background image

GWA/GWI/GWS

 

Gas-Fired Water Boilers – 

User’s Information Manual

10

Part Number 550-110-726/0703

  Check monthly

Boiler piping

1. Visually inspect for leaks around piping, circulators, relief valve

and other fittings. Immediately call a qualified service
technician to repair any leaks.

Have leaks fixed at once by a qualified service tech-
nician. Continual fresh makeup water will reduce
boiler life. Minerals can build up in sections, reduc-
ing heat transfer, overheating cast iron, and caus-
ing section failure.
Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to
boiler and system components can occur, resulting
in possible severe personal injury, death or sub-
stantial property damage.

Venting system

1. Visually inspect all parts or the flue gas venting system for

any signs of blockage, leakage or joints or deterioration of
the piping.

2.

GWA boilers

 — Check vent system operation:

a. With boiler firing, hold a candle or match below lower edge

of draft hood “skirt.” If flame does not blow out, but burns
undisturbed, the vent system is working properly. If flame
blows out or flickers severely, the vent system must be
checked for obstructions or other causes of improper
venting.

b. Verify the vent damper opens before burners ignite.

3. Notify your qualified service technician at once if you find any

problem.

Failure to inspect the vent system as noted above
and have it repaired by a qualified service techni-
cian can result in vent system failure, causing se-
vere personal injury or death.

Check condensate drain system (GWI or GWS)

1. Inspect condensate drain fittings and tubing. Verify that

condensate can flow freely to drain.

Boiler relief valve

1. Inspect the boiler relief valve and the

relief valve discharge pipe for signs of
weeping or leakage.

2. If the relief valve often weeps, the

expansion tank may not be working
properly.

Immediately contact your qualified
service technician to inspect the
boiler and system.

Automatic air vents (if used)

1. Remove the cap from any automatic

air vent in the system and check
operation by depressing valve 

B

slightly with the tip of a screwdriver.

2. If the air vent valve appears to be

working freely and not leaking, replace
cap 

A

, twisting all the way on. Loosen

cap 

one turn to allow vent to operate.

3. Have vent replaced if it does not

operate correctly.

Pilot burner flame

Proper pilot flame (see below):

1. Blue flame.

2. Inner cone engulfing thermocouple (standing pilot) or pilot

flame sensor (spark-ignited pilot).

3. Thermocouple or pilot flame sensor glowing cherry red.

Improper pilot flame:

1. Overfired — Large flame lifting or blowing past pilot flame

sensor.

2. Underfired — Small flame. Inner cone not engulfing pilot flame

sensor.

3. Lack of primary air — Yellow flame tip.

4. Incorrectly heated pilot flame sensor.

  Check monthly

Содержание GWA

Страница 1: ...vice procedures and the correct Lighting or Operating Instruc tions Propane gas odorant Propane boilers only Your propane supplier mixes an odorant with the propane to make its pres ence detectable In some instances the odorant can fade and the gas may no longer have an odor Propane gas can accumulate at floor level Smell near the floor for the gas odorant or any unusual odor If you suspect a leak...

Страница 2: ...ical supply to pump Instead shut off the gas supply at a location external to the appliance 6 DO NOT use this boiler if any part has been under water Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water 7 Have the building monitored when it is vacant for an extended period Safety controls c...

Страница 3: ...relief valve Check automatic air vents if used Check pilot and main burner flames Check and clean vent termination air intake screens GWS boil ers only Periodically Test low water cutoff if used Oil inducer motor GWI and GWS boilers only Every 6 months Operate relief valve End of season Shut down procedure Maintain your boiler using this schedule To locate Lighting or Operating Instructions Find y...

Страница 4: ...er to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicated on damper assembly 6 Turn gas control knob clockwise to OFF 7 When equipped with vent damper verify damper blade is in full open position 8 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas ...

Страница 5: ...cian to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowest setting 3 When equipped with Effikal vent damper Model RVGP place service switch in Hold Damper Open position 4 Turn off all electrical power to the appliance 5 When equipped with Johnson Con...

Страница 6: ... for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 10 Turn gas control knob counterclockwise to ON Press down on White Rodgers 36C valve knob to turn 11 Turn on all electric power to the appliance 12 When equipped with Effikal vent damper place service switch in Automatic Operation position 13 Set thermostat t...

Страница 7: ...he fire department 1 Stop Read the safety information above on this label 2 Set the thermostat to lowest setting 3 When equipped with Effikal vent damper Model RVGP place service switch in Hold Damper Open position 4 Turn off all electrical power to the appliance 5 When equipped with Johnson Controls vent damper Model M35 manually rotate damper blade in direction of arrow to Open position indicate...

Страница 8: ...witch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WHAT TO DO IF YOU SMELL GAS 1 STOP Read the safety information above on this label 2 Set the thermostat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove jacket front pa...

Страница 9: ...rovides detailed instruc tions for completing the maintenance items listed in the maintenance schedule page 3 In addition to this maintenance the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician See page 12 for troubleshooting procedures for common problems Air openings 1 Verify that combustion and ventilation air openings to the boil...

Страница 10: ...echnician at once if you find any problem Failure to inspect the vent system as noted above and have it repaired by a qualified service techni cian can result in vent system failure causing se vere personal injury or death Check condensate drain system GWI or GWS 1 Inspect condensate drain fittings and tubing Verify that condensate can flow freely to drain Boiler relief valve 1 Inspect the boiler ...

Страница 11: ...if installed 1 If the boiler or system is fitted with a low water cutoff device test the device following the cutoff manufacturer s instructions Oil inducer motor GWI and GWS boilers 1 Use only S A E 20 motor oil DO NOT use household universal oils Use only S A E 20 motor oil to lubricate the inducer motor Do not use common universal household oils 2 Place a few drops of oil in each of the two oil...

Страница 12: ...eak compounds Black water condition Oxygen corrosion due to leaks in boiler and piping Have qualified service technician repair at once Keep pH of water between 7 0 to 8 5 Popping or percolating noise heard in boiler Mineral deposits in sections due to constant use of makeup water Call qualified service technician to de lime boiler if necessary In some cases deposits will be too heavy to remove wi...

Отзывы: