12
Duct or pipe sensors
Installing temperature sensors
For measuring outlet air:
after delivery fan or
after coil to be controlled, at a distance of at least 0,5 m
For measuring room temperature:
before return air intake fan and near room's return airintake. For
measuring saturation temperature: after mist eliminator.
Installing pressure sensors
A - installation on ducts carrying fluids at max. temperature 80°C
B - installation on ducts at temperature over 80°C and for refrigerants
C - installation on ducts at high temperatures:
increase length of siphon
place sensor at side to prevent it being hit by hot air coming from
the pipe.
Bend 0.4m sensor by hand (never use tools) as illustrated.
Installing differential pressure sensors for water
Installation with casing facing down not allowed.-With temperature
over 80°C, siphons are needed.
To avoid damaging the sensor, you must comply with the following
instructions
when installing:
make sure pressure difference is not greater than thevalue permitted
by the sensor
when there are high static pressures, make sure you insert shutoff
valves A-B-C.
Putting into operation
Start disable
1=open C1=open C
2=open A2=close B
3=open B3=close A
4= close C
Use whole cross-section of duct, min. distance from walls 50 mm,
radius of curvature 10 mm for 2m or 6m sensors.
Installing combined humidity sensors
As max. humidity limit sensor on outlet (steam humidifiers).
Содержание KPBY70
Страница 33: ...PART III OPERATION 33 FLUIDICS 12AG 90Kg h...
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 57: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 64: ...8 Parameters level heating engineer...
Страница 106: ...50 ERROR CODE TABLE...
Страница 107: ...51...
Страница 108: ...52...
Страница 109: ...53...
Страница 110: ...54...
Страница 111: ...55...
Страница 112: ...56...
Страница 113: ...57...
Страница 114: ...58...
Страница 115: ...59...
Страница 116: ...60...
Страница 117: ...61...
Страница 118: ...62...
Страница 119: ...63...
Страница 120: ...64...
Страница 122: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 142: ......
Страница 151: ......
Страница 152: ......
Страница 153: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 168: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 169: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 170: ...M12927CA MOUNTING 2...