background image

11

Part Number 550-110-726/0703

GWA/GWI/GWS

 

Gas-Fired Water Boilers – 

User’s Information Manual

  Periodically

Operate boiler relief

To avoid water damage or scalding due to valve
operation, a metal discharge line must be connected
to relief valve outlet and run to a safe place of dis-
posal. This discharge line must be installed by a
qualified heating installer or service technician in
accordance with the instructions in the Boiler
Manual. The discharge line must be terminated so
as to eliminate possibility of severe burns should
the valve discharge.

1. Before proceeding, verify that the relief valve outlet has been

piped to a safe place of discharge, avoiding any possibility of
scalding from hot water.

2. Read the boiler pressure/temperature gauge to make sure

the system is pressurized.

3. Lift the relief valve top lever slightly, allowing water to relieve

through the valve and discharge piping.

4. If water flows freely, release the lever and allow the valve to

seat. Watch the end of the relief valve discharge pipe to ensure
that the valve does not weep after the line has had time to
drain. If the valve weeps, lift the seat again to attempt to clean
the valve seat. If the valve continues to weep afterwards,
contact your qualified service technician to inspect the valve
and system.

5. If water does not flow from the valve when you lift the lever

completely, the valve or discharge line may be blocked.
Immediately shutdown the boiler, following the instructions
on the inside jacket top "Lighting Instructions". Call your
qualified service technician to inspect the boiler and system.

Test low water cutoff (if installed)

1. If the boiler or system is fitted with a low water cutoff device,

test the device following the cutoff manufacturer’s instructions.

Oil inducer motor (GWI and GWS boilers)

1. Use only S.A.E. 20 motor oil. DO NOT use household

universal oils.

Use only S.A.E. 20 motor oil to lubricate the inducer
motor. Do not use common universal household oils.

2. Place a few drops of oil in each of the two oiler cups on the

inducer motor.

Clean vent termination & air intake screens —

GWS boilers only

1. Remove all lint and debris from both the boiler air intake screen

and the flue discharge screen.

The boiler control module will sense blockage of the air intake
or flue and lockout if the blockage is excessive. It will signal
the failure by flashing the appropriate indicator lights on the
control board.

2. If removing the debris does not allow the boiler to operate

correctly afterwards, contact your qualified service technician
to inspect the boiler and vent/air systems.

Main burner flame

Proper main burner flame (see below):

1. Yellow-orange streaks may appear (caused by dust).

Improper main burner flame:

1. Overfired — Large flames.

2. Underfired — Small flames.

3. Lack of primary air — Yellow tipping on flames (sooting will

occur).

  Check monthly

  Every 6 months

1. Follow “TO TURN OFF GAS TO APPLIANCE” on the

 

"Lighting

or Operating Instructions"

 

on the inside of the jacket panel.

You will also find these instructions on pages 4 through 8 of
this manual.

Use the "Lighting or Operating Instructions" for the gas valve
model installed on the boiler.

2. Do not drain system unless exposure to freezing temperatures

will occur.

3. Do not drain the system if it is filled with an antifreeze solution.

4. Do not shut down boilers used for domestic water heating.

They must operate year-round.

  End of season shutdown

1. See page 12.

  Troubleshooting

Содержание GWA

Страница 1: ...vice procedures and the correct Lighting or Operating Instruc tions Propane gas odorant Propane boilers only Your propane supplier mixes an odorant with the propane to make its pres ence detectable In some instances the odorant can fade and the gas may no longer have an odor Propane gas can accumulate at floor level Smell near the floor for the gas odorant or any unusual odor If you suspect a leak...

Страница 2: ...ical supply to pump Instead shut off the gas supply at a location external to the appliance 6 DO NOT use this boiler if any part has been under water Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water 7 Have the building monitored when it is vacant for an extended period Safety controls c...

Страница 3: ...relief valve Check automatic air vents if used Check pilot and main burner flames Check and clean vent termination air intake screens GWS boil ers only Periodically Test low water cutoff if used Oil inducer motor GWI and GWS boilers only Every 6 months Operate relief valve End of season Shut down procedure Maintain your boiler using this schedule To locate Lighting or Operating Instructions Find y...

Страница 4: ...er to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicated on damper assembly 6 Turn gas control knob clockwise to OFF 7 When equipped with vent damper verify damper blade is in full open position 8 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas ...

Страница 5: ...cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowest setting 3 When equipped with Effikal vent damper Model RVGP place service switch in Hold Damper Open position 4 Turn off all electrical power to the appliance 5 When equipped with Johnson Con...

Страница 6: ... for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 10 Turn gas control knob counterclockwise to ON Press down on White Rodgers 36C valve knob to turn 11 Turn on all electric power to the appliance 12 When equipped with Effikal vent damper place service switch in Automatic Operation position 13 Set thermostat t...

Страница 7: ...he fire department 1 Stop Read the safety information above on this label 2 Set the thermostat to lowest setting 3 When equipped with Effikal vent damper Model RVGP place service switch in Hold Damper Open position 4 Turn off all electrical power to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicate...

Страница 8: ...witch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WHAT TO DO IF YOU SMELL GAS 1 STOP Read the safety information above on this label 2 Set the thermostat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove jacket front pa...

Страница 9: ...rovides detailed instruc tions for completing the maintenance items listed in the maintenance schedule page 3 In addition to this maintenance the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician See page 12 for troubleshooting procedures for common problems Air openings 1 Verify that combustion and ventilation air openings to the boil...

Страница 10: ...echnician at once if you find any problem Failure to inspect the vent system as noted above and have it repaired by a qualified service techni cian can result in vent system failure causing se vere personal injury or death Check condensate drain system GWI or GWS 1 Inspect condensate drain fittings and tubing Verify that condensate can flow freely to drain Boiler relief valve 1 Inspect the boiler ...

Страница 11: ...if installed 1 If the boiler or system is fitted with a low water cutoff device test the device following the cutoff manufacturer s instructions Oil inducer motor GWI and GWS boilers 1 Use only S A E 20 motor oil DO NOT use household universal oils Use only S A E 20 motor oil to lubricate the inducer motor Do not use common universal household oils 2 Place a few drops of oil in each of the two oil...

Страница 12: ...eak compounds Black water condition Oxygen corrosion due to leaks in boiler and piping Have qualified service technician repair at once Keep pH of water between 7 0 to 8 5 Popping or percolating noise heard in boiler Mineral deposits in sections due to constant use of makeup water Call qualified service technician to de lime boiler if necessary In some cases deposits will be too heavy to remove wi...

Отзывы: