PART III: OPERATION
28
4.4 Light oil operation
z
The fan motor starts and the pre-purge phase as well. Since the pre-purge phase must be carried out at the maximum air rate, the
control box drives the actuator opening and when the maximum opening position is reached, the pre-purge time counting starts.
z
At the end of the pre-purge time, the actuator is in the light oil ignition position: the ignition transformer is energised (lamp
B4
on);
the ignitor gas valves and the light oil valves open. Few seconds after the valves opening, the transformer is de-energised and
lamp
B4
turns off.
z
The burner is now operating, meanwhile the actuator goes to the high flame position; after some seconds, the two-stage operation
begins; the burner is driven automatically to high flame or low flame, according to the plant requirements.Operation in high or low
flame is signalled by LED
B2
on the burner control panel.
The fuel is pushed into the pump to the nozzle at the delivery pressure set by the pressure governor. The solenoid valve stops the fuel
immission into the combustion chamber. The fuel flow rate that is not burnt goes back to the tank through the return circuit. The spill-
back nozzle is feeded at constant pressure, while the return line pressure is adjusted by means of the pressure governor controlled by
an actuator coupled to an adjusting cam.