background image

272313-UIM-A-0407

Unitary Products Group

19

confined space

 is an area with less than 50 cu.ft (1.42 m

3

) per 1,000

Btu/hr (0.2928 kW) input rating for all of the appliances installed in that
area. The following must be considered to obtain proper air for combus-
tion and ventilation in confined spaces.

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con-
sideration in calculating free area. If the free area of a specific louver or
grille is not known, refer to Table 12, to estimate free area.

*

Do not use less than 1/4” (0.635 cm) mesh.

+

Free area or louvers and grille varies widely; the installer should follow lou-
ver or grille 
manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.

The free area of a supply air opening shall be calculated by sub-
tracting the blockage area of all fixed louvers grilles or screens
from the gross area of the opening.

2.

Apertures in a fixed louver, a grille, or screen shall have no dimen-
sion smaller than 0.25” (6.4 mm).

3.

A manually operated damper or manually adjustable louvers are
not permitted for use.

4.

A automatically operated damper or automatically adjustable lou-
vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position

This type of installation requires that the supply air to the appli-
ance(s) be of a sufficient amount to support all of the appliance(s)
in the area. Operation of a mechanical exhaust, such as an exhaust
fan, kitchen ventilation system, clothes dryer or fireplace may cre-
ate conditions requiring special attention to avoid unsatisfactory
operation of gas appliances. A venting problem or a lack of supply
air will result in a hazardous condition, which can cause the appli-
ance to soot and generate dangerous levels of CARBON MONOX-
IDE, which can lead to serious injury, property damage and / or
death.

TABLE 12: 

Estimated Free Area

Wood or Metal

Louvers or Grilles

Wood 20-25%*

Metal 60-70% *

1/4” (0.635 cm)

mesh or larger 100%

TABLE 13: 

Free Area

BTUH Input 

Rating

Minimum Free Area Required for Each Opening

Horizontal Duct 

(2,000 BTUH)

Vertical Duct or 

Opening to Outside 

(4,000 BTUH)

Round Duct

(4,000 BTUH)

40,000

20 sq. in. (129 cm

2

)

10 sq. in. (64 cm

2

)

4” (10 cm)

60,000

30 sq. in. (194 cm

2

)

15 sq. in. (97 cm

2

)

5” (13 cm)

80,000

40 sq. in. (258 cm

2

) 20 sq. in. (129 cm

2

)

5” (13 cm)

100,000

50 sq. in. (323 cm

2

) 25 sq. in. (161 cm

2

)

6” (15 cm)

120,000

60 sq. in. (387 cm

2

) 30 sq. in. (194 cm

2

)

7” (18 cm)

EXAMPLE: Determining Free Area.
Appliance 1Appliance 

2Total 

Input

100,000 

+ 30,000 = (130,000 

÷

 4,000) = 32.5 Sq. In. Vertical

Appliance 1Appliance 

2Total 

Input

100,000 

+ 30,000 = (130,000 

÷

 2,000) = 65 Sq. In. Horizontal

TABLE 14: 

Unconfined Space Minimum Area in Square Inch

BTUH Input Rating

Minimum Free Area Required for Each Opening

40,000

40 (258 cm

2

)

60,000

60 (387 cm

2

)

80,000

80 (516 cm

2

)

100,000

100 (645 cm

2

)

120,000

120 (774 cm

2

)

 FIGURE 20:  

Outside and Ambient Combustion Air

GABLE
VENT

GAS
VENT

SOFFIT
VENT

VENTILATED

ATTIC

TOP ABOVE
INSULATION

OPTIONAL
INLET (a)

OUTLET
AIR (a)

VENTILATED

CRAWL SPACE

GAS
WATER
HEATER

VENTILATED

ATTIC

TOP ABOVE
INSULATION

GAS
VENT

GABLE
VENT

SOFFIT
VENT

GAS
WATER
HEATER

INLET
AIR (a)

INLET
AIR (b)

GAS
VENT

OUTLET
AIR (a)

OUTLET
AIR (b)

INLET
AIR (a)

INLET
AIR (b)

GAS
WATER
HEATER

FURNACE

1. An opening ma

y

be used in lieu of a duct to provide to provide the outside air

suppl

y

to an appliance unless otherwise permitted b

y

the authorit

y

having

jurisdiction. The opening shall be located within 12” (30.5 cm) horizontall

y

from,

the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS
AND VENT AND SUPPLY AIR SAFETY CHECK” in these instructions for
additional information and safet

y

check procedure.

2. The duct shall be either metal, or a material meeting the class 1

requirements of CAN4-S110 Standard for Air Ducts.

3. The duct shall be least the same cross-sectional area as the free

area of the air suppl

y

inlet opening to which it connects.

4. The duct shall terminate within 12 in (30.5 cm) above, and

within 24 in (61 cm) horizontall

y

from, the burner level of

the appliance having the largest input.

5. A square or rectangular shaped duct shall onl

y

be used

when the required free area of the suppl

y

opening is

9 in (58.06 cm ) or larger. When a square or rectangular
duct is used, its small dimensionshall not be less than
3 in (7.6 cm).

2

2

6. An air inlet suppl

y

from outdoors shall be equipped with

a means to prevent the direct entr

y

of rain and wind.

Such means shall not reduce the required free area of
the air suppl

y

opening.

7.

An air suppl

y

inlet opening from the outdoors shall

be located not less than 12” (30.5 cm) above the
outside grade level.

FURNACE

FURNACE

AIR SUPPLY OPENINGS AND DUCTS

COMBUSTION AIR SOURCE FROM OUTDOORS

1. Two permanent openings, one within 12 in (30.5 mm) of the top and

one within 12 in (30.5 mm) of bottom of the confined space,

shall communicate directl

y

or b

y

means of ducts

with the outdoors, crawl spaces or attic spaces.

Two

permanent openings,

2. One permanent openings, commencing within 12 in (30.5 mm)of the

top of the enclosure shall be permitted where the equipment has
clearances of at least 1 in (2.54 cm) from the sides and back and
6 in (15.24 cm) from the front of the appliance. The opening shall
communicate directl

y

with the outdoors and shall have a minimum

free area of:

3. The duct shall be least the same cross-sectional area as the free

area of the air suppl

y

inlet opening to which it connects.

1 square in per 3000 Btu per hour (6.45

0.879 kW) of the

total input rating of all equipment located in the enclosure.

cm per

3

a.

Not less than the sum of all vent connectors in the confined space.

b.

4. The blocking effects of louvers, grilles and screens must be given

consideration in calculating free area. If the free area of a specific
louver aor grille is not known.

Содержание PT9-UP

Страница 1: ...AS PIPING 7 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 13 CONDENSATE PIPING 20 SAFETY CONTROLS 21 START UP AND ADJUSTMENTS 21 WIRING DIAGRAM 29 LIST OF FIGURES Dimensions 6 Gas Valve 7 Gas Pipi...

Страница 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Страница 3: ...or and the furnace must be located or protected to avoid physical damage by vehicles The furnace area must not be used as a broom closet or for any other storage purposes as a fire hazard may be creat...

Страница 4: ...TE When attaching duct flange do not shoot the screw down into the casing Use the formed flange intended for duct flange attachment The duct system is a very important part of the installation If the...

Страница 5: ...er This access cover shall be attached in such a manner as to prevent leaks TABLE 2 Minimum Duct Sizing For Proper Airflow Input Airflow Return1 Rectangular2 Round2 Supply3 Rectangular2 Round2 BTU H k...

Страница 6: ...combustibles and have floor support with required service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cu...

Страница 7: ...m of the fur nace The furnace must be isolated from the gas supply piping system by closing its individual external manual shutoff valve during any pressure testing of the gas supply piping system at...

Страница 8: ...67 1100 3 2 2 7 2 4 41 0 0 80 0 66 0 61 2500 LP 9 8 8 2 7 5 93 2 LP 2 44 2 03 1 86 TABLE 6 Nominal Manifold Pressure Low Fire First Stage Manifold Pressures in wc First Stage Manifold Pressures kpa A...

Страница 9: ...wiring connections on the thermostat to the terminal board on the ignition module as shown in Figures 5 6 Electronic thermostats may require the common wire to be connected as shown in Figures 5 6 Ap...

Страница 10: ...unction Light E W1 First Stage Heat G Fan G Fan Connection of the C Termainal 24 Volt Common is optional when used with batteries Thermostat Installer Setup Number 1 System Type must be set to 6 2 Hea...

Страница 11: ...SG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor W2 Second Stage Auxiliary Heat W2 Second Stage Auxiliary Heat AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Hea...

Страница 12: ...gas supplies must be provided as specified with these instruc tions Since the furnaces are side by side with no space between gas supplies must enter on the right and left respectively All gas piping...

Страница 13: ...e with Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code Z223 1 NFPA 54 latest edition or Sections 7 2 7 3 or 7 4 of CSA B149 1 National Gas and Propane Codes latest edition...

Страница 14: ...or horizontal models the transition from 2 to 3 pipe should be done immediately after the drain tee or drain elbow 7 In Canada vents shall be certified to ULC S636 Standard for Type BH Gas Venting Sys...

Страница 15: ...the following systems A Sealed combustion air systems from the furnace to the out side termination B Ventilated combustion air systems from the furnace to the attic or crawl space termination 6 Disas...

Страница 16: ...ons 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Страница 17: ...r systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 14 or 15 VENTING MULTIPLE UNITS Multiple units can be installed in a space...

Страница 18: ...e The combustion air intake pipe should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be taken to locate side vented systems where trees or s...

Страница 19: ...cm2 60 000 60 387 cm2 80 000 80 516 cm2 100 000 100 645 cm2 120 000 120 774 cm2 FIGURE 20 Outside and Ambient Combustion Air GABLE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIO...

Страница 20: ...Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this instruction or in Section 5 3 Air...

Страница 21: ...e controls are mounted on the burner box assembly If the temper ature in the burner box exceeds its set point the ignition control and the gas valve are de energized The operation of this control indi...

Страница 22: ...ll start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Aft...

Страница 23: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Страница 24: ...shown in Figure 24 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entirely...

Страница 25: ...The furnace control board also allows user selection of the blower speed that is energized during continuous fan operation Place jumper on the HI COOL LO COOL or HEAT pins WITH BURNER BOX COVER IN PL...

Страница 26: ...out Low gas pressure faulty gas valve faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the...

Страница 27: ...35 33 31 30 28 25 25 22 100 1600 C 80 1600 C High 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 56 55 55 54 52 50 48 46 45 42 Med High 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 44 44 44 4...

Страница 28: ...50 w c 125 Pa from the airflow 0 60 w c 150 Pa to obtain airflow difference 2175 2285 110 CFM 3 11 m3 min Subtract the total system static from 0 50 w c 125 Pa and divide this difference by the differ...

Страница 29: ...272313 UIM A 0407 Unitary Products Group 29 SECTION X WIRING DIAGRAM FIGURE 27 Wiring Diagram...

Страница 30: ...272313 UIM A 0407 30 Unitary Products Group NOTES...

Страница 31: ...272313 UIM A 0407 Unitary Products Group 31 NOTES...

Страница 32: ...t to change without notice Printed in U S A 272313 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167487 UIM B 0806 Unitary 5005 Norman Product York OK Group Drive...

Отзывы: