System Configuration

The Unipower HPL110A measures voltage in all three legs of the 3-phase supply (or one

leg and neutral for single phase versions) and current in one leg.  The HPL110A has an

internal current transformer with a measurement range of 8 Amps.

In configuring the HPL110A for a particular application, the voltage rating of the unit

must match the mains supply being used and the effective current measured by the unit

must be within its internal 8 Amp capacity.

4.1 VOLTAGE MATCHING: 

From Table 4.1, ensure that the rated voltage for the HPL110A unit matches the mains

voltage being used.

For single phase applications, an isolation transformer must always be used with a 

secondary voltage of 24V.

Note:

The display full scale for the HPL110A is based on the nominal voltage of the unit;

e.g. when using a nominal 220V unit at 208V, the display range will read 95% at full load

(208/220 in %). 

4.2  CURRENT MATCHING:  

From the motor name plate, note the full load current in Amps. If full load amperage for

the motor is 8 amps or less, an external current transformer is not required.  

If the full load current is greater than 8 amps, then an external N/1 or N/5 current 

transformer must be used.  

Refer to Table 4.2 for the appropriate selection of current transformer and current range

setting for the HPL110A.  

The HF3A current transformers specified in this table are low voltage, through-primary

devices offered as accessories for the HPL110A product line; equivalent devices from other

manufacturers may be substituted at user’s discretion.

8

Catalog Number

Phase

Use for 50/60 Hz Mains Voltages

HPL110/220

3-Phase

208/220/230/240 VAC

HPL110/380

3-Phase

380/415 VAC

HPL110/460

3-Phase

460/480 VAC

HPL110/575

3-Phase

575/600 VAC

HPL110A/S24

1-Phase

110/120 and 208/220/230/240 VAC

F i g u re   4 . 1

4

Содержание HPL110/220

Страница 1: ...o n i t o r Installation and Operation True Motor Power Monitor with High Trip Alarm Low Trip Alarm Digital Display Start and Trip Delay Timers Typical Applications Pumps Fans Conveyors Crushers and m...

Страница 2: ...on 6 Specifications 13 Technical Specifications DIP Switches 7 Mechanical Installation 14 HPL110A Current Transformer 8 Programming 16 9 Troubleshooting 19 10 Set Up Log Sheet 20 WARNING Dangerous vol...

Страница 3: ...f dry running and High Power Alarm for example to stop a feeder when blocked The alarm functions activate a single alarm relay which may be used to control the motor being monitored i e to trip a shut...

Страница 4: ...o the on condition At time 1 the motor is turned on and the load immediately surges due to the starting current inrush before settling to a steady value at time 4 5 At time 8 this example shows power...

Страница 5: ...ion with the L1 Max Limit and programmable in the range 0 0 to 99 9 seconds Tr1 is time for which the P must remain above the L1 Max Limit before an alarm is declared If P falls below the L1 during th...

Страница 6: ...the high power alarm becomes active and a hysteresis band programmable is shown under this alarm level At time 5 the mixing power rises above the L1 Max Limit and after the Tr1 trip delay times out th...

Страница 7: ...pressure and high power The HPL110A provides a simple non intrusive monitoring function which can be effectively used to protect against dead heading Again dry running is detrimental to the pump and r...

Страница 8: ...e g when using a nominal 220V unit at 208V the display range will read 95 at full load 208 220 in 4 2 CURRENT MATCHING From the motor name plate note the full load current in Amps If full load ampera...

Страница 9: ...formers ensure that the wraps are wound to the sides and not across the top or bottom of the current transformer 9 Figure 4 2 Full Load Current Ratio Primary HPL110 Range Effective Range Amps Transfor...

Страница 10: ...ormally closed contact on the motor starter being used to short S2 to Gnd when the motor is off This activates the S2 inhibit function which inhibits alarm functions and prevents a Min Limit alarm on...

Страница 11: ...ists fail safe operation The Relay LED on the front panel is illuminated when the Relay is energized this Relay LED therefore is on during normal operation and is switched off when an alarm occurs 11...

Страница 12: ...d it can be connected between Terminal 11 and neutral to illuminate when an alarm state exists 5 5 RESET FUNCTION The HPL110A may be reset by any one of three methods Manual Reset Depress the Reset ke...

Страница 13: ...250VAC 5Amp Mechanical Housing Noryl Mounting Panel mounting for 2 64 x 2 64 cut out 67 x 67 mm Min mounting depth 5 125 mm Protection Class IP54 Terminals 12 AWG max 20A 7 in lb tightening torque 0...

Страница 14: ...is required of 2 64 x 2 64 67 x 67 mm the HPL110A is installed through the cut out and retained with fittings supplied A minimum depth of 5 125 mm will be required to allow space for the terminal fitt...

Страница 15: ...be mounted either directly to standard 35mm DIN rail as shown on Page 9 using accessory 741B0231 not included or screwed directly to a panel using two M5 or 10 cap screws with accessory 741B0230 6 no...

Страница 16: ...e the limits have been set first de activate the high and low alarms by programming the L1 Max Limit to 101 and the L2 Min Limit to 0 When a limit is de activated OFF is written in the display Then st...

Страница 17: ...g the Peak Detect function run the system at its minimum load condition and observe the min normal reading by depressing the D key Set the Min Limit value a few units lower than this value by depressi...

Страница 18: ...DIP Switch 1 to the ON position see section 6 2 for access When Program Lock is ON all setting values may be viewed but not changed The Reset button however remains functional Power Down Alarm Block I...

Страница 19: ...tly long Either increase L1 Max Limit or TS Start Timer as appropriate First check that alarm values are correct If nuisance alarms persist increase the Tr Reaction Timer associated with the nuisance...

Страница 20: ...80 460 575 S24 Current Transformer None 50 5 75 5 100 5 150 5 Turns through CT 1x 2x Program Current Range A 1 3 5 8 Start Time S S Max Limit Reaction Timer S Max S Min Limit Reaction Timer S Min S Pr...

Отзывы: