18
Note 1)
1
Neither indoor unit nor outdoor unit runs.
Check the following points first. (There are following case in normal operation)
a. Is the timer mode set the "timer ON".
b. Is the timer mode set the "timer-OFF" and the time had passed?
2
Neither outdoor fan nor compressor runs while indoor fan runs.
Check following points first. (There are following cases in normal operation)
a. Is the temperature set point suitable?
b. Has the 3 minutes time guard for compressor operated?
• Error Code •
1
When the compressor do not run.
i) Check the voltage between
and
of terminal block.
(Indoor Unit, Outdoor Unit)
ii) Check connecting wire of indoor unit and outdoor unit.
iii) Check relay RL1 on power P.C.B
2
Check fixing of indoor coil thermistor.
3
Check the GAS LEAKAGE of the pipe.
N
L
Self-Diagnostic Function
Содержание DPA-246LG
Страница 2: ...FLOOR STANDING TYPE Air Conditioner Model DPA 246LR DPA 246LG ...
Страница 16: ...14 2 DPA 246LR LGINDOORUNITOUTLINEANDSECTION ...
Страница 19: ...17 1 INDOORUNIT 4 WIRING DIAGRAM ...
Страница 20: ...18 2 OUTDOORUNIT ...
Страница 22: ...20 1 DPA 246LR LGINDOORUNIT 5 EXPLODED DIAGRAM ...
Страница 25: ...23 2 DPA 246LR LG OUTDOOR UNIT ...
Страница 31: ...29 8 PCB DRIVING DESCRIPTION 1 DPA 246L R G INDOOR UNIT MAIN PCB CIRCUIT ...
Страница 32: ...30 2 DPA 246L R G INDOOR UNIT FRONT PCB CIRCUIT ...
Страница 33: ... 3 DPA 246L R G OUTDOOR UNIT PCB CIRCUIT ...
Страница 43: ...SPLIT TYPE Air Conditioner Model DSA 0910LR M DSA 0910LG M ...
Страница 46: ...3 2 OUTLINE AND DIMENSIONS 1 INDOOR UNIT DSA 0910LR G M ...
Страница 56: ...13 4 WIRING DIAGRAM Indoor Unit DSA 0910LR G M ...
Страница 59: ...16 6 CONTROL BLOCK DIAGRAM DSA 0910LR G M ...
Страница 66: ...23 PCBDRIVINGDESCRIPTION ...
Страница 67: ...24 1 PCB CIRCUIT DIAGRAM DSA0910LR G M ...
Страница 76: ...33 3 EXPLODED DIAGRAM Indoor Unit DSA 0910LR G R ...