background image

271043-UIM-B-0707

22

Unitary Products Group

IMPORTANT: 

The inlet gas pressure operating range table specifies

what the minimum and maximum gas line pressures must be for the fur-
nace to operate safely. 

The gas line pressure 

MUST BE

7” W.C. (1.74 kPA) for Natural Gas

11” W.C. (2.74 kPA) for Propane (LP) Gas

in order to obtain the BTU input specified on the rating plate and/or the
nominal manifold pressure specified in these instructions and on the
rating plate.

ADJUSTMENT OF MANIFOLD GAS PRESSURE

Manifold gas pressure may be measured by two different procedures. It
may be measured with the burner box cover in place or it may be mea-
sured with the burner box cover removed. Follow the appropriate sec-
tion in the instructions below. Refer to Figure 21 for a drawing of the
locations of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line 
before the gas valve. Find the pressure ports on the gas 
valve marked OUT P and IN P.

1.

The manifold pressure must be taken at the port marked OUT P. 

2.

The inlet gas line pressure must be taken at the port marked IN P.

3.

Using a 3/32” (2.4 mm) Allen wrench, loosen the setscrew by turn-
ing it 1 turn counter clockwise. DO NOT REMOVE THE SET
SCREW FROM THE PRESSURE PORT.

Read the inlet gas pressure using either of the two 
methods below.

Reading the gas pressure with the burner box cover in place:

A.

Disconnect the pressure reference hose from the right side of
the burner box. Using a tee fitting and a short piece of hose,
connect the negative side of the manometer to the burner
box as described below.

B.

Remove one end the 5/16” (7.94 mm) ID flexible tubing over
the pressure port on the burner box. 

C.

Insert the end of the 5/16” (7.94 mm) tubing, that has the 1/8”
(3.175 mm) adapter at the end of the tube, in to the 1/8”
(3.175 mm) tee.

D.

Connect the 1/8” (3.175 mm) tee to the burner box adapter
and to the negative side of a U-tube manometer or digital
pressure measuring equipment with 2 – 1/8” (3.175 mm)
tubes.

E.

Use the 5/16” (7.94 mm x 1/8” (3.175 mm) reducing coupling
and a 4” (101.6 mm) piece of 1/8” (3.175 mm) tubing to con-
nect the positive side of the manometer to the gas valve pres-
sure reference port. Refer to Figure 22 for connection details.

Reading the gas pressure with the burner box cover removed -

Remove the screws securing the burner box front cover plate. Remove
the cover. The gasket and may stick in place. Connect the positive side
of the manometer to the gas valve as described in E above. There will
be no second connection to the manometer, as it will reference atmo-
spheric pressure. Refer to Figure 22 for connection details.

This gas valve has separate regulator adjustment screws for high fire
and low fire, as shown in Figure 21. The procedure below is used to
adjust either the high fire manifold pressure or the low fire manifold
pressure.

IMPORTANT: 

The cap for the pressure regulator must be removed

entirely to gain access to the adjustment screw. Loosening or tightening
the cap does not adjust the flow of gas.

1.

Refer to Figure 21 for location of pressure regulator adjustment
cap and adjustment screws on main gas valve.

2.

Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.

3.

Adjust manifold pressure by adjusting gas valve regulator screw
for the appropriate gas per the following:

IMPORTANT: 

If gas valve regulator is turned in (clockwise), manifold

pressure is increased. If screw is turned out (counterclockwise), mani-
fold pressure will decrease.

4.

After the manifold pressure has been adjusted, re-calculate the
furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to “CALCULATING THE FURNACE
INPUT (NATURAL GAS)”.

5.

Once the correct BTU (kW) input has been established, turn the
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing and fittings from the gas valve pressure
tap and the pressure reference hose from the right side of the
burner box and tighten the pressure tap plug using the 3/32”
(2.4 mm) Allen wrench. Replace the burner box front cover (if it
was removed) and place the pressure reference hose back on the
gas valve.

6.

Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved gas detector, a non-corrosive
leak detection fluid, or other leak detection methods.

Be sure to relight any gas appliances that were turned off at the
start of this input check.

TABLE 15: 

Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas

Propane (LP)

Minimum

4.5” W.C. (1.12 kPa)

8.0” W.C. (1.99 kPa)

Maximum

10.5” W.C. (2.61 kPa)

13.0” (3.24 kPa) W.C.

TABLE 16: 

Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas (High Fire)

3.5" w.c. (0.87 kPa)

Natural Gas (Low Fire)

1.6" w.c. (0.40 kPa)

Propane (LP) Gas (High Fire)

10.0" w.c. (2.488 kPa)

Propane (LP) Gas (Low Fire)

4.0" w.c. (0.99 kPa)

 FIGURE 21:  

Gas Valve

The manifold pressure must be checked with the screw-off cap for
the gas valve pressure regulator in place. If not, the manifold pres-
sure setting could result in an over-fire condition. A high manifold
pressure will cause an over-fire condition, which could cause pre-
mature heat exchanger failure. If the manifold pressure is too low,
sooting and eventual clogging of the heat exchanger could occur.
Be sure that gas valve regulator cap is in place and burner box to
gas valve pressure reference hose is connected.

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON OFF
SWITCH

LOW STAGE REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT
PORT

HIGH STAGE REGULATOR
ADJUSTMENT

Содержание AHC9V UP

Страница 1: ...electrical and mechanical codes LIST OF SECTIONS SAFETY 1 DUCTWORK 4 FILTERS 6 GAS PIPING 7 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 12 CONDENSATE PIPING 18 SAFETY CONTROLS 19 START UP AND AD...

Страница 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Страница 3: ...or and the furnace must be located or protected to avoid physical damage by vehicles The furnace area must not be used as a broom closet or for any other storage purposes as a fire hazard may be creat...

Страница 4: ...NOTE When attaching duct flange do not shoot the screw down into the casing Use the formed flange intended for duct flange attachment The duct system is a very important part of the installation If th...

Страница 5: ...e presence of leaks in the heat exchanger This access cover shall be attached in such a manner as to prevent leaks TABLE 2 Minimum Duct Sizing For Proper Airflow Input Cabinet Airflow Return1 Rectangu...

Страница 6: ...provided with that accessory for proper hole cut size SECTION III FILTERS FILTER INSTALLATION All applications require the use of a filter Filters must be installed external to the furnace cabinet DO...

Страница 7: ...igure 1 dimensions The inlet to the gas valve lines up directly with the opening in the left side of the furnace casing To line up with the opening in the right side of the casing two street ells shou...

Страница 8: ...5 1 4 1 3 39 1 0 37 0 34 0 31 1100 1 3 1 2 1 1 41 0 0 34 0 31 0 28 2500 LP 4 1 3 8 3 5 93 2 LP 1 03 0 95 0 87 PROPANE AND HIGH ALTITUDE CONVERSION KITS It is very important to choose the correct kit...

Страница 9: ...o the terminal board on the ignition module as shown in Figures 5 and 6 Electronic thermostats may require the common wire to be connected as shown in Figures 5 and 6 Apply strain relief to thermostat...

Страница 10: ...ight O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage H...

Страница 11: ...W2 Delay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y...

Страница 12: ...length listed in Table 8 is for the vent pip ing and the air intake piping separately For example if the table allows 65 equivalent feet for a particular model then the vent can have 65 equivalent fe...

Страница 13: ...piping apply cement primer and the cement per the manufactures instructions Primer and cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent air...

Страница 14: ...ns 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Страница 15: ...systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 11 or 12 VENTING MULTIPLE UNITS Multiple units can be installed in a space or...

Страница 16: ...vent Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from entering the terminal Also the terminal assembly should be located as far as p...

Страница 17: ...LE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIONAL INLET a OUTLET AIR a VENTILATED CRAWL SPACE GAS WATER HEATER VENTILATED ATTIC TOP ABOVE INSULATION GAS VENT GABLE VENT SOFFI...

Страница 18: ...Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this instruction or in Section 5 3 Air...

Страница 19: ...e controls are mounted on the burner box assembly If the temper ature in the burner box exceeds its set point the ignition control and the gas valve are de energized The operation of this control indi...

Страница 20: ...ll start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Aft...

Страница 21: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Страница 22: ...shown in Figure 21 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entirely...

Страница 23: ...blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as shown in Figure 23 WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED FIG...

Страница 24: ...een the R and W terminals The indoor fan motor is energized through the W1 heat terminal and runs on the speed selected on the HEAT tap of the control board Humidistat When a humidistat is installed i...

Страница 25: ...T CODE STORAGE AND RETRIEVAL The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily This memory will...

Страница 26: ...A C 52 1 35 4 53 2 35 4 1560 1010 1620 1030 C B 44 2 28 6 45 9 29 2 1470 940 1500 960 B C 41 6 26 6 42 5 27 2 1370 890 1410 880 D B 38 8 25 2 39 9 24 9 1460 930 1490 920 C A 41 3 26 3 42 2 26 1 1250 7...

Страница 27: ...in in2 cm2 In W C kPA In W C kPA In W C kPA 0 750 0 21 4 230 1484 0 01 0 00249 0 01 0 00249 0 15 0 03736 751 1000 21 25 28 32 330 2129 0 05 0 01245 0 05 0 01245 0 20 0 04982 1001 1250 28 33 35 40 330...

Страница 28: ...Printed in U S A 271043 UIM B 0707 Copyright by York International Corp 2007 All rights reserved Supersedes 271043 UIM A 0407 Unitary 5005 Norman Products York OK Group Drive 73069 SECTION X WIRING D...

Отзывы: