How to interpret the burner’s “Performance curve”
To check if the burner is suitable for the boiler to which it must be installled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h / 860);
backpressure (data are available on the boiler’s ID plate or in the user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4mbar
In the “Performance curve” diagram (Fig. 2), draw a vertical line matching the furnace input value and an horizontal line matching the
backpressure value. The burner is suitable if the intersection point A is inside the performance curve.
Fig. 2
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15°C.
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Type
RG520
Model
G-. PR. S. *
*
. A.
(1)
(2) (3) (4) (5) (6)
(1) BURNER TYPE
RG91 - RG92 - RG93 - RG510 - RG515 - RG520 - RG525
(2) FUEL
G -
Light oil
(3) OPERATION
(Available versions)
PR -
Progressive
MD -
Fully modulating
(4) BLAST TUBE
S -
standard
L -
extended
(5) DESTINATION COUNTRY
* - see data plate*
(6) BURNER VERSION
A -
Standard
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
-1
0
1
2
3
4
5
6
7
8
100
200
300
400
500
600
700
800
900
Potenza kW
Contropressione in camera di
combustione mbar
A