NOTE
When mounting the system to an open frame, the brackets should be moved to the
middle position.
To mount the subrack into a cabinet, follow the steps below:
1. Determine the installation position according to the subrack measurement. If necessary,
fix the mounting bracket in a different position, see Figure 4-1. (The default position of
mounting brackets is 19” rack width, front mount.)
FIXED
BRACKETS
SLIDE
BRACKETS
2.7 (68)
2.7 (68)
2.7 (68)
2.7 (68)
3.9 (99)
1.2 (31)
10.2 (260)
Figure 4-1 System Mounting
2. Place the subrack into the cabinet.
3. The subrack with adjustable brackets has to be fastened to the cabinet in the middle of the
mounting bracket with two M6 x 12mm screws. Tighten the screws to 6Nm, Figure 4-2.
Figure 4-2 Slide Bracket Fixing