Siemens VGD valves with SKP actuator:
The pressure adjusting range, upstream the gas valves group, changes according to the spring provided with the valve group.
Once the train is installed, connect electrically all its elements: gas valves group, pressure switches, gas proving system.
Performance range (mbar)
0 - 22
15 - 120
100 - 250
Spring colour
neutral
yellow
red
ATTENTION:
once the gas train is mounted according to the diagram on Fig. 3, the gas proving test mus be performed,
according to the procedure set by the laws in force.
BS
BS
SKP1.
SKP2.
BS
BS
SA
SA
TP
D
SIEMENS VGD..MOUNTING
POSITIONS
2
(cap)
1
(spring)
Fig. 4