SUPPLY AIR BLOWER ADJUSTMENT
The RPM of the supply air blower will depend on the required
CFM, the unit accessories and the static resistances of both
the supply and the return air duct system. With this informa-
tion, the RPM for the supply air blower can be determined
from the blower performance shown in Table 9.
Knowing the required blower RPM and the blower motor HP,
the setting (turns open) for the supply air motor pulley can be
determined from Table 8.
Each motor pulley has:
1.
A threaded barrel with two flats (or notched recesses)
180 degrees apart.
2.
A movable flange with one set screw.
After the movable flange has been rotated to the proper num-
ber of “turns open”; the set screw should be tightened against
the flat on the barrel to lock the movable flange in place. If the
pulley includes a locking collar, the locking collar must be
loosened to adjust the setting of the movable flange.
Note the following:
1.
The supply air CFM must be within the limitations shown
in Table 3.
2.
All Pulleys can be adjusted in half turn increments.
3.
The tension on the belt should be adjusted for a deflec-
tion of 3/16 of an inch per foot of belt span with an
applied force of 2 to 3 pounds. Moving the blower motor
mounting plate makes this adjustment. Refer to Figure
13. Turning the adjustment bolt (B) moves the motor
mounting plate up or down. Note - NEVER loosen the
two nuts (C). Two hex nuts (A) have to be loosened to
move the mounting plate and retighten after the mount-
ing plate has been moved to the proper position.
TABLE 7: KBU, KBC ELECTRICAL DATA (CONTINUED)
Model
(TONS)
Power
Supply
Voltage
Indoor
Motor
FLA
Heater
Model
Number
Nominal
Heater
KW
Applied
Heater KW
Electric
Heat Amps
Min.
Circuit
Ampacity
(AMPS)
Max. Fuse
1
/
HACR
Breaker
2
(AMPS)
180
(15)
208
10.6
None
--
--
--
13.3
20
2HS04501025
10
7.5
20.8
39.3
40
2HS04501625
16
12.0
33.4
54.9
60
2HS04502625
26
19.5
54.2
81.0
90
2HS04503625
36
27.0
75.1
107.1
110
2HS04507225
72
54.1
150.1
200.9
225
240
9.6
None
--
--
--
12.0
15
2HS04501025
10
10.0
24.1
42.1
45
2HS04501625
16
16.0
38.5
60.1
70
2HS04502625
26
26.0
62.5
90.2
100
2HS04503625
36
36.0
86.6
120.3
125
2HS04507225
72
72.0
173.2
228.5
250
460
4.8
None
--
--
--
6.0
15
2HS04501046
10
10.0
12.0
21.0
25
2HS04501646
16
16.0
19.2
30.1
35
2HS04502646
26
26.0
31.3
45.1
50
2HS04503646
36
36.0
43.3
60.1
70
2HS04507246
72
72.0
86.6
114.3
125
575
3.9
None
--
--
--
4.9
15
2HS04501058
10
10.0
9.6
16.9
20
2HS04501658
16
16.0
15.4
24.1
25
2HS04502658
26
26.0
25.0
36.1
40
2HS04503658
36
36.0
34.6
48.2
50
2HS04507258
72
72.0
69.3
91.5
100
1.
Dual element time delay.
2.
HACR type per NEC.
3.
The K*BU060 indoor motor is single phase. The electrical heaters MUST be supplied with 3-phase voltage only.