Manual No. aspiro2u-3

aspiro2u_m23-man-rev3-0516.indd

RECTIFIER MODEL

XPGe12.48

XR08.48

XR04.48

Efficiency

95% typical @ I

out

 nom

90% typical @ I

out

 nom

88% typical @ I

out

 nom

Input Current (max)

<7.3A

<10.5A

<5.3A

Output Current (max) 

53.5V float

22.4A

15.0A

7.5A

Output Power

1200W @ >180VAC

750W @ 90-180VAC

800W

400W

Operating Temperature 

(without derating)

55°C

65°C

65°C

Input Voltage

(Nominal 100-240VAC)

90-300VAC

85-300VAC

Output Voltage

46-57VDC

Load sharing

< 5% of nominal current

Dimensions (WxHxD)

40.6 (1.6”) x 101.62(4”) x 228.5(9”) mm

Weight

1.1 kg

Cooling

Fan-cooled, speed and alarm controlled, air flow direction rear to front

Protection

Short circuit proof, automatic current limiting, selective shutdown of modules 

at excessive output voltage.

Alarms

High output voltage/ shutdown, Low voltage/ module failure

LED Indication

Green: 

Power ON

Yellow: 

Current limit/ thermal protection

 

Fan failure / Over temperature

 

Pre-warning / thermal protection

 

Communication Failure (flashing)

Red: 

Module failure / high output voltage shutdown

Audible noise

<55dBA according to ISO7779

MECHANICAL

Dimensions (WxHxD)

19” (483mm) x 3.5” (88mm) x 11.7” (297mm)

Weight of the system

(fully equipped)

32lbs (14.5kg)

Mounting Options

19”/ ETSI / Mid-mount

Cable Entry

Rear Access (top cover has to be removed to make connections)

STANDARD COMPLIANCE / ENVIRONMENTAL

EMC and Immunity

EN55022:2006 +A1:2007, EN55024:1998 +A1:2001 +A2:2003,

EN61000-3-2:2006+A1:2009 +A2:20009, EN61000-3-3:2008

ETSI EN300386 V1.4.1

Safety

EN60950-1: 2006 + A11:2009

Environment

Storage : ETS300 019-2-1, Transport: ETS300 019-2-2, Operation 

ETS300 019-2-3, Damp Heat: IEC60068-2-78

Operating Temperature

-40°C to +65°C (derated above 55°C)

Storage Temperature

-40°C to +85°C

Содержание XPGe12.48

Страница 1: ...umber ASPIRO2U 3 2016 UNIPOWER LLC All Rights Reserved aspiro2u_m23 man rev3 0516 indd UNIPOWER LLC 3900 Coral Ridge Drive Coral Springs Florida 33065 USA sales unipowerco com North America 1 954 905...

Страница 2: ...manual are the property of their respective trademark holders These trademark holders are not affiliated with UNIPOWER LLC or our products They do not sponsor or endorse our products LIMITATIONS AND...

Страница 3: ...13 3 1 1 System Markings 13 3 1 2 Safety Recommendations 13 3 1 3 Installation Warning 14 3 1 4 Restricted Access Area Warnings 14 3 1 5 System Enclosure 14 3 1 6 Operating Temperature Warnings 14 3...

Страница 4: ...0 5 3 Preparation 30 5 4 Commissioning procedure 31 5 5 Test of output voltage 32 5 5 1 Float charge U1 32 5 5 2 Adjustment of Float Charge U1 32 5 5 3 Boost charging U2 if applicable 32 5 6 Battery s...

Страница 5: ...nections 25 Figure 4 11 2 block Symmetry Measurement for illustration only 26 Figure 4 12 4 Block Symmetry Measurement for illustration only 27 Figure 4 13 Temperature Sensor Connection 27 Figure 4 14...

Страница 6: ...llation and installing the power system This manual assumes that the technician has an understanding of power systems in general and understands safety procedures for working around AC and DC voltage...

Страница 7: ...Distribution Drawer 3 x load D33 Distribution Drawer 2 x load B33 Distribution Drawer 2 x battery 1 4 Feedback Support For technical support or feedback please visit http www unipowerco com contact a...

Страница 8: ...elf protection and three LEDs for immediate rectifier status indication The Power system is highly configurable with installed capacity from 400W up to 4800W together with DC distribution system contr...

Страница 9: ...ers 8 x NADER NDB3 Series Ratings 1A 4A 5A 7 5A 10A 15A 20A 25A 30A MONITORING AND CONTROL Controller PCC or ACC Extended Local Interface 4 x 20 LCD 4 key menu USB ACC only and RS232 Remote Interface...

Страница 10: ...ive output voltage Alarms High output voltage shutdown Low voltage module failure LED Indication Green Power ON Yellow Current limit thermal protection Fan failure Over temperature Pre warning thermal...

Страница 11: ...re supervised by measuring the voltage drop across each breaker In case of load breakers any MCBs that are not connected to a load will not cause breaker alarm even if they are left open A battery fus...

Страница 12: ...to the system controller and companion rectifiers This guarantees tightly controlled load sharing among rectifiers and provides status and identification information to the controller The rectifiers...

Страница 13: ...fety label is located inside the system 3 1 2 Safety Recommendations Any device that uses electricity requires proper guidelines to ensure safety The Power System should only be installed or serviced...

Страница 14: ...d to reduce the chance of system overheating 3 1 4 Restricted Access Area Warnings The Power System is designed for installation in locations with restricted access often secured by a locking mechanis...

Страница 15: ...g ANSI CEC NEC etc When makingAC connections allAC power and DC load distribution breakers should be in the OFF position All circuit breakers should meet the original design specifications of the syst...

Страница 16: ...is equipment may use Lead Acid Batteries When handling batteries follow the instructions included with the battery set as the fluids contained within these batteries are known to be a health hazard Th...

Страница 17: ...discharge 3 2 2 Disposal CAUTION The product should not be disposed with other wastes at the end of its working life so as to prevent possible harm to the environment or human health from uncontrolled...

Страница 18: ...an rev3 0516 indd 3 2 5 Breakers CAUTION Breakers should always be replaced with the same type and rating in order to avoid damage to system components 3 2 6 Hot Surfaces CAUTION Areas of the Power Sy...

Страница 19: ...cross head sizes 1 2 and 3 insulated Torque spanner for battery connection insulated WARNING Useonlysingle ended fullyinsulatedtools Shaftsofforexamplescrewdrivers should be insulated CAUTION Install...

Страница 20: ...ack measurement If necessary fix the mounting bracket in a different position see Figure 4 1 The default position of mounting brackets is 19 rack width front mount FIXED BRACKETS SLIDE BRACKETS 2 7 68...

Страница 21: ...et with four M6 x 12mm 2 on each side of the subrack Tighten the screws to 6Nm Figure 4 3 Figure 4 3 System Bracket Fixing 4 4 Cable Entry If the top distribution cover is installed it should be remov...

Страница 22: ...s first WARNING High leakage current Ensure earth is connected before connecting mains supply CAUTION Depending on deployment region with regards to lightning strikes and heavy inductive energy it is...

Страница 23: ...230VAC 2x230VAC 6 6 5 5 4 4 3 3 2 2 1 1 1 1 7 7 6 5 4 3 2 1 1 7 US Install Reference Figure 4 7 AC Connection Options Recommended AC mains breaker 400VAC 3 phase UL listed triple pole 20A C characteri...

Страница 24: ...o the opening on top of the terminal and tighten the screw to 2 5Nm See figure 4 8 Load 0V Load 48V Figure 4 8 DC Load Connection 4 8 Battery Connection The battery cables are not delivered with the s...

Страница 25: ...ailable Each alarm contact represents different alarm condition dependent on system configuration The alarm connections are located on the top right side of the subrack on the Alarm Interface Use suit...

Страница 26: ...Insert the green plug back into the Alarm Interface board 4 10 Symmetry Connection NOTE Symmetry cables are pre connected to the system 1 Attach the interblock connection plates between the batteries...

Страница 27: ...nsor cables If not use a three pin plug and connect according to the Appendix A Installation Details Battery Temperature Temperature sensor 1 measures the temperature of the battery bank while the con...

Страница 28: ...e bottom left position in the rectifier shelf Rectifier Installation 1 Place the rectifier module in the mounting slot with handle facing out 2 Slide the rectifier module into the slot until it contac...

Страница 29: ...R ALARM CONNECTOR Load 0V Load 48V DC Parallel Connection Busbar Figure 4 15 External PDU Connection 48VDC F1 Fn F2 External PDU Fuse Alarm Board Load Breakers 0VDC Fuse Alarm Figure 4 16 DC Parallel...

Страница 30: ...f there are any difficulties in increasing the voltage to alarm level the alarm level can be adjusted to a lower level 5 2 Tools and Test Equipment 5 2 1 Tools List The essential commissioning tools a...

Страница 31: ...nection of the blue and black battery cables to the batteries 6 Turn on the AC mains voltage 7 Measure the AC voltage on the AC terminal block between phases and neutral The correct value is approxima...

Страница 32: ...of Float Charge U1 Unless otherwise ordered the default output voltage is factory pre set to 53 5V The total voltage has to be in accordance to the number of battery cells Please verify number of cel...

Страница 33: ...ng to make sure that it is in accordance with the battery manufacturer s recommendations For systems with temp probe cable supplied Temperaturecompensationisfactorypre set Checkthatthetemp probeisacti...

Страница 34: ...phase to N when 400V mains input is used L1 N V AC L2 N V AC L3 N V AC 4 Mount the rest of the rectifiers 5 After connection of battery verify right polarity by measuring the voltage drop across the...

Страница 35: ...nal Screw M5 4 5 40 Table 6 1 Connection Torque Setting Check 6 2 Troubleshooting This troubleshooting chapter helps to determine the cause of the problem and suggests possible repair solutions If the...

Страница 36: ...ting Verify AC Input connection Verify AC Input voltage AC High Voltage AC voltage rises above the set limit Verify the High AC voltage limit Verify the AC Input voltage Module Failure Faulty module A...

Страница 37: ...tall the module and wait for 5 minutes Verify that the communication cable is properly connected and it is not damaged Replace if necessary If the board address does not communicate check if it is ins...

Страница 38: ...system Check the ambient temperature it should not be lower than recommended battery temperature high Battery Temperature Battery temperature exceeded the set limit Check the cooling or ventilation Ve...

Страница 39: ...d If none of the above solves the problem please contact customer support To phone us please visit http www unipowerco com contact and select Customer Support Repairs and then Customer Service where y...

Страница 40: ...rner of the controller front panel using a flat screwdriver see Figure 7 1 Figure 7 1 Unlocking the Controller 2 Pull the controller out of the shelf as shown in Figure 7 2 Figure 7 2 Removing the Con...

Страница 41: ...er from the slot Figure 7 3 2 3 Replace the module and fasten the screw Release spring Handle 1 2 2 Figure 7 3 Replacing an XR04 48 or XR08 48 Rectifier 7 2 2 XPGe12 48 Replacement 1 Insert a flat scr...

Страница 42: ...Make sure the system is switched OFF The power rack is designed front accessible for easy maintenance Battery and load breakers can be replaced without removing the power rack from the cabinet This se...

Страница 43: ...O G Y Manual No aspiro2u 3 aspiro2u_m23 man rev3 0516 indd Figure 7 6 Removing the top cover 2 Pull out the faulty breakers Figure 7 7 Figure 7 7 Pulling out a faulty breaker 3 Install the correct br...

Страница 44: ...off AC input power 2 Remove the top cover 3 Pull out the failed surge protection module 4 Insert a new surge protection module into the corresponding position 5 Reinstall the top cover 6 Switch on AC...

Страница 45: ...aspiro2u 3 aspiro2u_m23 man rev3 0516 indd Appendix A Drawings Front View Layout Description 10 10 10 10 10 10 10 10 F1 F2 F3 F4 F5 F6 F7 F8 FB2 FB1 XPGe12 48 XPGe12 48 XPGe12 48 XPGe12 48 RECTIFIERS...

Страница 46: ...ys Voltage Out 1 Sys Voltage Out Digital Output 2 Digital Output 1 12V 24V 36V Battery type 4 blocks 6 5 4 XC2 3 2 1 Battery symmetry 6 XC2 Battery symmetry 1 Battery symmetry 2 Battery symmetry 3 Bat...

Страница 47: ...t 4 XPGe12 48 XR08 48 XR04 48 X1 27 Rect 3 XPGe12 48 XR08 48 XR04 48 X1 27 Rectifier backplane Top J1 27 J5 27 0V 48V 8 RS485 Com J12 J4 J3 J2 J6 J7 J8 PE N L PE N L 8 J11 B2 B1 Rect 2 XPGe12 48 XR08...

Страница 48: ...anual No aspiro2u 3 aspiro2u_m23 man rev3 0516 indd Detailed Dimensions Fixed Bracket Option 3 5 88 3 0 76 2 2 95 75 18 3 465 19 0 482 6 20 3 515 21 1 535 17 37 441 2 12 69 322 2 11 63 295 4 0 06 1 6...

Страница 49: ...o2u 3 aspiro2u_m23 man rev3 0516 indd Detailed Dimensions Slide Bracket Option 3 5 88 3 0 76 2 2 95 75 1 25 31 7 18 3 465 19 0 482 6 20 3 515 21 1 535 17 65 448 4 12 69 322 2 11 63 295 4 0 06 1 6 0 98...

Отзывы: