PART I: SPECIFICATIONS
7
1.2 Technical Specifications
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
1.3 Country and usefulness gas categories
BURNER TYPE
HRX515
Output
min. - max. kW
770 - 4400
Fuel
Natural gas - Light oil
Category
(
see next paragraph
)
Gas rate- Natural gas
min.- max. (Stm
3
/h)
81 - 466
PressureGas pressure
mbar
(
see Note 2
)
Light oil rate
min.-max. kg/h
65 - 371
Oil viscosity
2 - 7.4 cSt @ 40°C
Oil density
kg/m
3
840
Light oil train inlet pressure
bar max
2
Power supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
13
Electric motor
kW
11
Pump motor
kW
1.5
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
Valves size / Gas connection
50 / Rp2
Gas train 65
Valves size / Gas connection
65 / DN65
Gas train 80
Valves size / Gas connection
80 / DN80
Gas train 100
Valves size / Gas connection
100 / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service (*)
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
);
Note2:
Maximum gas pressure = 360mbar (with
Dungs MBDLE)
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
GAS
CATEGORY
COUNTRY
I
2H
AT ES GR SE
FI
IE
HU
IS
NO CZ DK GB
IT
PT CY EE LV
SI
MT SK BG LT RO TR CH
I
2E
LU
PL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2E( R ) B
BE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2L
NL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2ELL
DE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2Er