035-14519-002 Rev. B (1204)
Unitary Products Group
9
*
May be 0 (no breaker) or 1 (with breaker).
** If first stage heat or 66 is connected to W1, otherwise refer to this table.
*
May be 0 (no breaker) or 1 (with breaker).
** If first stage heat or 66 is connected to W1, otherwise refer to this table.
TABLE 4:
Physical and Electrical Data
Models F2FV / F3FV(T)
060
Blower - Diameter x Width
11 x 10
Motor
HP
1.0
Nominal RPM
1200
Voltage
208 / 230
Amps
Full Load
7.8 / 7.0
Locked Rotor
–
Filter
1
Type
Disposable or Permanent
Size
22 x 20 x 1
Permanent Type Kit
1PF603BK
Shipping / Operating Weight (lbs.) - FP
160
TABLE 5:
Conversion Table
KW & MBH Conversions - for Total Power Input Requirement
FOR
208V
OPERATION
MULTIPLY
240V
TABULATED KW & MBH BY
.751
230V
240V
.918
TABLE 6:
Electrical Data - 1 Ø - 208/230-1-60
1
Models
Heater
Model
Max. Static
& Min. CFM
Total Heat
2
KW Staging**
KW
MBH
W1 Only
W2 Only
W1 + W2
Static
Tap
208V
240V
208V
240V
208V
240V
208V
240V
208V
240V
F2FV060H06
F3FV060H06T
2HK*6500806B
0.5
1335
5.6
7.5
19.1
25.6
3.8
5.0
5.6
7.5
5.6
7.5
2HK*6501006B
7.5
10.0
25.6
34.1
3.8
5.0
7.5
10.0
7.5
10.0
2HK16501506B
11.3
15.0
38.6
51.2
3.8
5.0
7.5
10.0
11.3
15.0
2HK16502006B
15.0
20.0
51.2
68.3
3.8
5.0
7.5
10.0
15.0
20.0
2HK16502506B
18.8
25.0
64.2
85.3
3.8
5.0
11.3
15.0
18.8
25.0
1. Heat amps shown at 240V represents maximum heater rating.
2. See conversion Table 5.
TABLE 7:
Electrical Data - 3 Ø - 208/230-3-60
1
Models
Heater
Model
Max. Static
& Min. CFM
Total Heat
2
KW Staging**
KW
MBH
W1 Only
W2 Only
W1 + W2
Static
Tap
208V
240V
208V
240V
208V
240V
208V
240V
208V
240V
F2FV060H06
F3FV060H06T
2HK06501025B
0.5
1335
7.5
10.0
25.6
34.1
3.8
5.0
7.5
10.0
7.5
10.0
2HK06501525B
11.3
15.0
38.8
51.2
3.8
5.0
7.5
10.0
11.3
15.0
1. Heat amps shown at 240V represents maximum heater rating.
2. See conversion Table 5.
TABLE 8:
Electrical Data - Cooling Only
MODEL
Minimum Circuit
Ampacity
ALL VOLTAGES
06
Max. O.C.P.
1
Amps/Type
75
°
C Wire Size - AWG
208V
240V
F2FV060H06
F3FV060H06T
9.7
8.8
15
14
1.
OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.