Page 28
P O W E R I N G T E C H N O L O G Y
Manual No. aspiro2u-3
aspiro2u_m23-man-rev3-0516.indd
NOTE
The temperature compensation factor can be set only for temperature sensor 1.
Ambient Temperature
Temperature sensor 2 allows a second temperature reading, most commonly the ambient
temperature around the system. Place the sensor as required.
The temperature is displayed in the External Measurements menu in the ACC controller or
in PowCom™ software.
NOTE
Temperature sensor 2 can be activated only in the systems with the ACC
controller installed.
4.12 Rectifier Installation
Rectifier module should be installed starting from the bottom left position in the rectifier
shelf.
Rectifier Installation:
1.
Place the rectifier module in the mounting slot with handle facing out.
2.
Slide the rectifier module into the slot until it contacts the interface connection at the rear
of the shelf.
3.
a) For XR04.48/XR08.48 fully insert the rectifier by pushing it into the shelf, fasten the
rectifier in the slot and tighten the screw with a screw driver.
b) For XPGe12.48 fully insert the rectifier by pushing the handle towards the shelf. The
rectifier handle will rise up and lock the rectifier into position.
NOTE
Ensure that the rectifier handle is in the OPEN position (forms 35-40° angle with
rectifier body) before inserting the module into the slot.
4.
Repeat steps 1 to 3 if more rectifiers are to be installed.
XR04.48 & XR08.48
XPGe12.48
Figure 4-14 Rectifier Installation