Programming
The Modes and Programming ranges for the HPL110A are given in the Function Table below:
The HPL110A is programmed using only three keys - MODE,
D, Ñ
. The MODE key is used
to select the variable to be programmed and the values are adjusted using the
D, Ñ
keys.
The default state for the HPL110A on power up is kW[%] mode. If any key is continuously
depressed, its action is repeated. When no key has been depressed for about 5 seconds,
the mode reverts to kW[%] mode.
The HPL110A is programmed in the following sequence:
8.1 CURRENT RANGE
Depress the MODE key to select Current Range [A] mode. From Table 4.2, find the correct
Current Range value for the unit as installed and enter this value using the
D, Ñ
keys.
8.2 CHOOSING LIMITS
The HPL110A may be programmed while running and it is useful to observe normal
conditions in order to set the remaining parameters - Ts, L1, Tr1, L2 and Tr2.
To run the HPL110A before the limits have been set, first de-activate the high and low
alarms by programming the L1 Max Limit to 101% and the L2 Min Limit to 0%. When
a limit is de-activated, “OFF” is written in the display.
Then start the motor and:
-
note time delay between pressing start button and stable display reading,
-
load the system to max. normal operating load and press the
D
key to note the max.
allowable %kW value,
-
load the system to min. normal operating load and press the
Ñ
key to note the min.
allowable %kW value.
16
8
Mode
Function
Variable
▼
▲
Display
Default
Power=kW(%)
kW display
-
Min.Peak
Max.Peak
kW (%)
-
Max. Limit
Max.kW Limit
5-100%/off
Decrease
Increase
Off/Max.Limit (%)
80%
Min.Limit (%)
Min.kW Limit
Off/5-100%
Decrease
Increase
Off/Min.Limit (%)
20%
Start Timer(S)
Start Timer
0.1-99.9 Sec.
Decrease
Increase
Ts (Sec.)
2.0 Sec.
Reaction Timer(S)
Max.Alarm Delay
0.0-99.9 Sec
Decrease
Increase
Max. Tr (Sec.)
0.1 Sec.
Reaction Timer(S)
Min.Alarm Delay
0.0-99.9 Sec
Decrease
Increase
Min. Tr (Sec.)
0.1 Sec.
Hysteresis(%)
2 points regulation
2-50%
Decrease
Increase
Hysteresis (%)
10%.
Current Range(A)
Current Range
1,3,5,8 Amp.
Decrease
Increase
1,3,5,8
5 Amp.