Unitary products group HDHB180 Скачать руководство пользователя страница 7

CAUTION: Do not attempt to start the compressor without at

least eight hours of crankcase heat or compressor
damage will occur.

If a unit has just been installed or the unit disconnect switch has
been open for a long period of time, move the system switch on
the room thermostat to the “OFF” position before closing the
unit disconnect switch. Eight hours of crankcase heat are re-
quired to drive the liquid refrigerant out of the compressor bef-
ore the compressor can be started.

REFRIGERANT PIPING

GENERAL GUIDELINES

Many service problems can be avoided by taking adequate
precautions to provide an internally clean and dry system and
by using procedures and materials that conform with estab-
lished standards.

Use hard drawn copper tubing where no appreciable amount of
bending around pipes or other obstructions is necessary. Use
long radius ells wherever possible with one exception—short
radius ells for the traps in all suction risers. If soft copper is
used, care should be taken to avoid sharp bends which may
cause a restriction.

Pack fiber glass insulation and a sealing material such as per-
magum around refrigerant lines where they penetrate a wall to
reduce vibrations and to retain some flexibility.

Support all refrigerant lines at minimum intervals with suitable
hangers, brackets or clamps.

Braze all copper to copper joints with Silfos-5 or equivalent
brazing material. Do not use soft solder.

Insulate all suction lines with a minimum of 1/2" ARMAFLEX or
equal. Liquid lines exposed to direct sunlight and/or high tem-
peratures must also be insulated.

Never solder suction and liquid lines together. They can be
taped together for convenience and support purposes, but they
must be completely insulated from each other.

A filter-drier MUST be installed in the liquid line of every system
to prevent dirt and moisture from damaging the system. A
properly-sized filter-drier is shipped with each condensing unit

for field installation near the evaporator coil. The filter-drier is
shipped inside the unit control box.

NOTE: Installing a filter-drier does not eliminate the need for

the proper evacuation of a system before it is
charged.

A moisture indicating sight-glass may be field installed in the
liquid line(s) between the filter-drier and the evaporator coil.
The moisture indicating sight-glass can be used to check for
excess moisture in the system or used as a visual means to
verify refrigerant charge.

LINE SIZING

When sizing refrigerant lines for a split-system air conditioner,
check the following:

1. Suction line pressure drop due to friction at full capacity,

2. Liquid line pressure drop due to friction at full capacity,

3. Suction line velocity for oil return at half capacity, and

4. Liquid line pressure drop due to static head.

NOTE: Never base refrigerant line sizes on the OD of the suc-

tion and liquid connections on the unit.

Tables 4 and 5 list friction losses for both the suction and liquid
lines on the system. Table 6 shows the amount of refrigerant
charge required per foot of refrigerant line.

When the evaporator coil is below the condensing unit, the suc-
tion line must be sized for both pressure drop and for oil return.
For certain piping arrangements, different suction line sizes
may have to be used. The velocity of the suction gas must al-
ways be great enough to carry oil back to the compressor.

When the condensing unit is below the evaporator coil, the liq-
uid line must be designed for the pressure drop due to both fric-
tion loss and vertical rise. If the total pressure drop exceeds 40
psi, some refrigerant may flash before it reaches the thermal
expansion valve. This flashing will not only cause erratic valve
operation and poor system performance, but could also dam-
age the expansion valve.

SERVICE VALVES

These condensing units have service valves on both the com-
pressor suction and discharge connections and on the liquid
line leaving the condenser coil.

The liquid and suction line service valves are shipped from the
factory front-seated and closed with the valve stem in the maxi-
mum clockwise position. The discharge service valve is

Unitary Products Group

7

035-17393-000 Rev. A (0501)

Model
Designation

Nominal
Capacity
(Tons)

Refrigerant
Flow Rate

3

(Lbs./Min.)

Type L
Copper Tubing
(Inches O.D.)

Refrigerant
Gas
Velocity
(FT./Min.)

Friction
Loss 4, 5
(PSI/100 Ft.)

HHB180

Full
Capacity

15

45

1-5/8
2-1/8

2300
1360

2.5
0.6

Half
Capacity

8-1/2

25.5

1-5/8
2-1/8

1150

680

6

0.7
0.2

HHB240

Full
Capacity

20

60

1-5/8
2-1/8
2-5/8

3120
1800
1200

4.3
1.2
0.4

Half
Capacity

10

30

1-5/8
2-1/8
2-5/8

1560

900

6

600

6

1.2
0.3
0.1

1

All horizontal suction lines should be pitched at least 1 inch every 20 feet in the direction of the refrigerant flow to aid the return of oil to the compressor.

2

Every vertical suction riser greater than 3 feet in height should have a “P” trap at the bottom to facilitate the return of oil to the compressor. Use short radius fittings for these traps.

3

Based on Refrigerant-22 at the nominal capacity of the condensing unit, a suction temperature of 40

°

F and a liquid temperature of 105

°

F.

4

Although suction lines should be sized for a friction loss equivalent to a 2

°

F change in saturation temperature (or approximately 3 psi), sizing the lines for the proper return of oil

is more important.

5

These friction losses do not include any allowances for valves or fittings.

6

Since the refrigerant gas velocity may be too low to maintain good oil return up a vertical riser, use the next smaller size. The larger size may be used for horizontal runs for a lesser

pressure drop.

TABLE 4 - SUCTION LINES

1,2

Содержание HDHB180

Страница 1: ...it REFERENCE This instruction covers the installation and operation of the ba sic condensing unit For information on the installation and op eration of the evaporator blower units refer to instruction...

Страница 2: ...Secure Owner s Approval 13 Maintenance 13 Cleaning Condenser Surface 13 Lubrication 13 Compressor Replacement 13 TABLES No Description Page 1 Unit Application Data 3 2 Physical Data 4 3 Electrical Da...

Страница 3: ...fs check for special installation requirements GROUND LEVEL LOCATIONS The units must be installed on a one piece level concrete slab with a minimum thickness of 4 inches The length and width should be...

Страница 4: ...ances Follow manufacturer s instructions enclosed with ther mostat for general installation procedure Refer to Figure 3 for typical field wiring COMPRESSOR After the unit is in its final position the...

Страница 5: ...A 208 230 3 60 2 32 1 195 2 1 4 7 81 6 110 HDHBW180A 460 3 60 2 16 4 95 2 1 2 5 41 9 50 HDHBX180A 575 3 60 2 12 80 2 1 2 0 31 2 40 HDHBT240A 208 230 3 60 2 42 239 2 1 4 7 103 9 125 HDHBW240A 460 3 60...

Страница 6: ...tion is expected is expected CLEARANCES All dimensions are in inches They are sub ject to change without notice Certified di mensions will be provided upon request Connection Entry Connection Size 15...

Страница 7: ...turn at half capacity and 4 Liquid line pressure drop due to static head NOTE Never base refrigerant line sizes on the OD of the suc tion and liquid connections on the unit Tables 4 and 5 list frictio...

Страница 8: ...8 0 047 lb ft TABLE 6 REFRIGERANT 22 LINE CHARGE1 NOTE Add the operating charge of the condensing unit the evaporator coil and the refrigerant lines to determine the total refrigerant charge of the sy...

Страница 9: ...the evaporator coil as possible Do not allow the filter drier to be exposed to the atmos phere for an extended period of time Once it absorbs moisture from the atmosphere it loses its effective ness T...

Страница 10: ...nit and the refrigerant lines using information in Tables 2 Physical Data and 6 Refrigerant Line Charge Using the charging procedures outlined above weigh the re quired amount of refrigerant charge in...

Страница 11: ...ressure Discharge Pressure 115 F Ambient 105 F Ambient 95 F Ambient 85 F Ambient 75 F Ambient Charging Curve HDHB240 200 250 300 350 400 57 62 67 72 77 82 87 92 97 Suction Pressure Discharge Pressure...

Страница 12: ...0 volts the LOR coil is no longer energized closing the LOR 1 contacts and removing the lock out The low pressure bypass timer 1TR leaves the 1TR 1 contacts closed upon the start of a call for coolin...

Страница 13: ...low ambient operation to 0 F SAFETY FEATURES 1 The compressor is protected against over current and ex cessive temperature as described in the Sequence of Op eration 2 The compressor is equipped with...

Страница 14: ...14 Unitary Products Group 035 17393 000 Rev A 0501...

Страница 15: ...Unitary Products Group 15 035 17393 000 Rev A 0501...

Страница 16: ...to change without notice Printed in U S A Copyright by Unitary Products Group 1998 All rights reserved Supersedes Nothing Code SBL F E Unitary Products Group 5005 Interstate Drive North Norman Oklahom...

Отзывы: