PART III: MAINTENANCE
35
Adjusting the electrodes
Important Note: Check the ignition and detection electrodes after removing/adjusting the combustion head.
The gap between the ignition electrodes must be
4mm
.
TP90A-91A-92A-93A
Fig. 9
TP512A-515A-520A-525A
Fig. 10
Replacing the ignition electrodes
To replace the ignition electrodes, proceed as follows:
1
remove the burner cover
2
loose the nuts that fasten;the electrodes group to the combustion head (A);
3
disconnect the electrodes cables (B);
4
loose the security dowes of the adjusting ring nut (C);
5
shift the electrodes group back to the outside and remove the combustion head (D),
6
loose the screw of th eignition electrodes support (E);
7
remove the electrodes and replace them paying attention to the measures shown on previous paragraph.
ATTENTION:
avoid
the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), otherwise the boi-
ler’s operation would be compromised. Check the electrodes position after any intervention on the combustion head.
ATTENTION:
avoid
the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), otherwise the boi-
ler’s operation would be compromised. Check the electrodes position after any intervention on the combustion head.
528
528
7
4
-
TP512A
TP515A
TP520A
TP525A
A
534 mm
519 mm
515 mm
515 mm