C.I.B. UNIGAS
- M03956CR
5
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Specifications
*
NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
Type
P72
Model
M-. AB. S. *. A. 0. 50
(1)
(2) (3) (4) (5) (6) (7) (8)
(1) BURNER TYPE
P72
(2) FUEL
M - Natural gas
(3) OPERATION
Available versions
AB - Double stage
PR - Progressive MD - Fully modulating
(4) BLAST TUBE
S - standard
L - Extended
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A - Standard
(7) EQUIPMENT
Available version
0 = 2 valves
1 = 2 gas proving system
7 = 2 high gas pressure switch
8 = 2 gas proving high gas pressure switch
(8)GAS CONNECTION
40 = Rp1
1/2
50 = Rp2
65 = DN65 80 = DN80
BURNER TYPE
P60 M-...0.40
P60 M-...0.50
P60 M-...0.65
P65 M-....50
P65 M-....65
Output
min. - max. kW
160 - 523
160 - 800
160 - 800
270 - 970
Fuel
Natural gas
Category
see next paragraph
Gas flow rate
min.-max. Stm
3
/h
17 - 56
17 - 84.7
17 - 84.7
28.6 - 103
28.6 - 103
Gas pressure
min.-max. mbar
(see Note 2)
Electric supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
1.6
2
Fan motor
kW
1.1
1.5
Protection
IP40
Weight
kg
55
55
70
80
95
Operation
Double stage - Progressive - Fully modulating
Valves size/Gas connection
1"
1/2
/
Rp1
1/2
2"
/
Rp2
2"
1/2
/
DN65
2"
/
Rp2
2"
1/2
/
DN65
Operating temperature
°C
-10 ÷ +50
Storage TemperatureStorage
Temperature
°C
-20 ÷ +60
Working service*
Intermittent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
)
Note2:
Maximum gas pressure = 360mbar (with
Rp1"1/2 - 2" and Dungs MBDLE/MBC valves)
= 500mbar (with
DN65/80 and Siemens VGD / Dungs MBCvalves)
Minimum gas pressure = see gas curves.
PART I: INSTALLATION MANUAL