PART I: SPECIFICATIONS

6

              

Burner model identification

Burners are identified by burner type and model. Burner model identification is described as follows.

                 

Fuel

The burner technical specifications, described in this manual, refer to natural gas (calorific net
value Hi = 9.45 kWh/Stm

3

,  density 

ρ

 = 0.717 Kg/Stm

3

). For different fuel such as LPG, town gas

and biogas, multiply the values   of flow and pressure by th corrective factors shown in the table
below.

For example, to obtain the flow and pressure values for the biogas:

Type

RX63

Model   

M-.

MD. S.

*.

A. 1.

80.

EA.

(1)

(2)

(3)

(4)

(5)

(6)

(7)

(8)

(9)

1 BURNER TYPE

RX63

2 FUEL

M - Natural gas
B - Biogas
L -  LPG

3 OPERATION (Available versions)

PR - Progressive 
MD - Fully modulating

4 BLAST TUBE

S - Standard              L - Extended

5 DESTINATION COUNTRY

* - see data plate

6 BURNER VERSION

A - Standard
Y - Special

7 EQUIPMENT 

0 = 2 gas valves
1 = 2 gas  gas proving system
7 = 2 gas  maximum gas pressure switch
8 = 2 gas  gas proving maximum gas pressure switch

8 GAS CONNECTION 

see Specifications

32 = Rp1

1/4                     

40 = Rp1

1/2                     

50 = Rp2

65 = DN65                  80 = DN80

9 MICRO-PROCESSOR CONTROL

EA = micro-processor control, without inverter
EB = micro-processor control, with inverter

WARNING! The burner must be used only with the fuel specified in the burner data
plate .

Fuel

Hi 

(KWh/Stm

3

)

ρ

 

(kg/Stm

3

)

f

Q

f

p

LPG

26.79

2.151

0.353

0.4

Town gas

4.88

0.6023

1.936

3.3

Biogas

6.395

1.1472

1.478

3.5

ATTENTION! The  combustion head type and the  settings  depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .

ATTENTION! The corrective factors in the above table depend on the gas composition, so on the calorifc value and
the density of the gas. The above value can be taken only as reference.

Type --
Model

--

Year --
S.Number --
Output --
Oil Flow 

--

Fuel

--

Category --
Gas Pressure 

--

Viscosity --
El.Supply --
El.Consump. --

Q

biogas

Q

naturalGas

1 478

,

=

p

biogas

p

naturalGas

3 5

,

=

Содержание RX63

Страница 1: ...M039379CA Rel 0 02 2018 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES LMV2x 3x Microprocessor controlled gas burners MANUAL OF INSTALLATION USE MAINTENANCE RX63...

Страница 2: ...n a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only burners designed according to the regulations in force...

Страница 3: ...EC Gas Directive 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Directive 2006 42 EC Machinery Directive Harmonized standards UNI EN 676 Automatic forced draught burners for...

Страница 4: ...ype Characteristics and test methods Industrial burners European directives 2009 142 EC Gas Directive 2014 35 UE Low Tension Directive 2014 30 UE Electromagnetic compatibility Directive 2006 42 EC Mac...

Страница 5: ...pressure in the utilisation limits The actuators move proportionally the air damper and the gas butterfly valve in order to achieve the optimisation of the gas flue values as to get an efficient combu...

Страница 6: ...gas valves gas proving system 7 2 gas valves maximum gas pressure switch 8 2 gas valves gas proving system maximum gas pressure switch 8 GAS CONNECTION see Specifications 32 Rp11 4 40 Rp11 2 50 Rp2 65...

Страница 7: ...alorific value Hi 93 5 MJ Stm3 Note2 Maximum gas pressure 360mbar with Dungs MBDLE 500mbar with Siemens VGD Minimum gas pressure see gas curves Note3 Burners are suitable only for indoor operation wit...

Страница 8: ...3 458 131 327 540 502 198 155 RX63 50 87 1039 1124 328 300 385 705 342 978 634 344 219 249 233 300 347 M10 330 216 250 233 473 131 342 526 502 198 155 RX63 65 87 1039 1124 328 300 385 705 342 1062 718...

Страница 9: ...spheric pressure at 1013mbar ambient temperature at 15 C NOTE The performance curve is a diagram that represents the burner performance in the type approval phase or in the laboratory tests but does n...

Страница 10: ...ine as far as matching on the y axis the value of pressure necessary to get the requested furnace input This value must be lower or equal to the pgas value calcula ted before GAS PRESSURE IN THE NETWO...

Страница 11: ...the combustion chamber 3 Gas pressure outlet on the butterfly valve 4 Differential pressure gauge Measuring the gas pressure in the combustion head In order to measure the pressure in the combustion h...

Страница 12: ...PART I SPECIFICATIONS 12 Pressure rate in combustion head curves Curves are referred to pressure 0mbar in the combustion chamber Gas pressure in combustion head RX63 M Stm3 h...

Страница 13: ...tions and health and safety regulations Do not stand under lifted loads Packing The burners are despatched in wooden crates whose dimensions are z 1636mm x 1036mm x 1016mm L x P x H Packing cases of t...

Страница 14: ...diagram In case the burner must be coupled with boilers with a combustion chamber smaller in dia meter or shorter than those described in the diagram please contact the supplier to verify that a corr...

Страница 15: ...TWORK BE SURE THAT THE MANUAL CUTOFF VALVES ARE CLOSED Gas train with valves group MB DLE 2 valves gas filter pressure governor Gas train with valves group VGD with built in gas pressure governor 1 Fi...

Страница 16: ...vices The procedures of installation fo the gas valves are showed in the next paragraphs according to the gas train used z threaded gas trains with Multibloc Dungs MB DLE or Siemens VGD20 z flanged ga...

Страница 17: ...mounting positions Fig 8 4 after installation perform leakage and functional test 5 disassembly in reverse order 2 MULTIBLOC DUNGS MB DLE 415 420 Mounting 1 Loosen screws A and B do not unscrew Fig 9...

Страница 18: ...in figure 8mm external size pipe supplied loose to the gas pressure nipples placed on the gas pipe downstream the gas valves gas pressure must be measured at a distance that must be at least 5 times...

Страница 19: ...on functionality and compliance with the health and safety principles of the earth cable If in doubt ask for an accurate inspection by qualified technical engineers z Check the connection to the groun...

Страница 20: ...ration with separate electrical panel optional The length of the electrical cables must comply with the provisions in the technical sheets of the equipment or the advice the company gives at the time...

Страница 21: ...dy Injury hazard Do not touch any parts containing fuel i e tank and pipes Scalding hazard Do not use the burner in situations other than the ones provided for in the data plate Do not use fuels other...

Страница 22: ...ER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE EXCEPT FOR ITS MAINTENANCE TO SECURE THE MACHINE ACT ON THE ISOLATOR SWITCH IN CASE OF ANOMALIES THAT REQUIRED A SHUT DOWN OF THE BURNER IT S POSSIBLE...

Страница 23: ...oving system LED turns on At the end of the test the burner staring cycle begins in case of leakage in a valve the gas proving system stops the bur ner and the lamp B1 turns on z At the beginning of t...

Страница 24: ...he head air and fuel side 6 Open the thermostatic series and the safety chain 7 Turn the main switch on the panel front with the MAN AUTO selector to position 0 8 Select the GAS mode with the fuel sel...

Страница 25: ...and keys Key F A While pressing the two keys contemporarly the code message will appear by entering the proper password it is possible to access the Service mode Info and Enter keys Used for Info and...

Страница 26: ...Dati di processo Process data OEM Service Info Fase Phase Funzione Function Ph00 Fase blocco Lockout phase Ph01 Fase di sicurezza Safety phase Ph10 t10 tempo raggiungimento posizione riposo t10 home r...

Страница 27: ...t62 massimo tempo bassa fiamma funzionamento 2 in preparazione per spegnimento verso bassa fiamma t62 max time low fire operation 2 prepa ring for shutdown traveling to low fire Ph70 t13 tempo postcom...

Страница 28: ...hows some basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _ on the right 6 press InFo for 1 3 seconds the date...

Страница 29: ...and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event which does not lead to shutdown The display shows current error code c alternating...

Страница 30: ...parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for more than three seconds orto return to the normal displa...

Страница 31: ...ver C By screwing down the pressure is increased and by unscrewing it is reduced Note the screw VSB must be removed only in case of replacemente of the coil Fig 16 Fig 17 Key 1 Electrical connection f...

Страница 32: ...z Repeat the ignition cycle of the burner and check it runs properly z Refit the transparent plastic cover on the pressure switch Calibration of low gas pressure switch As for the gas pressure switch...

Страница 33: ...is the optimal configuration to assure flame stability If different settings are required it is possible to change the position move the combustion head backwards turning clockwise the screw VRT CAUTI...

Страница 34: ...ventually wash it with non corrosive detergents z Check the blast tube it must be substituted in case of obvious cracks or anomalous holes Slight deformations that do not affect combustion may be tole...

Страница 35: ...ousing screw in screws 1 6 without using any force and fasten 5 Perform leakage and functional test pmax 360 mbar 6 Pay attention that dirt does not fall inside the valve Replacing the spring in the g...

Страница 36: ...5 and tighten screws 1 4 without using any force and fasten 5 Perform leakage and functional test pmax 360 mbar 6 Pay attention that dirt does not fall inside the valve Gas filter maintenance To clean...

Страница 37: ...ct metallic parts blast tube head etc otherwise the boi ler s operation would be compromised Check the electrodes position after any intervention on the combustion head OR V G C VRT AR To replace the...

Страница 38: ...ollows 1 turn the burner main switch to 0 Off position 2 disconnect the power mains 3 close the fuel valve of the supply line Burner disposal In case of disposal follow the instructions according to t...

Страница 39: ...PART IV MAINTENANCE 39 WIRING DIAGRAMS Refer to the attached wiring diagrams WARNING 1 Electrical supply 230V 400V 50Hz 3N a c 2 Do not reverse phase with neutral 3 Ensure burner is properly earthed...

Страница 40: ...TURES WITHOUT IGNITING THE BURNER Air pressure switch damaged or bad links Check air pressure switch functions and links Burner control damaged Replace burner control BURNER LOCKS OUT WITHOUT ANY GAS...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 3 01 2017...

Страница 46: ...900 Process data 32 Actuators references 33 Gas proving system 33 Air fuel curve points 33 COMMISSIONING THE BURNER 34 Warm setting 38 Cold setting 39 BURNER STARTUP WITH LMV2x ALREADY PROGRAMMED 40...

Страница 47: ...CTIONS FOR BURNERS z The burner should be installed in a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only b...

Страница 48: ...ditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directi...

Страница 49: ...apparatus EN 50165 Electrical equipment of non electric appliances for household and similar purposes Safety requirements UNI EN 746 2 Industrial thermoprocessing equipment Burner data plate For the...

Страница 50: ...forms all the burner control functions and of the Siemens AZL local programming unit that interfaces the system with the user Keys 1 Burner 2 AZL2 3 Air actuator 4 Fuel actuator 5 LMV2 User interface...

Страница 51: ...ice mode Info and Enter keys Used for Info and Service menues Used as Enter key in the setting modes Used as Reset key in the burner operation mode Used to enter a lower level menu Key Used to decreas...

Страница 52: ...8 Parameters level heating engineer...

Страница 53: ...ription Password 000 Internal parameters OEM Service 100 Informazioni generali General OEM Service Info 200 Controllo bruciatore Burner control OEM Service 300 Controllo bruciatore solo LMV26 Burner c...

Страница 54: ...kup data set Service Info Param Descrizione Description Password LMV20 LMV27 LMV26 LMV37 102 Data produzione in gg mm aa Identification date yy mm dd Service Info x x x 103 Numero identificativ Identi...

Страница 55: ...ed OEM Service x x 145 Indirizzo dispositivo per Modbus Device address for Modbus OEM Service x x 146 Velocit di trasmissione per Modbus Baud rate for Modbus OEM Service x x 147 Parit per Modbus Parit...

Страница 56: ...erci zio azzerabile da Service Fuel 1 Operation hours resettable Service Info x 174 Fuel 1 secondo combustibile Numero di partenze azzerabile da Service Fuel 1 Number of startups resettable Service In...

Страница 57: ...e fuel train modula ting multistage actuators etc __ undefined delete curves 1 gas direct ignition G mod 2 ignition by gas pilot connected between the two gas solenoid valves EV1 EV2 Gp1 mod 3 ignitio...

Страница 58: ...x x x 210 Allarme impedimento avviamento 0 non attivo 1 attivo Alarm in the event of start prevention 0 deactivated 1 activated OEM Service x x x 211 Tempo aumento giri ventilatore valore fab brica 2...

Страница 59: ...nge impostazione 20s 60min Gas Prepurge time default value 20s range 20s 60min OEM Service x x x 226 Gas tempo di preaccensione valore fab brica 2s range impostazione 0 2s 60min Gas Preignition time d...

Страница 60: ...ivo 1 esso modificabile solo su LMV37 Dal punto di vista della sicurezza il funzionamento continuo valido esclusiva mente per bruciatori di gas con elettrodo di rilevazione Gas Forced intermittent ope...

Страница 61: ...Postpurge time 3 abortion with load controller LR ON OEM Service x x x 261 Olio sonda rilevazione fiamma attivo valore fabbrica 0 0 QRB QRC 1 ION QRA Oil active detector flame evaluation default value...

Страница 62: ...0 inactive 1 active from phase 38 2 active from safety time TSA OEM Service x x 277 Olio Pressostato olio di massima ingresso POC 0 inattivo 1 pressostato olio di massima 2 POC Oil Pressure switch max...

Страница 63: ...lvole EV1 EV2 del gas regolazione pneumatica Gp1 mod pneu 9 accensione tramite pilota gas con attacco a monte dell elettrovalvola EV1 del gas regolazione pneumatica Gp2 mod pneu 10 olio modulante con...

Страница 64: ...ore fabbrica 1 0 QRB QRC 1 ION QRA Fuel 1 Gas active detector flame evalua tion default value 1 0 QRB QRC 1 ION QRA OEM Service x 322 Combustibile 1 Gas Preventilazione valore fabbrica 1 1 attivo 0 no...

Страница 65: ...Intervallo 2 valore fabbrica 2s range impostazione 0 2s 60min Fuel 1 Gas Interval 2 default value 2s range 0 2s 60min OEM Service x 333 Combustibile 1 Gas Tempo postcombu stione valore fabbrica 8s ra...

Страница 66: ...t filling time default value 3s range 0 2s 10s OEM x 345 Combustibile 1 Gas tempo test pressione gas valore fabbrica 10s range imposta zione 0 2s 60s Fuel 1 Gas proving test time gas pres sure default...

Страница 67: ...mbustibile 1 Olio tempo di risposta a cadute di pressione entro TSA1 e TSA2 valore fabbrica 1 8s range imposta zione 0 2s 14 8s Fuel 1 Oil time to respond to pressure faults in TSA1 and TSA2 default v...

Страница 68: ...censione corta Ph38 fase pro gramma 38 1 preaccensione lunga con ventilatore Ph22 fase programma 22 Fuel 1 Oil time oil ignition default value 1 0 short preignition Ph38 progr phase 38 1 long preignit...

Страница 69: ...ting the cur ves OEM Service x x x 403 Curve controllo inverter F A si accede alla lista dei punti da impostare da P0 a P9 con sultare paragrafo Impostazione curve Ratio control curves VSD curve setti...

Страница 70: ...repurge speed 100 Index 2 postpurge speed 50 OEM Service x x 504 Combustibile 1 Posizione servocomando combustibile in assenza di fiamma no flame Indice 0 posizione di sosta 0 Indice 1 posizione preve...

Страница 71: ...di carico per modulazione valore fabbrica n d range imposta zione 20 100 Lower load limit default value n d range 20 100 OEM Service x x x 546 Percentuale massima di carico per modula zione valore fa...

Страница 72: ...0 combustibile Indice 1 aria Tolerance limit of position monitoring 0 1 Index 0 fuel Index 1 air OEM Service x x x 608 Combustibile 1 Impostazione punto di riferi mento Indice 0 combustibile Indice 1...

Страница 73: ...top SQN1 3 both OEM x 613 Tipo di servocomando Indice 0 combustibile Indice 1 aria 0 5s 90 1Nm 1 2Nm 3Nm 1 10s 90 6Nm 2 17s 90 10Nm Type of actuator Index 0 fuel Index 1 air 0 5 s 90 1Nm 1 2Nm 3Nm 1 1...

Страница 74: ...tion of analog output default value 0 0 DC 0 10 V 1 DC 2 10 V 2 DC 0 2 10 V OEM Service LMV27 x x ATTENTION as for SQM3x actuators set the direction according to the acutator function As far as SQN1x...

Страница 75: ...ror history 701 725 02 diagnostic code Service Info Storico errori 701 725 03 classe errore Error history 701 725 03 error class Service Info Storico errori 701 725 04 fase Error history 701 725 04 ph...

Страница 76: ...Active load source OEM Service 945 Solo con LMV26 Combustibile attuale 0 combustibile 0 1 combustibile 1 Actual fuel 0 fuel 0 1 fuel 1 Service Info 947 Risultato interrogazione contatti codifica bit...

Страница 77: ...a leakage test designed to detect leaking gas valves and if necessary to pre vent the valves from opening or ignition from being switched on Lockout is initiated When performing valve proving the gas...

Страница 78: ...2x already programmed At the first LMV startup the AZL display will show It means that the unit was never set or that no mode was chisen or that some parameters have to be set furthert Push F fuel and...

Страница 79: ...l elettrov EV1 del gas Gp2 mod 4 accensione a gasolio modul Lo mod 5 accens a gasolio bistadio Lo 2 stage 6 accens a gasolio tristadio Lo 3 stage Burner operating mode fuel train mod multi stage actua...

Страница 80: ...the fuel actuator 0F until the requested value is reached for example 8 see below for the ignition point or press F and to decrease the angle To set the air damper opening angle 0A in the ignition poi...

Страница 81: ...ner is operating warm setting by pressing the ENTER InFo or while the burner is in stand by mode cold setting by pressing ESC CAUTION at the first burner adjustment it is recommended to set the maximu...

Страница 82: ...the flue analyser Keep the air excess inside normal figures from 3 to 7 residual O2 operating by means for the air damper servomotor Keep increasing the air damper opening and then the gas throttle a...

Страница 83: ...t before end by pressing ESC or for a faulty shutdown the message OFF UPr Start preven tion will be diplayed until all the curvepoints will be set Note2 if the gas flow rate at high flame point maximu...

Страница 84: ...e than 5 seconds to process the curve downwards The curve is then a straight line go on checking the combustion values point by point change them if necessary and in case linearise the curve again Bef...

Страница 85: ...e burntime Ph72 travelling to postpurging Ph74 postpurge countdown is displayed Press ESC the parameter 546 Setting the maximum load is displayed Then press to exit the programming mode The display wi...

Страница 86: ...n Longer or shorter pushes on the button do not produce a reset so that the system maintains the lockout position Timeout for menu operation The time for automatically leaving the parameter setting le...

Страница 87: ...levels By means of a proper use of the keys it is possible to enter the various level parameters as shown in the following flow chart The burner and consequently the LMV2x are factory set the air and...

Страница 88: ...nd go back to the flashing number The Info level shows some basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _...

Страница 89: ...h another message Diagnostic code in the example diagnostic code 3 Record the codes and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event...

Страница 90: ...ht By pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for m...

Страница 91: ...ignition time OFF Ph44 t44 intervallo 1 t44 interval 1 Ph50 TSA2 secondo tempo sicurezza TSA2 2nd safety time Ph52 t52 intervallo 2 t52 interval 2 Ph60 Funzionamento 1 stazionario Operation 1 stationa...

Страница 92: ...ess ENTER until the display will show with the button go to the group 000 of the parameters and press with the buttons and go to 050 parameter press the disply show press again with the button select...

Страница 93: ...uttons by pressing enter to confirm iWith the buttons go to the group 000 of the parameters press end select the 050 parameter press the disply show with the button the display shows press again with...

Страница 94: ...50 ERROR CODE TABLE...

Страница 95: ...51...

Страница 96: ...52...

Страница 97: ...53...

Страница 98: ...54...

Страница 99: ...55...

Страница 100: ...56...

Страница 101: ...57...

Страница 102: ...58...

Страница 103: ...59...

Страница 104: ...60...

Страница 105: ...61...

Страница 106: ...62...

Страница 107: ...63...

Страница 108: ...64...

Страница 109: ...L PE QRB C N ION QRB C X75 1 X10 05 1 X10 06 1 X3 02 1 PLUFT FLAMME P L PE N L 2 3 L X5 03 1 X8 04 1 X8 02 1 X5 03 X10 05 X7 01 X8 04 X8 02 X75 X10 06 X3 02 X3 04 N PE L 1 1 1 1 1 1 1 1 1 QRA QRA QRA...

Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...

Страница 111: ...tion speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply 4 Feedback signal 3 PWM Pulse Width Modulation speed output 2 GND signal reference 1 External supply 24V DC ConnectorX75 Con...

Страница 112: ...dulation speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply ConnectorX75 ConnectorX64 ConnectorX74 2 Fuel meter input 1 Supply fuel meter ConnectorX5 02 Connections Pmax 4 Feedback...

Страница 113: ......

Страница 114: ......

Страница 115: ......

Страница 116: ...and data subject to change Errors and omissions excepted C I B UNIGAS S p A Via L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail...

Страница 117: ...IG FU B...

Страница 118: ......

Страница 119: ......

Страница 120: ......

Страница 121: ......

Страница 122: ......

Страница 123: ......

Страница 124: ......

Страница 125: ......

Страница 126: ......

Страница 127: ......

Отзывы: