10 in order to get the maximum oil flow rate, adjust the pressure (reading its value on the
PG
pressure gauge) without changing the air flow
rate set during the gas operation adjustments (see previous paragraph): checking always the combustion parameters, the adjustment is to
be performed by means of the
SV2
adjusting cam screw (see picture) when the cam has reached the high flame position.
11 as for the point-to-point regulation in order to set the cam foil shape, move the oil low flame microswitch (cam IV) a little lower than
the maximum position (90°);
12 set the
TAB
thermostat to the minimum in order that the actuator moves progressively towards the low flame position;
13 move cam IV (oil low flame) towards the minimum to move the actuator towards the low flame until the two bearings find the adju-
sting screw that refers to a lower position: screw
V2
to increase the rate, unscrew to decrease, in order to get the pressure as
showed on chart/diagram on “Adjustment for light oil operation” on page 29, according to the requested rate.
14 Move again cam V towards the minimum to meet the next screw on the adjusting cam and repeat the previous step; go on this way
as to reach the desired low flame point.
15 The low flame position must never match the ignition position that is why cam
IV
must be set 20°- 30° more than the ignition posi-
tion.
16
Set cam V (“stroke limitation cam”) 5° higher than the lowest “low flame cam” (cam III or cam IV).
17 Turn the burner off; then start it up again. If the adjustment is not correct, repeat the previous steps.
18 Replace the actuator and control panel covers.