background image

271043-UIM-B-0707

10

Unitary Products Group

For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the
Product Catalog Section.

 FIGURE 5:  

Thermostat Chart - AC

AC10

2 Stage Scroll A/C w/ Variable Speed Furnace - PV8/9; (F,L)*8/9V, (G,L)*8/9V, XYG8V-*, XYF8V-*, XYG9V-*, XYF9V-*

*DN22U00124

THERMOSTAT

Y

First Stage Cool

R

24-Volt Hot (Heat XFMR)

C

24-Volt Common

THERMOSTAT

Connection of the "C" 

Termainal, 24-Volt 

Common, is optional 

when used with batteries

*PP32U70124

Y

First Stage Cool

Y2

Second Stage Cool

R

24-Volt Hot (Heat XFMR)

C

24-Volt Common

W/W1

Single/First Stage Heat

W2

Second Stage Heat

G

Fan

Thermostat Installer 

Setup Number 0170 - 

System Type - must be 

set to 8 - 2 Heat/2 Cool 

Multistage Conventional

G

Fan

G

Fan

E/W1

First Stage Heat

W2

Second Stage Heat

*PP32U72124

RC

24-Volt Hot (Cool XFMR)

E/W1

First Stage Heat

L

Malfunction Light

W2

Second Stage Heat

G

Fan

E/W1

First Stage Heat

Y2

Second Stage Cool

C

24-Volt Common

Y1

First Stage Cool

*DP22U70124

HM

Humidistat

DHM

Dehumidistat

VARIABLE SPEED

FURNACE CONTROL

R

24-Volt Hot

CFM CONTROL

W2

Second Stage Heat

Y1

First Stage Cool

*PP32U71124

THERMOSTAT

24V HUMIDIFIER

(Optional)

(X/L)

Malfunction Light

(O)

Reversing Valve– Energized in Cool

TWO STAGE

AIR CONDITIONING

Comfort Alert

Interface

HUM

Dehumidification - Open on Humidity Rise

C

24-Volt Common

C

24-Volt Common

R

24-Volt Hot

W2

Second Stage Heat

G

Fan

Y2

Second Stage Cool

E/W1

First Stage Heat

RC

24-Volt Hot (Cool XFMR)

Y1

First Stage Cool

R

24-Volt Hot

Y/Y2

Single/Second Stage Cool

Y2

Second Stage Cool

Y

First Stage Cool

Y2

Second Stage Cool

W2

Second Stage Heat

G

Fan

R

24-Volt Hot

W

First Stage Heat

R

24-Volt Hot

*DN22C00124

THERMOSTAT

Y2

Second Stage Cool

Y1

First Stage Cool

C

24-Volt Common

C

24-Volt Common

THERMOSTAT

Thermostat Installer Setup 

Number 15 - Compressor 

Protection - must be set to 5

( ) CONVENIENCE TERMINAL

NO FUNCTION IN THIS APPLICATION.

E2/P Switch must be in 

the E2 position and the 

Humidistat Jumper on 

CFM Control must be 

in the 'YES' position 

for Dehumidification

Step 1 of Thermostat User 

Configuration Menu 

must be set to MS 2

Connection of the "C" 

Termainal, 24-Volt Common, 

is optional 

when used with batteries

Step 16 of Thermostat 

User Configuration Menu 

must be set to ON to use 

Comfort Alert Features

Thermostat Installer Setup 

Number 1 - System Type - 

must be set to 6 - 2 

Heat/2 Cool Conventional

Connection of the "C" Termainal, 

24-Volt

Common, is optional 

when used with batteries

Connection of the "C" 

Termainal, 24-Volt 

Common, is optional 

when used with batteries

Step 1 of Thermostat User 

Configuration Menu must be 

set to MLTI STG

Содержание AHC9V UP

Страница 1: ...electrical and mechanical codes LIST OF SECTIONS SAFETY 1 DUCTWORK 4 FILTERS 6 GAS PIPING 7 ELECTRICAL POWER 8 COMBUSTION AIR AND VENT SYSTEM 12 CONDENSATE PIPING 18 SAFETY CONTROLS 19 START UP AND AD...

Страница 2: ...ible materials as listed under Clearances to Combustibles in Table 1 Provide clearances for servicing ensuring that service access is allowed for both the burners and blower These models ARE NOT CSA l...

Страница 3: ...or and the furnace must be located or protected to avoid physical damage by vehicles The furnace area must not be used as a broom closet or for any other storage purposes as a fire hazard may be creat...

Страница 4: ...NOTE When attaching duct flange do not shoot the screw down into the casing Use the formed flange intended for duct flange attachment The duct system is a very important part of the installation If th...

Страница 5: ...e presence of leaks in the heat exchanger This access cover shall be attached in such a manner as to prevent leaks TABLE 2 Minimum Duct Sizing For Proper Airflow Input Cabinet Airflow Return1 Rectangu...

Страница 6: ...provided with that accessory for proper hole cut size SECTION III FILTERS FILTER INSTALLATION All applications require the use of a filter Filters must be installed external to the furnace cabinet DO...

Страница 7: ...igure 1 dimensions The inlet to the gas valve lines up directly with the opening in the left side of the furnace casing To line up with the opening in the right side of the casing two street ells shou...

Страница 8: ...5 1 4 1 3 39 1 0 37 0 34 0 31 1100 1 3 1 2 1 1 41 0 0 34 0 31 0 28 2500 LP 4 1 3 8 3 5 93 2 LP 1 03 0 95 0 87 PROPANE AND HIGH ALTITUDE CONVERSION KITS It is very important to choose the correct kit...

Страница 9: ...o the terminal board on the ignition module as shown in Figures 5 and 6 Electronic thermostats may require the common wire to be connected as shown in Figures 5 and 6 Apply strain relief to thermostat...

Страница 10: ...ight O Reversing Valve Energized in Cool TWO STAGE AIR CONDITIONING Comfort Alert Interface HUM Dehumidification Open on Humidity Rise C 24 Volt Common C 24 Volt Common R 24 Volt Hot W2 Second Stage H...

Страница 11: ...W2 Delay on furnace to OFF HM Humidistat BSG Bonnet Sensor Bonnet Sensor Optional BS Bonnet Sensor AUX Auxiliary Heat E W1 First Stage Auxiliary Heat E W1 First Stage Auxiliary Heat W Auxiliary Heat Y...

Страница 12: ...length listed in Table 8 is for the vent pip ing and the air intake piping separately For example if the table allows 65 equivalent feet for a particular model then the vent can have 65 equivalent fe...

Страница 13: ...piping apply cement primer and the cement per the manufactures instructions Primer and cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent air...

Страница 14: ...ns 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Страница 15: ...systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone Refer to Figures 11 or 12 VENTING MULTIPLE UNITS Multiple units can be installed in a space or...

Страница 16: ...vent Care should be taken to locate side vented systems where trees or shrubs will not block or restrict supply air from entering the terminal Also the terminal assembly should be located as far as p...

Страница 17: ...LE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIONAL INLET a OUTLET AIR a VENTILATED CRAWL SPACE GAS WATER HEATER VENTILATED ATTIC TOP ABOVE INSULATION GAS VENT GABLE VENT SOFFI...

Страница 18: ...Air The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in AIR SOURCE FROM OUTDOORS in this instruction or in Section 5 3 Air...

Страница 19: ...e controls are mounted on the burner box assembly If the temper ature in the burner box exceeds its set point the ignition control and the gas valve are de energized The operation of this control indi...

Страница 20: ...ll start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Aft...

Страница 21: ...3600 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the...

Страница 22: ...shown in Figure 21 The procedure below is used to adjust either the high fire manifold pressure or the low fire manifold pressure IMPORTANT The cap for the pressure regulator must be removed entirely...

Страница 23: ...blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins as shown in Figure 23 WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED FIG...

Страница 24: ...een the R and W terminals The indoor fan motor is energized through the W1 heat terminal and runs on the speed selected on the HEAT tap of the control board Humidistat When a humidistat is installed i...

Страница 25: ...T CODE STORAGE AND RETRIEVAL The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily This memory will...

Страница 26: ...A C 52 1 35 4 53 2 35 4 1560 1010 1620 1030 C B 44 2 28 6 45 9 29 2 1470 940 1500 960 B C 41 6 26 6 42 5 27 2 1370 890 1410 880 D B 38 8 25 2 39 9 24 9 1460 930 1490 920 C A 41 3 26 3 42 2 26 1 1250 7...

Страница 27: ...in in2 cm2 In W C kPA In W C kPA In W C kPA 0 750 0 21 4 230 1484 0 01 0 00249 0 01 0 00249 0 15 0 03736 751 1000 21 25 28 32 330 2129 0 05 0 01245 0 05 0 01245 0 20 0 04982 1001 1250 28 33 35 40 330...

Страница 28: ...Printed in U S A 271043 UIM B 0707 Copyright by York International Corp 2007 All rights reserved Supersedes 271043 UIM A 0407 Unitary 5005 Norman Products York OK Group Drive 73069 SECTION X WIRING D...

Отзывы: