![Unitary products group HDHB180 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/unitary-products-group/hdhb180/hdhb180_installation-instruction_4033801005.webp)
Unitary Products Group
5
035-17393-000 Rev. A (0501
FIG. 3 - TYPICAL FIELD WIRING
TABLE 3 - ELECTRICAL DATA (Installation); ELECTRICAL DATA (Sales)
Compressor
Condenser Fan Motor
Unit
Model
Unit Power
Supply
Qty
RLA
LRA
Qty
HP
FLA
Minimum
Circuit
Ampacity
(Amps)
Maximum
Fuse
Size
1
(Amps)
HDHBT180A
208/230/3/60 2
32.1
195
2
1
4.7
81.6
110
HDHBW180A 460/3/60
2
16.4
95
2
1
2.5
41.9
50
HDHBX180A
575/3/60
2
12
80
2
1
2.0
31.2
40
HDHBT240A
208/230/3/60 2
42
239
2
1
4.7
103.9
125
HDHBW240A 460/3/60
2
19.2
125
2
1
2.5
48.2
60
HDHBX240A
575/3/60
2
13.8
80
2
1
2.0
35
45
1. Dual element, time delay type.
2. The 208-230 V compressors and motors use a single tap for the entire range of voltages. The 208/230 V to 24 V transfo
have different taps for 208 and 230 V.
TABLE 3 - ELECTRICAL DATA