13
Duct or pipe sensors
Installing temperature sensors
For measuring outlet air:
z
after delivery fan or
z
after coil to be controlled, at a distance of at least 0,5 m
For measuring room temperature:
z
before return air intake fan and near room's return air
intake. For measuring saturation temperature: after mist
eliminator.
Installing pressure sensors
A - installation on ducts carrying fluids at max. temperature
80°C
B - installation on ducts at temperature over 80°C and for refri-
gerants
C - installation on ducts at high temperatures:
z
increase length of siphon
z
place sensor at side to prevent it being hit by hot air
coming from the pipe.
Bend 0.4m sensor by hand (never use tools) as illustrated.
Installing differential pressure sensors for water
z
Installation with casing facing down not allowed.-With
temperature over 80°C, siphons are needed
z
To avoid damaging the sensor, you must comply with the
following instructions
when installing:
z
make sure pressure difference is not greater than the
value permitted by the sensor
z
when there are high static pressures, make sure you
insert shutoff valves A-B-C.
Putting into operation
start disable
1=open C1=open C
2=open A2=close B
3=open B3=close A
4= close C
Use whole cross-section of duct, min. distance from walls 50
mm, radius of curvature 10 mm for 2m or 6m sensors.
Installing combined humidity sensors
As max. humidity limit sensor on outlet (steam humidifiers).