NOTES:

1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m

3

/min).

2. Return air is through side opposite motor (left side).

3. In order to stay within the velocity rating the filters, airflows above 1800 CFM (50.97 m

3

/min) require either return from two sides or one side plus bottom.

4. Motor voltage at 115 V.

5. NR = Operation at this static pressure is not recommended.

FILTER PERFORMANCE

The airflow capacity data published in Table 17 represents blower per-
formance WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the filter being
used or select an appropriate value from the Table 18.

NOTE: 

The filter pressure drop values in Table 18 are typical values for

the type of filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter manufactur-
ers.

TABLE 17: 

Blower Performance CFM

Models

Input

Airflow/
Cabinet

Speed

Tap

Airflow with Bottom or One Side Retrun - 

without Filters (CFM)

Airflow with Bottom or One Side Retrun - 

without Filters (m

3

min)

External Static Pressure, Inches W.C.

External Static Pressure, Inches

 (kPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0.025 0.050 0.075 0.099 0.124 0.149 0.174 0.199 0.224 0.249

40/1200/A

High

1395

1330

1265

1200

1120

1030

940

820

NR

NR

40

38

36

34

32

29

27

23

NR

NR

Med-High

1025

990

960

925

885

825

750

660

NR

NR

29

28

27

26

25

23

21

19

NR

NR

Med-Low

785

765

745

715

670

625

545

NR

NR

NR

22

22

21

20

19

18

15

NR

NR

NR

Low

640

605

590

565

530

465

405

NR

NR

NR

18

17

17

16

15

13

11

NR

NR

NR

80/1200/B 
60/1200/B

High

1650

1605

1570

1525

1465

1410

1350

1275

1170

1060

47

45

44

43

41

40

38

36

33

30

Med-High

1165

1185

1175

1165

1150

1140

1100

1050

970

875

33

34

33

33

33

32

31

30

27

25

Med-Low

895

915

935

940

940

920

905

860

815

750

25

26

26

27

27

26

26

24

23

21

Low

710

725

725

725

720

700

685

660

625

560

20

21

21

21

20

20

19

19

18

16

100/2000/C

High

2300

2210

2120

2020

1930

1830

1715

1595

1480

1350

65

63

60

57

55

52

49

45

42

39

Med-High

1950

1900

1830

1755

1680

1595

1500

1390

1270

1155

55

54

52

50

48

45

42

39

36

33

Med-Low

1610

1545

1490

1440

1390

1315

1230

1155

1050

920

46

44

42

41

39

37

33

33

30

26

Low

1325

1270

1225

1175

1105

1045

990

905

890

790

38

36

35

33

31

30

28

25

25

22

100/1600/C 

80/1600/C

High

1960

1955

1925

1890

1830

1765

1695

1615

1600

1485

56

55

55

54

52

50

48

46

45

42

Med-High

1565

1560

1560

1575

1545

1530

1475

1425

1365

1260

44

44

44

45

44

43

42

40

39

36

Med-Low

1230

1275

1285

1300

1310

1300

1280

1245

1190

1070

35

36

36

37

37

37

36

35

34

30

Low

930

945

965

975

975

975

975

950

910

850

26

27

27

28

28

28

28

27

26

24

120/2000/D

High

2560

2485

2410

2320

2220

2135

2035

1920

1785

1650

72

70

68

66

63

60

58

54

51

47

Med-High

2090

2050

1990

1970

1885

1820

1760

1675

1545

1405

59

58

56

56

53

52

50

47

44

40

Med-Low

1695

1675

1665

1615

1565

1510

1460

1385

1285

1140

48

47

47

46

44

43

41

39

36

32

Low

1175

1150

1135

1110

1085

1055

1005

980

970

845

33

33

32

31

31

30

28

28

27

24

Models

Input

Airflow/
Cabinet

Speed

Tap

Airflow with Two Side Returns or with Bottom and One 

Side Return - without Filters (CFM)

Airflow with Two Side Returns or with Bottom and One 

Side Return - without Filters (m

3

min)

External Static Pressure, Inches W.C.

External Static Pressure, Inches

 (kPa)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0.025 0.050 0.075 0.099 0.124 0.149 0.174 0.199 0.224 0.249

100/2000/C

HIGH

2465

2380

2295

2195

2095

1995

1875

1760

1620

1470

70

67

65

62

59

56

53

50

46

42

M-HI

2085

2035

1960

1880

1800

1705

1605

1485

1360

1235

59

58

55

54

51

48

45

42

39

35

M-LO

1725

1625

1595

1540

1485

1405

1315

1235

1125

995

49

46

45

44

42

40

37

35

32

28

LOW

1420

1360

1310

1255

1180

1120

1070

970

950

845

40

39

37

36

33

32

30

27

27

24

120/2000/D

HIGH

2615

2535

2450

2385

2285

2175

2075

1945

1825

1670

74

72

69

68

65

62

59

55

52

47

M-HI

2055

2045

2015

1985

1932

1855

1785

1730

1605

1470

58

58

57

56

55

53

51

49

45

42

M-LO

1690

1650

1620

1600

1570

1525

1470

1395

1300

1200

48

47

46

45

44

43

42

40

37

34

LOW

1345

1335

1335

1285

1250

1230

1180

1115

1010

850

38

38

38

36

35

35

33

32

29

24

TABLE 18: 

Filter Performance - Pressure Drop Inches W.C. and (kPa)

Airflow Range

Minimum 

Opening Size

Filter Type

Disposable

Washable Fiber

Pleated

CFM

m

3

/min

 in

2

   

cm

2

In W.C.

kPA

In W.C.

kPA

In W.C.

kPA

0 - 750

0 - 21.4

230

1484

0.01

0.00249

0.01

0.00249

0.15

0.03736

751 - 1000

21.25 - 28.32

330

2129

0.05

0.01245

0.05

0.01245

0.20

0.04982

1001 - 1250

28.33 - 35.40

330

2129

0.10

0.02491

0.10

0.02491

0.20

0.04982

1251 - 1500

35.41 - 42.48

330

2129

0.10

0.02491

0.10

0.02491

0.25

0.06227

1501 - 1750

42.49 - 49.55

380

2452

0.15

0.03736

0.14

0.03487

0.30

0.07473

1751 - 2000

49.56 - 56.63

380

2542

0.19

0.04733

0.18

0.04484

0.30

0.07473

2001 & Above

56.64 - Above

463

2987

0.19

0.04733

0.18

0.04484

0.30

0.07473

Содержание PT9-UP

Страница 1: ...AS PIPING 7 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 13 CONDENSATE PIPING 20 SAFETY CONTROLS 21 START UP AND ADJUSTMENTS 21 WIRING DIAGRAM 29 LIST OF FIGURES Dimensions 6 Gas Valve 7 Gas Pipi...

Страница 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Страница 3: ...or and the furnace must be located or protected to avoid physical damage by vehicles The furnace area must not be used as a broom closet or for any other storage purposes as a fire hazard may be creat...

Страница 4: ...TE When attaching duct flange do not shoot the screw down into the casing Use the formed flange intended for duct flange attachment The duct system is a very important part of the installation If the...

Страница 5: ...er This access cover shall be attached in such a manner as to prevent leaks TABLE 2 Minimum Duct Sizing For Proper Airflow Input Airflow Return1 Rectangular2 Round2 Supply3 Rectangular2 Round2 BTU H k...

Страница 6: ...combustibles and have floor support with required service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cu...

Страница 7: ...m of the fur nace The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at...

Страница 8: ...67 1100 3 2 2 7 2 4 41 0 0 80 0 66 0 61 2500 LP 9 8 8 2 7 5 93 2 LP 2 44 2 03 1 86 TABLE 6 Nominal Manifold Pressure Low Fire First Stage Manifold Pressures in wc First Stage Manifold Pressures kpa A...

Страница 9: ...wiring connections on the thermostat to the terminal board on the ignition module as shown in Figures 5 6 Electronic thermostats may require the common wire to be connected as shown in Figures 5 6 Ap...

Страница 10: ...unction Light E W1 First Stage Heat G Fan G Fan Connection of the C Termainal 24 Volt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Hea...

Страница 11: ...SG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Hea...

Страница 12: ...gas supplies must be provided as specified with these instruc tions Since the furnaces are side by side with no space between gas supplies must enter on the right and left respectively All gas piping...

Страница 13: ...e with Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code Z223 1 NFPA 54 latest edition or Sections 7 2 7 3 or 7 4 of CSA B149 1 National Gas and Propane Codes latest edition...

Страница 14: ...or horizontal models the transition from 2 to 3 pipe should be done immediately after the drain tee or drain elbow 7 In Canada vents shall be certified to ULC S636 Standard for Type BH Gas Venting Sys...

Страница 15: ...the following systems A Sealed combustion air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disas...

Страница 16: ...ons 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Страница 17: ...r systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 14 or 15 VENTING MULTIPLE UNITS Multiple units can be installed in a space...

Страница 18: ...e The combustion air intake pipe should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be taken to locate side vented systems where trees or s...

Страница 19: ...cm2 60 000 60 387 cm2 80 000 80 516 cm2 100 000 100 645 cm2 120 000 120 774 cm2 FIGURE 20 Outside and Ambient Combustion Air GABLE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIO...

Страница 20: ...Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this instruction or in Section 5 3 Air...

Страница 21: ...e controls are mounted on the burner box assembly If the temper ature in the burner box exceeds its set point the ignition control and the gas valve are de energized The operation of this control indi...

Страница 22: ...ll start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Aft...

Страница 23: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Страница 24: ...shown in Figure 24 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entirely...

Страница 25: ...The furnace control board also allows user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins WITH BURNER BOX COVER IN PL...

Страница 26: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the...

Страница 27: ...35 33 31 30 28 25 25 22 100 1600 C 80 1600 C High 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 56 55 55 54 52 50 48 46 45 42 Med High 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 44 44 44 4...

Страница 28: ...50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 2175 2285 110 CFM 3 11 m3 min Subtract the total system static from 0 50 w c 125 Pa and divide this difference by the differ...

Страница 29: ...272313 UIM A 0407 Unitary Products Group 29 SECTION X WIRING DIAGRAM FIGURE 27 Wiring Diagram...

Страница 30: ...272313 UIM A 0407 30 Unitary Products Group NOTES...

Страница 31: ...272313 UIM A 0407 Unitary Products Group 31 NOTES...

Страница 32: ...t to change without notice Printed in U S A 272313 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167487 UIM B 0806 Unitary 5005 Norman Product York OK Group Drive...

Отзывы: