6
ConF > Cntr
Parameter Value
Description
CtYP
controller type
1
2
1 = 3-position controller (open-stop-close only RWF50.2)
2 = continuative action controller (only RWF50.3)
CACt
control action
1
0
1 = heating controller
0 = cooling controller
SPL
least value of the
set-point range
-1999..
0
..+9999
set-point limitation prevents entry of values outside the defined
range
SPH
maximum value of the
set-point range
-1999..
100
..+9999
set-point limitation prevents entry of values outside the defined
range
oLLo
set-point limitation
start, operation limit
low
-1999
.... +9999
lower working range limit
oLHi
set-point limitation
end, operation limit
high -1999....
+9999
upper working range limit
(
bold
= factory settings)
ConF > rAFC
Activation boiler shock termic protetion:
RWF50.. can activate the thermal shock protection only on sites where the set-point is lower than 250°C and according
to
rAL
parameter.
Parameter Value
Description
FnCT
function
0
1
2
Choose type of range degrees/time
0 = deactivated
1 = Kelvin degrees/minute
2 = Kelvin degrees/hour
rASL
ramp rate
0,0 …
999,9
Slope of thermal shock protection (only with functions 1 and 2)
toLP
tolerance band ramp
0
…9999
width of tolerance band (in K) about the set-point
0 = tolerance band inactive
rAL
ramp limit
0
…250
Ramp limit. When this value is lower than the temperature set-
point, the RWF controls the output increasing the temp set
point step by step according to rASL. If this is over the temp set
point, the control is performed in cooling.
(
bold
= factory settings)
Содержание KPBY70
Страница 33: ...PART III OPERATION 33 FLUIDICS 12AG 90Kg h...
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 57: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 64: ...8 Parameters level heating engineer...
Страница 106: ...50 ERROR CODE TABLE...
Страница 107: ...51...
Страница 108: ...52...
Страница 109: ...53...
Страница 110: ...54...
Страница 111: ...55...
Страница 112: ...56...
Страница 113: ...57...
Страница 114: ...58...
Страница 115: ...59...
Страница 116: ...60...
Страница 117: ...61...
Страница 118: ...62...
Страница 119: ...63...
Страница 120: ...64...
Страница 122: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 125: ......
Страница 126: ......
Страница 127: ......
Страница 142: ......
Страница 151: ......
Страница 152: ......
Страница 153: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 168: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 169: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 170: ...M12927CA MOUNTING 2...