. DO NOT OVERTIGHTEN.

You must have the correct replacement control
module for the furnace being serviced. The con-
trols are factory programmed for specific operating
modes. Consult the parts list supplied with this fur-
nace to obtain the correct part number before
ordering the part. 

Using the wrong control module voids all product
warranties and may produce unexpected results.

When the hex bolts are removed from the control
module, the module is free from the motor but still
connected by a plug and cable. Carefully rotate
the control so as to gain access the plug on the
end of cable. Squeeze the release latch and gently
pull the plug out of the control module. Do not pull
on the wires.

Содержание PxDUA12V06401 series

Страница 1: ...035 17438 001 Rev A 901 EFFICIENCY RATING CERTIFIED CAUTION READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR FURNACE SAVE THIS MANUAL TABLE OF CONTENTS GENERAL INFORMATION 2 UNIT INSTALLATION 3...

Страница 2: ...PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR AD...

Страница 3: ...ptable heat loss calculation for the structure ACCA Manual J or other approved methods may be used The furnace should be located using these guidelines 1 Where a minimum amount of vent piping and elbo...

Страница 4: ...the total input rating of all equipment located in the enclosure b Not less than the sum of the areas of all vent con nectors in the confined space 3 Louvers Grilles and Screens a In calculating free...

Страница 5: ...nds in a general vertical direction and does not con tain offsets exceeding 45 degrees except that a vent system having not more than one 60 degree offset is permitted NOTE This appliance may be commo...

Страница 6: ...nce being operated in operation Adjust thermostat so appli ance will operate continuously 5 Test for draft hood equipped appliance spillage at the draft hood relief opening after 5 minutes of main bur...

Страница 7: ...V UH INPUT MBH H L OUTPUT MBH H L NOM CFM CABINET WIDTH IN AFUE1 LOW FIRE TEMP RISE F HIGH FIRE TEMP RISE MAX OUTLE AIR TEMP F BLOWER TOTAL UNIT AMPS MAX OVER CURRENT PROPECT2 MIN WIRE SIZE AWG 75 FT...

Страница 8: ...removable access panel is recommended in the outlet duct such that smoke or reflected light would be observable inside the casing to indi cate the presence of leaks in the heat exchanger This access...

Страница 9: ...and notes on blower perfor mance tables in this manual Where the return duct system is not complete the return con nection must run full size to a location outside the utility room or basement For fur...

Страница 10: ...s is recommended Refer to Fig ure 6 on page 10 NOTE See crawl space installation for suspending the fur nace in attic installations CRAWL SPACE INSTALLATION The furnace can be hung from floor hoists o...

Страница 11: ...cordance with instructions Specific electrical data is given on the furnace rating plate Provide a power supply separate from all other circuits Install overcurrent protection and disconnect switch pe...

Страница 12: ...OFF position and the main electrical source disconnected complete the low voltage wiring from the ther mostat to the terminal board on the CFM programmable board Connect Class 2 control wiring see Fig...

Страница 13: ...nt 1 Blockage of internal flue gas passage ways 2 Blockage of vent piping 3 Failure of combustion air blower motor Limit Control The high temperature limit control is located on the furnace vestibule...

Страница 14: ...increment find the cubic feet of gas consumed per hour from Table 4 on page 15 NOTE To find the Btuh input multiply the number of cubic feet of gas consumed per hour by the BTU content of the gas in y...

Страница 15: ...cement The temperature rise or temperature difference between the return air and the heated air from the furnace must be within the range shown on the furnace rating plate Application limi tations are...

Страница 16: ...uction for the recommended airflow and Table 6 on page 17 The DELAY Tap should be set in the B position for a two stage condenser This results in a 45 second off delay at 82 of the programmed cooling...

Страница 17: ...002UHC11 L8V1002UHC11 P DUC20V09601 G8V12020UHC11 L8V12020UHC11 COOL TAP ADJ TAP High Low High Low High Low High Low 1340 740 1675 920 2050 1135 2020 1130 A B 1155 635 1555 850 1860 980 1855 960 B B 1...

Страница 18: ...is fixed at 60 seconds for SEER enhance ment HEATING OPERATIONAL SEQUENCE Two Stage Thermostat The ignition control in this furnace is unique to this product The control allows for a 24 volt or a 115...

Страница 19: ...gas valve When power is restored the gas valve will remain deener gized and a restart of the ignition sequence will begin imme diately A momentary loss of gas supply flame blowout or a shorted or open...

Страница 20: ...LOW INDUCER LOW STAGE PRESSURE SWITCH HSI 1ST STAGE MAIN VALVE FLAME SENSE LOW CIRCULATOR HEAT SPEED 1ST STAGE LOW PRESSURE SWITCH CLOSE RECOGNITION HSI WARM UP 17 SEC IGNITION ACTIVATION PERIOD 4 SE...

Страница 21: ...bly for cleaning is as follows 1 Disconnect the power supplied to the furnace 2 Remove the vest and blower panels 3 Disconnect the motor control harness and the power har ness from the motor 4 Remove...

Страница 22: ...including the flue baffle plate rear may be vacuumed or cleaned with hot water if necessary 6 The upper portion of the heat exchanger is now accessi ble With a long flexible wire brush clean inside ea...

Страница 23: ...R REMOVAL FOR CONTROLLER REPLACEMENT Refer to BLOWER CARE on page 21 of this manual for blower removal instructions Rest the blower on its side so the end of the motor is accessible and facing up Wait...

Страница 24: ...ehind a clear view port in the blower compartment door DO NOT remove the furnace blower compartment panel OR turn off furnace power as either action will clear the control s memory of the fault The co...

Страница 25: ...y low gas pressure faulty gas valve faulty hot surface ignitor reversed line polarity or burner problem 8 FLASH This fault is indicated if the flame is lost 5 times during the heating cycle This could...

Страница 26: ...NTROL BOARD P3 S3 2 PIN PLUG SOCKET AT HOT SURFACE IGNITOR P4 S4 3 PIN PLUG SOCKET AT INDUCER MOTOR P5 S5 3 PIN PLUG SOCKET ON VALVE P6 S6 6 PIN PLUG SOCKET ON CFM TIMER BOARD P7 S7 16 PIN PLUG SOCKET...

Страница 27: ...035 17438 001 Rev A 901 Unitary Products Group 27 SERVICE RECORDS...

Страница 28: ...hange without notice Printed in U S A 035 17438 001 Rev A 901 Copyright by York International Corp 2001 All rights reserved Supersedes 035 17438 001 Rev A 801 Unitary 5005 Norman Product York OK Group...

Отзывы: