background image

035-19624-001 Rev. A (0104)

10

Unitary Products Group

COMBUSTION AIR/VENT PIPE SIZING

Select the correct size from Table 9. The size will be determined by a
combination of furnace model, total length of run, and the number of
elbows required. The following rules must also be observed.

1.

Long radius (sweep) elbows are required for all units.

2.

Elbows are assumed to be 90 degrees. Two 45-degree elbows
count as one 90-degree elbow.

3.

Elbow count refers to combustion air piping and vent piping sepa-
rately. For example, if the table allows for 5 elbows, this will allow a
maximum of 5 elbows in the combustion air piping and a maximum
of 5 elbows in the vent piping.

4.

For Horizontal Applications the three vent terminal elbows (two for
vent pipe and one for air intake pipe) are already accounted for as
vent termination. Vertical vent applications does not require an
elbow for termination.

5.

Combustion air and vent piping must be of the same diameter.

6.

All combustion air/vent pipe and fittings must conform to American
National Standards Institute (ANSI) standards and American Soci-
ety for Testing and Materials (ASTM) standards D1785 (Schedule
40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core).
D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628
(Schedule 40 ABS. Pipe cement and primer must conform to
ASTM Standards D2564 (PVC) or D2235 (ABS).

7.

The use of flexible connectors or no hub connectors in the vent
system is not allowed. This type connection is allowed in the com-
bustion air pipe near the furnace for air conditioning coil accessibil-
ity.

8.

Sidewall horizontal vent terminals and roof mounted vertical termi-
nals may be field fabricated. Standard PVC/SRD fittings may be
used. Terminal configuration must comply as detailed in this sec-
tion.

9.

The minimum vent length is 5 ft. (1.524 m).
The maximum vent length is up to 75 ft. (22.86 m) on same mod-
els. Refer to Table 9 for maximum vent length's.

10. If the Outdoor Combustion Air and vent pipe configuration is

desired, the combustion air pipe and the vent pipe must terminate
together in the same atmospheric zone regardless whether a hori-
zontal (sidewall) or vertical (roof) termination is desired.

*. Vent pipe size must be increased to 3” diameter after connection to furnace on this model.

IMPORTANT: 

Accessory concentric vent / intake termination kits

1CT0302 and 1CT0303 are available and approved for use with these
furnaces.

IMPORTANT: 

Furnace vent pipe connections are sized for 2-in. pipe.

Any pipe size change must be made outside the furnace casing in a
vertical pipe section to allow proper drainage of condensate. An offset
using two 45º (degree) elbows will be required for plenum clearance
when the vent is increased to 3”.

*. Elbow count does not include the elbows required for the termination. See Step 4 under Combustion Air/Vent Pipe Sizing.

NOTE: If installing furnace at altitudes between 2000 - 4500 ft. (610 – 1372 m), intake and vent pipe length must be reduced by 10 ft. (3.05 m). If the installation requires the maximum allowable 

intake and vent pipe length, the furnace must be converted for high altitude operation. Refer to SECTION IV “GAS PIPING” of these instructions and the proper high altitude application 
instruction for details.

NOTE: 

If installing furnace at altitudes between 2000 - 4500 ft., intake

and vent pipe length must be reduced by 10 ft. If the installation
requires the maximum allowable intake and vent pipe length, the
furnace must be converted for high altitude operation. Refer to
the proper high altitude application instruction for details.

COMBUSTION AIR AND VENT PIPING ASSEMBLY

The final assembly procedure for the combustion air and vent piping is
as follows:

1.

Cut piping to the proper length beginning at the furnace.

2.

Deburr the piping inside and outside.

3.

Chamfer (bevel) the outer edges of the piping.

4.

Dry-fit the vent piping assembly from the furnace to the outside ter-
mination checking for proper fit support and slope.

5.

Dry-fit the combustion air piping assembly checking for proper fit,
support and slope on the following systems:

A.

Sealed combustion air systems from the furnace to the out-
side termination.

B.

Ventilated combustion air systems from the furnace to the
attic or crawl space termination.

6.

Disassemble the combustion air and vent piping, apply cement
primer and the cement per the manufactures instructions. Primer
and cement must conform to ASTM D2564 for PVC, or ASTM
D2235 for ABS piping.

7.

All joints must provide a permanent airtight and watertight seal.

8.

Support the combustion air and vent piping such that it is angled a
minimum of 1/4” per foot (21 mm/m) so that condensate will flow
back towards the furnace. Piping should be supported with pipe
hangers to prevent sagging.

9.

Seal around the openings where the combustion air and / or vent
piping pass through the roof or sidewalls.

COMBUSTION AIR / VENT CLEARANCES

IMPORTANT: 

The vent must be installed with the following minimum

clearances, and must comply with local codes and requirements.

TABLE 8: 

Combustion Air Intake and Vent Connection Size at Furnace 

(All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

60 - 100 MBH 

(17.6-29.3 kW)

120 MBH

 (35.17 kW)

Intake Pipe Size

2” (50.8 mm)

3" (76.2 mm)

Vent Pipe Size

2” (50.8 mm)

2"* (50.8 mm)

TABLE 9: 

Combustion Air Supply and Vent Piping

MODELS

Max. Elbows vs. One Way Vent Length (Ft.) (m)*

Low Fire 

Heating Input

Low Fire

Heating Output

High Fire 

Heating Input

High Fire

Heating Output

Furnace

Airflow

Pipe Size

Pipe Size

5 - 40

45

50

75

BTU/H

kW

BTU/H

kW

BTU/H

kW

BTU/H

kW

CFM

m

3

/min

Inches

mm

(1.5 - 12.2 m)

(13.7 m)

(15.2 m)

(22.9 m)

39,000

11.43

36,000

10.55

60,000

17.58

55,000

16.12

1200

33.98

2

50.8

6

5

4

N/A

52,000

15.24

48,000

14.07

80,000

23.45

75,000

21.98

1600

45.31

65,000

19.05

60,000

17.58

100,000

29.31

95,000

27.84

2000

56.63

39,000

11.43

36,000

10.55

60,000

17.58

55,000

16.12

1200

33.98

3

76.2

8

7

6

5

52,000

15.24

48,000

14.07

80,000

23.45

75,000

21.98

1600

45.31

65,000

19.05

60,000

17.58

100,000

29.31

95,000

27.84

2000

56.63

78,000

22.86

72,000

21.10

120,000

22.86

112,000

32.82

2000

56.63

3" only

76 mm only

6

5

4

N/A

Solvent cements are flammable and must be used in well-ventilated
areas only. Keep them away from heat, sparks and open flames.
Do not breathe vapors and avoid contact with skin and eyes.

Содержание P XU-V/G9V-UP Series

Страница 1: ... TABLE OF CONTENTS SAFETY 1 DUCTWORK 3 FILTERS 6 GAS PIPING 6 COMBUSTION AIR AND VENT SYSTEM 9 CONDENSATE DRAIN 16 SAFETY CONTROLS 16 START UP AND ADJUSTMENTS 17 WIRING DIAGRAM 25 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Perforated Panel 5 Furnace Filter Slot Locations 6 Filter Retainer Placement 6 Side Return Cutout Markings 6 Gas Valve 6 Gas Piping 7 Electrical Wiring 8 Line Wiring ...

Страница 2: ...rnace is not approved for installation in trailers or recre ational vehicles Failure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combustible flooring shall not be installed directly on carpeting tile or other combustible material other than wood flooring Check the rating pla...

Страница 3: ...age to the front when servicing or for inspection or replacement of flue vent connections In all cases accessibility clearances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage 13 A gas fired furnace for installation in a residential garage must be installed so the burner s and the ignition source are l...

Страница 4: ...l static pressure includes the pressure drop across the return air filter and A coil TABLES 2 AND 3 are to be used as a guide only to help the installer determine if the duct sizes are large enough to obtain the proper air flow CFM through the furnace TABLES 2 and 3 ARE NOT to be used to design ductwork for the building where the furnace is being installed There are several variables associated wi...

Страница 5: ...Figure 2 for flange locations 4 Be sure to seal the furnace to plenum connections to prevent air leakage Refer to Figure 1 for unit and plenum dimensions Attic installations must meet all minimum clearances to combustibles and have floor support with required service accessibility IMPORTANT if an external mounted filter rack is being used see the instructions provided with that accessory for prope...

Страница 6: ...lter s is provided at another location in the return air system the ductwork may be directly attached to the furnace side panel An accessory filter rack is available for mounting the filter exter nal to the cabinet IMPORTANT Some accessories such as electronic air cleaners and pleated media may require a larger side opening Follow the instruc tions supplied with that accessory for side opening req...

Страница 7: ...ernal pressure Never apply a pipe wrench to the body of the gas valve when installing piping A wrench must be placed on the octa gon hub located on the gas inlet side of the valve Placing a wrench to the body of the gas valve will damage the valve causing improper operation and or the valve to leak CHECKING THE GAS PRESSURES 1 The pressure ports on the gas valve are on the inlet and outlet sides o...

Страница 8: ...to Figure 8 3 The furnace s control system requires correct polarity of the power supply and a proper ground connection Refer to Figure 9 or FURNACE CONTROL DIAGONSICS for symptoms of reversed power supply polarity IMPORTANT The power connection leads and wiring box may be relo cated to the left side of the furnace Remove the screws and cut wire tie holding excess wiring Reposition on the left sid...

Страница 9: ...sions of the local building code and these instructions IMPORTANT The VENT SYSTEM must be installed as specified in these instructions for Residential and Non HUD Modular Homes The sealed combustion air vent system is the only configuration that can be installed in a Non HUD Modular Home FIGURE 10 Field Wiring for Single Stage Thermostat FIGURE 11 Field Wiring for Two Stage Thermostat Set the heat...

Страница 10: ...gth the furnace must be converted for high altitude operation Refer to SECTION IV GAS PIPING of these instructions and the proper high altitude application instruction for details NOTE If installing furnace at altitudes between 2000 4500 ft intake and vent pipe length must be reduced by 10 ft If the installation requires the maximum allowable intake and vent pipe length the furnace must be convert...

Страница 11: ...listed in vent clearances in these instruc tions 2 Termination should be positioned where vent vapors will not dam age plants or shrubs or air conditioning equipment FIGURE 13 Home Layout L E D B V V V X V B V J X B B B V V F V C B X V I V G H A M K OPERABLE FIXED CLOSED FIXED CLOSED VENT TERMINAL AIR SUPPLY AREA WHERE TERMINAL IS NOT PERMITTED Canadian Installations1 US Installation2 A Clearance ...

Страница 12: ...m diameter pipe that has a minimum length of 3 76 mm long into the reducer to serve as a nipple IMPORTANT Tee reducer and nipple must be properly cemented together using the appropriate method and materials specified in COMBUSTION AIR AND VENT PIPING ASSEMBLY in these instruc tions 4 Connect a piece of flexible drain tubing such as EPDM rubber or PVC to the nipple 5 Loop the drain tubing to provid...

Страница 13: ...ected to the PVC coupling attached to the burner box and is terminated in the same atmospheric zone as the vent This type of installation is approved on all models 2 AMBIENT COMBUSTION AIR Combustion air is supplied from the area surrounding the furnace through vents or knockouts in the furnace casing The combustion air and the vent pipes are not ter minated in the same atmospheric zone Refer to F...

Страница 14: ...res in a fixed louver a grille s or screen shall have no dimension smaller than 0 25 6 4 mm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position FIGURE 21 Combustion A...

Страница 15: ... OUTDOORS in this instruction or in Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 latest edition This type installation requires two properly sized pipes One brings combustion air from a properly ventilated attic space or crawl space and a second pipe that extends from the furnace vent connection top right of unit to the exterior of the building Refer to ...

Страница 16: ...rnace A condensate sump pump MUST be used if required by local codes or if no indoor floor drain is available The condensate sump pump must be approved for use with acidic condensate CONDENSATE DRAIN TRAP AND DRAIN FREEZE PROTECTION Special precautions MUST be made if installing furnace in an area which may drop below freezing This can cause improper operation or damage to the equipment If the fur...

Страница 17: ...ow five minutes for any gas to dissipate before continuing with the start up procedure TOOLS AND INFORMATION THAT WILL BE REQUIRED IN ORDER TO PROPERLY PERFORM THE FURNACE STARTUP PROCEDURE 1 Call the local gas supplier to obtain heating value of the natural gas If you cannot obtain the heating valve of the gas from the gas supplier you may use a default value of 1030 BTU SCF 38 8 MJ m 2 You will ...

Страница 18: ...ystem during any pressure testing of the system where test pressures are in excess of 1 2 PSI 3 45 kPa CALCULATING THE FURNACE INPUT NATURAL GAS NOTE Front door of burner box must be secured when checking gas input NOTE Burner orifices are sized to provide proper input rate using nat ural gas with a heating value of 1050 BTU Ft3 If the heating value of your gas is significantly different it may be...

Страница 19: ...om the gas meter The formula for metric input calculation using a cubic foot gas meter DO NOT ADJUST the manifold pressure regulator if the actual input is equal to or within 8 less than the furnace input specified on the rating plate or if the furnace rise is above the specified rise range on the rating plate If the actual input is significantly higher than the furnace input specified on the rati...

Страница 20: ... regulator until pressure shown on manometer matches the pressure specified on the appliance rating plate 6 Replace low adjustment seal screw and tighten securely Cycle the valve several times to verify regulator setting 7 Remove manometer and replace the outlet pressure tap plug Low Outlet Pressure Adjustment 1 Turn off all electrical power to the system at main fuse or circuit breaker 2 Attach a...

Страница 21: ...ver if one is not available a 3 speed direct drive motor may be used in the interim Removal of the Variable Speed Blower Assembly and Motor The procedure for removing the direct drive blower assembly is as fol lows 1 Disconnect the electrical supply to the furnace and remove the access doors 2 Remove blower assembly mounting screws and slide the blower assembly out of the slots in the deck If the ...

Страница 22: ...nt of the maximum CFM The heating and cooling airflows must be field adjusted to match the HVAC system at installation CFM Timer Board Delay Taps Selection Position A is the factory setting and is used for test purposes The blower will operate at 100 of the cooling airflow for 60 seconds Move the jumper to Position B for a two stage condenser This results in 82 of the cooling airflow with a 45 sec...

Страница 23: ...ap ADJ Tap 2030 1090 57 48 30 87 2180 1210 61 73 34 26 A B 1780 945 50 40 26 76 1760 970 49 84 27 47 B B 1890 1000 53 52 28 32 2000 1100 56 63 31 15 A A 1630 850 46 16 24 07 1600 910 45 31 25 77 B A 1685 895 47 71 25 34 1780 990 50 40 28 03 A C 1555 830 44 03 23 50 1540 860 43 61 24 35 C B 1430 785 40 49 22 23 1410 820 39 93 23 22 B C 1310 740 37 10 20 95 1300 770 36 81 21 80 D B 1400 770 39 64 21...

Страница 24: ...a to obtain airflow difference 2035 2125 90 CFM 2 55 m3 min Subtract the total system static from 0 50 w c 125 Pa and divide this difference by the difference in ESP values in the table 0 60 w c 150 Pa 0 50 w c 125 Pa to obtain a percentage 0 58 0 50 0 60 0 50 0 8 Multiply percentage by airflow difference to obtain airflow reduction 0 8 X 90 72 Subtract airflow reduction value to airflow 0 50 w c ...

Страница 25: ...035 19624 001 Rev A 0104 Unitary Products Group 25 SECTION X WIRING DIAGRAM FIGURE 30 Wiring Diagram ...

Страница 26: ...035 19624 001 Rev A 0104 26 Unitary Products Group NOTES ...

Страница 27: ...035 19624 001 Rev A 0104 Unitary Products Group 27 ...

Страница 28: ...ect to change without notice Printed in U S A 035 19624 001 Rev A 0104 Copyright by York International Corp 2004 All rights reserved Supersedes Nothing Unitary 5005 Norman Product York OK Group Drive 73069 ...

Отзывы: