10
Configuration of INVERTER start / stop parameters and operating mode
Parameter
1.020
Min. frequency (Hz)
Minimum input frequency in Hz.
Set value = 0 Hz (LMV2x-3x / LMV5x)
Set value = > 35 Hz (ETAMATIC)
1.021
Max. frequency (Hz)
Maximum input frequency in Hz.
Set value = 51,5 Hz (LMV2x-3x / LMV5x)
Set value = 50 Hz (ETAMATIC)
1.050
Ramp 1
Braking time 1
Braking time at switch-off to reach the speed of 0 Hz after the start/stop contact has
opened (not used).
Set value = 10 seconds
1.051
Ramp 1
Acceleration time 1
Acceleration time 1 is the time necessary for the drive controller to accelerate from
0 Hz to maximum frequency (not used).
Set value = 10 seconds
1.052
Ramp 2
Braking time 2
Braking time at switch-off to reach the speed of 0 Hz after the start/stop contact has
opened.
Set value = 10 seconds
1.053
Ramp 2
Acceleration time 2
Acceleration time 2 is the time necessary for the drive controller to accelerate from
0 Hz to maximum frequency.
Set value = 10 seconds
1.054
Selects ramp used
Digital input 1 (
dig In1 / X5-6
) selects the ramp used.
Set value = 1 (parameters 1.052 and 1.053)
1.088
Quick stop
Not used but set.
Set value = 10 seconds
1.100
Operating mode
Frequency control mode: specifies the operating mode of the INVERTER. In our case it is
always frequency control (0).
Set value = 0
1.130
Reference set point
Determines the source from which the reference value is read.
In our case it is always analogue input AI1.
Set value = 1 (analogue input 1)
1.131
Enabling software
Depending on the change made, the motor may start immediately.
Selection of the source for enabling control.
Set value = 0
1.132
Start-up protection
Selection of behaviour in response to enabling software.
Set value = 1
(Start only with rising edge at input of control enable)
1.150
Motor rotation direction
Do not change this parameter. To invert the direction of rotation, invert 2 of the 3
INVERTER / MOTOR cabling wires, so that the INVERTERS always have the same
setting.
Set value = 1 forwards only / clockwise rotation
(no changes to direction of rotation are possible)
Содержание HTLX92R
Страница 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 64: ...8...
Страница 65: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 68: ...12 2 2 LMV5x program structure...
Страница 95: ...39...
Страница 102: ......
Страница 103: ......
Страница 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 106: ...Annex1 Example for motor cable...
Страница 107: ......
Страница 108: ...Annex 2 Example for sensor cable...
Страница 109: ......
Страница 110: ......
Страница 114: ......