TABLE 9: 

Electrical Data - (for Single Source Power Supply) - Copper Wire 208/230-1-60

Model

Heater Model

1

Heater 

Amps 240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

2

Amps/Type

75

°

C Wire Size - AWG

208V

240V

208V

240V

208V

240V

F2FV060H06

F3FV060H06T

2HK*6500806B

31.3

43.8

47.8

45

50

8

8

2HK*6501006B

41.7

55.2

60.8

60

70

6

4

2HK16501506B

62.5

78.0

86.9

80

90

4

3

2HK16502006B

83.3

100.3

112.9

110

125

2

1

2HK16502506B

104.2

123.1

139.0

125

150

1

1/0

1. May be 0 or 1 (No Breaker or Breaker)
2. O.C.P. = Over-Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TABLE 10: 

Electrical Data - (for Single Source Power Supply) - Copper Wire 208/230-3-60

Model

Heater Model

1

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

75

°

C Wire Size - AWG

208V

240V

208V

240V

208V

240V

F2FV060H06

F3FV060H06T

2HK06501025B

48.6

52.9

50

60

8

6

2HK06501525B

48.6

52.9

50

60

8

6

1. May be 0 or 1 (No Breaker or Breaker)
2. O.C.P. = Over-Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

TABLE 11: 

Electrical Data - (for Multi-Source Power Supply) - Copper Wire 208/230-1-60

Model

Heater Model

Min. Circuit Ampacity

Max. O.C.P.

Amps/Type

75

°

C Wire Size - AWG

Circuit

Circuit

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/240V

208/240V

208/240V

208/240V

208/240V

208/240V

208/240V

208/240V

208/240V

F2FV060H06

F3FV060H06T

2HK16501506B

33.0/34.8

45.1/52.1

-

35/35

50/60

-

8/8

8/6

-

2HK16502006B

55.2/60.8

45.1/52.1

-

60/70

50/60

-

6/4

8/6

-

2HK16502506B

33.2/34.8

45.1/52.1

45.1/52.1

35/35

50/60

50/60

8/8

8/6

8/6

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse..

 FIGURE 14:  

Cooling Models with Electric Heat Wiring

THERMOSTAT

CFM SELECTION

BOARD

FIELD
INSTALLED
JUMPER

OUTDOOR

UNIT

DEHUMIDIFICATION
CONTROL CONNECTION

(”HUMIDISTAT” JUMPER ON
CFM SELECTION BOARD
MUST BE REMOVED

CONTROL BOARD

NOTE: THERMOSTAT TERMINAL “W” NOT USED FOR COOLING ONLY.

R

Y

G

W

R

Y

G

W2

W1

O

C

HUM

X

Y1

Y2

Содержание F2FV060

Страница 1: ...s including but not limited to building electrical and mechanical codes TABLE OF CONTENTS SAFETY 1 SPECIFIC SAFETY RULES AND PRECAUTIONS 2 SAFETY REQUIREMENTS 2 GENERAL INFORMATION 2 INSPECTION 2 LIMI...

Страница 2: ...INFORMATION This Single Piece Air Handler provides the flexibility for installation in any upflow or horizontal application These versatile models may be used for cooling or heat pump operation with...

Страница 3: ...n to remove pan from position 4A if factory installed 3 Position horizontal pan as required in either A or B position locking it into the vertical drain pan as shown 4 Horizontal drain pans have 4 plu...

Страница 4: ...THE SIDES AND REAR OF UNIT SUPPORT BRACKET 060 COIL BAFFLE SHOWN IN RIGHT HORIZONTAL POSITION FIGURE 4 Dimensions Duct Sizes SHIPPING BRACKET REMOVE PRIOR TO INSTALLATION 2 SCREWS 10 3 8 J DRAIN CONNE...

Страница 5: ...size filter Standard 1 size permanent or throw away filter may be used or permanent washable filters are available using model num ber 1PF603BK only See Table 4 for filter size SUSPENSION KITS A suspe...

Страница 6: ...fitting hand tight and turn an additional 1 8 turn to seal NOTE This procedure should be done within 2 minutes to keep air and contaminates from entering the coil If the orifice cannot be replaced an...

Страница 7: ...y with local and national electrical code requirements Read and heed all unit caution labels NOTE It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump S...

Страница 8: ...d Remove for Heat Pump for heat pump operation See Figure 12 To Set Electric Heat CFM The blower speed required for the Electric Heat is different than cooling Refer to the label in the bag attached t...

Страница 9: ...240V F2FV060H06 F3FV060H06T 2HK 6500806B 0 5 1335 5 6 7 5 19 1 25 6 3 8 5 0 5 6 7 5 5 6 7 5 2HK 6501006B 7 5 10 0 25 6 34 1 3 8 5 0 7 5 10 0 7 5 10 0 2HK16501506B 11 3 15 0 38 6 51 2 3 8 5 0 7 5 10 0...

Страница 10: ...60 8 6 2HK06501525B 48 6 52 9 50 60 8 6 1 May be 0 or 1 No Breaker or Breaker 2 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 11 Electrical Data for...

Страница 11: ...HEAT 3 4 THERMOSTAT OUTDOOR UNIT DEFROST CONTROL GND SCREW TERMINAL NOT AVAILABLE ON ALL THERMOSTATS IMPORTANT NOTE HEAT PUMP JUMPER ON THE CFM SELECTION BOARD MUST BE REMOVED WHEN AIR HANDLER IS USED...

Страница 12: ...nd the local atmospheric conditions Clean filters keep unit efficiency high COIL CLEANING If the coil needs to be cleaned or replaced it should be washed with Calgon coilclean mix one part Coilclean t...

Отзывы: