background image

Subject to change without notice. Printed in U.S.A.

035-14519-002 Rev. B (1204)

Copyright

 ©

 by York International Corp. 2004. All rights reserved.

Supersedes:  035-14519-002 Rev. A (0604)

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

DRAIN CONNECTIONS

All drain lines should be trapped a minimum of three inches, should be
pitched away from unit drain pan and should be no smaller than the coil
drain connection.

Route the drain line so that it does not interfere with accessibility to the
coil, air handling system or filter and will not be exposed to freezing
temperatures. See Figures 2, 3 and 4.

NOTE: 

When the coil is installed in an attic or above a finished ceiling,

an auxiliary drain pan should be provided under the coil as is
specified by most local building codes.

Coils should be installed level or pitched slightly toward the drain end.
Suggested pitch should not exceed 1/4 inch per foot of coil.

The coil is provided with a secondary drain that should be trapped and
piped to a location that will give the occupant a visual warning that the
primary drain is clogged. If the secondary drain is not used it must be
capped.

The drain pan connections are designed to ASTM Standard D 2466
Schedule 40. Use 3/4" PVC or steel threaded pipe. Since the drains are
not subject to any pressure it is not necessary to use Schedule 40 pipe
for drain lines.

It is recommended that all drain connections be sealed with teflon tape
or equivalent.

MAINTENANCE

Filters must be cleaned or replaced when they become dirty. Inspect at
least once per month. The frequency of cleaning depends upon the
hours of operation and the local atmospheric conditions. Clean filters
keep unit efficiency high.

COIL CLEANING

If the coil needs to be cleaned or replaced, it should be washed with
Calgon coilclean (mix one part Coilclean to seven parts water). Allow
solution to remain on coil for 30 minutes before rinsing with clean water.
Solution should not be permitted to come in contact with painted sur-
faces.

LUBRICATION

The bearings of the blower motor are permanently lubricated.

CONDENSATE DRAINS

During the cooling season check the condensate drain lines to be sure
that condensate is flowing from the primary drain but not from the sec-
ondary drain. If condensate ever flows from the secondary drain the unit
should be promptly shut off and the condensate pan and drains cleaned
to insure a free flowing primary drain.

Threaded drain connection should be hand-tightened, plus no
more than 1/16 turn.

Horizontal drain cutout in the center access panel should be
removed by using a utility knife. DO NOT TRY TO KNOCK OUT.

TROUBLESHOOTING GUIDE

PROBLEM

POSSIBLE CAUSE

Blower Runs all of the time

1. No heat units do not have 6-pin connector installed.
2. Limit open or not connected.
3. Blower OFF delay (approx. 1 min).
4. Thermostat fan switch in “ON” position.

Blown Fuse

1. Low voltage short to C or ground from R, Y, G, W, or O.

No 24V

1. 4-pin connector loose.
2. Loose wire from control to transformer (24V and 230V).
3. Blown fuse on control board.

No 2nd stage heat

1. Check 6-pin connector and connections to panel mount relays.
2. Verify that both W

1

 & W

2

 are connected at the terminal strip.

No Heat or Limited Heating

1. Check filter.
2. Closed registers.
3. Restricted airflow (supply registers or return registers)
4. Check blower motor operation.
5. If the safety limit opens 4 times, the control will not permit the heating element to operate for 1 hour.

Содержание F2FV060

Страница 1: ...s including but not limited to building electrical and mechanical codes TABLE OF CONTENTS SAFETY 1 SPECIFIC SAFETY RULES AND PRECAUTIONS 2 SAFETY REQUIREMENTS 2 GENERAL INFORMATION 2 INSPECTION 2 LIMI...

Страница 2: ...INFORMATION This Single Piece Air Handler provides the flexibility for installation in any upflow or horizontal application These versatile models may be used for cooling or heat pump operation with...

Страница 3: ...n to remove pan from position 4A if factory installed 3 Position horizontal pan as required in either A or B position locking it into the vertical drain pan as shown 4 Horizontal drain pans have 4 plu...

Страница 4: ...THE SIDES AND REAR OF UNIT SUPPORT BRACKET 060 COIL BAFFLE SHOWN IN RIGHT HORIZONTAL POSITION FIGURE 4 Dimensions Duct Sizes SHIPPING BRACKET REMOVE PRIOR TO INSTALLATION 2 SCREWS 10 3 8 J DRAIN CONNE...

Страница 5: ...size filter Standard 1 size permanent or throw away filter may be used or permanent washable filters are available using model num ber 1PF603BK only See Table 4 for filter size SUSPENSION KITS A suspe...

Страница 6: ...fitting hand tight and turn an additional 1 8 turn to seal NOTE This procedure should be done within 2 minutes to keep air and contaminates from entering the coil If the orifice cannot be replaced an...

Страница 7: ...y with local and national electrical code requirements Read and heed all unit caution labels NOTE It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump S...

Страница 8: ...d Remove for Heat Pump for heat pump operation See Figure 12 To Set Electric Heat CFM The blower speed required for the Electric Heat is different than cooling Refer to the label in the bag attached t...

Страница 9: ...240V F2FV060H06 F3FV060H06T 2HK 6500806B 0 5 1335 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0...

Страница 10: ...60 8 6 2HK06501525B 48 6 52 9 50 60 8 6 1 May be 0 or 1 No Breaker or Breaker 2 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 11 Electrical Data for...

Страница 11: ...HEAT 3 4 THERMOSTAT OUTDOOR UNIT DEFROST CONTROL GND SCREW TERMINAL NOT AVAILABLE ON ALL THERMOSTATS IMPORTANT NOTE HEAT PUMP JUMPER ON THE CFM SELECTION BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED...

Страница 12: ...nd the local atmospheric conditions Clean filters keep unit efficiency high COIL CLEANING If the coil needs to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean t...

Отзывы: