50
Adjusting the electrodes position
Adjust the electrodes position, according to the quotes shown on the next picture.
Fig. 28
Рис
. 29
Replacing the spring in the gas valve group
Cleaning and replacing the detection photocell
The photocell working life is about 10000 working hours (about 1 year), at max 50°C after
which it must be replaced.
To clean/replace the detection photocell, proceed as follows:
1
Disconnect the system from the electrical power supply.
2
Shut off the fuel supply;
3
remove the photocell from its slot (see next figure);
4
clean the bulbe if dirty, taking care not to touch it with bare hands;
5
if necessary, replace the bulb;
6
replace the photocell into its slot.
U
E
TG
Keys
E
electrodes
TA
air pipe
TG
ignition gas pipe
U
nozzle
TA
1
3
To replace the spring in the gas valve group,proceed as follows:
1
Carefully twist the protection cap 1 and the O-ring 2.
2
remove the “set value” spring 3 from housing 4.
3
Replace spring 3.
4
Carefully insert the new “set value” spring. Pay attention to mount pro-
perly. First insert the spring part with smaller diameter in the housing.
5
Place O-ring 2 in protective cap 1. Screw in the protective cap with the O-
ring in it.
6
Stick the adhesive label for spring identification on the type plate.
SKP Siemens actuator
Содержание HTP90A
Страница 33: ...33 Fig 16...
Страница 54: ...54...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ......
Страница 59: ......
Страница 61: ...LME73 000Ax PME73 831AxBC LME73 831AxBC Service instruction manual M12921CB Rel 1 2 02 2016...
Страница 83: ...23...
Страница 84: ...Note Specifications and data subject to change Errors and omissions excepted...